ML20210S933

From kanterella
Jump to navigation Jump to search
Forwards SER Re Auxiliary & Power Conversion Sys Branch Areas of Primary Responsibility.Review Includes All Amends Through Amend 17.Applicant Will Be Required to Provide Flood Protection to ECCS Pumps.W/O Encl
ML20210S933
Person / Time
Site: Satsop
Issue date: 06/17/1975
From: Tedesco R
Office of Nuclear Reactor Regulation
To: Deyoung R
Office of Nuclear Reactor Regulation
References
CON-WNP-1707 NUDOCS 8605290522
Download: ML20210S933 (2)


Text

w e

JUN 17 M DIsTn1EUTIos:

Dociet Fil;>s URR Rcading CS Fecdir.;-

APCSS Etading Docket Nos.

STN 50-503 S W 50-50?

MS 24-02

1. C. DeYoung, Assistant Director for Light Water East. tors Croup 1. EL SAFETT EVALUATION REPORT Plant Name: WFPSS Nuclear Project Mo. 3 and No. 5 Licensing Stage: CP Docket Numbers:

ST'I 50-508; STN 50-509 Responsible Eranch: INR 1-3 Project Mannt.er:

P. D. O'Reilly Requested Completion Dato: June 16, 1975 The enclosed Safety Evaluation Report covere areas of the PCA'. fi'r which the Auxiliary and Power Conversien Systees Eranch bas primry respansibility.

The review includes all amendments through Amendo.cnt 17.

The following areas have not been resolved:

(1) Section 9.1.1, Spent Tuc1 Storage -

f O*9i' "iII b" The present PSAR states that a maximun Ed naintained under any credibir_ conditims. fWe will require the applicant to confirm that a ruxinm K of 0.95 vill te wain-tained under the conditions when the Ehit fuel is fico*cd by unborated water. The applicant has s.cated verbally tM the 0.93 valve might be fa error and is Jookinr. into it.

(2) Section 9.3.3, Equitynent and Floor Irrainare ?yAt?P. -

The present PSAR st.ates that the ECC', puty rooms are locate.1 on the lowest level (330 f t. clevation) cf the rcactor auxiliary building.

The sumps and susp pmens in the area are net Es. signed fc,r flooding. We are cencerned with the potential of flooding of i

both ECCS pump rooms due to a postulated rupture of a non-seiseic Category I fluid system inside the reactor auxiliary building. We vill traquire the applicant to provide flood protection to these ECCS pumps.

.Frie s

  • evemama >

DATE M Fora AEc.318 (Rev. 9 53) AECM 0240 W u e.novsaneenwr Pasatine orrecas een.sas.ies 8605290522 750617 PDR ADOCK 05000508 F

PDR

3*

1 JUN 171975 E. C. L:Youar

_2_

(3) Section 9.5.1, Fire Protection System -

The present system design criteria and design bases do not provide any means of leaksge detections for the Ralon 1301 flooding system in the cable vaults and cable chases adjacent to the control room area. Ve will require the applicant to provide means of Balon leakage detectors and alarus or the results of an analysis to demonstrate that the control rootn operators and the personnel in other essential manned areas will be protected from Halen and its pyrolytic dacorposition products fdr all conditions including fire, inadvertent actuation and leaks.

We will report on the resolution of these probler.s in supplenents to this report.

In Amendment 17 we have received the applicant's response to our questions regarding possible feedwater flow instability. We will revi m the information provided as a post-CP ite:a.

With the exception of the above, we find the proposed systees acceptabic in the stated areas.

Original Signed by:

Robert L Tedesco Robert L. Tedesco, Assistant Director for Containment Safety Division of Technieni Reviev Office of Nuclear Reactor 2es:ulation I'nclosure:

As Stated cc S. Uanauer. TA i

l W. Mcdonald, MIPC A. Gianhusso, RL F. Schroeder, TR

0. Parr, RL l

V. Benareya, APCSB l

P. O'Reilly, RL i

D. Fischer, APCSD

(

P. Matthews, APCSB l

S. Varga, RL J. Clynn, CS l

C. Liang, APCSB l

D. Eisenhut, ERR or rec s

  • TR CS:APCSB- -TR:CS;APCSB-- --TR:CS : AFCSB - -- H;CS i

C.Liant:me"~

P;Marthews~

~~T3enareye-R.7edesco-l oats >

Form AEC 313 (Rev. 9 53) AECM 0240 W u. s. eovananment enintime orrics so?4.sas. nee l

.