i p/t6 PRIO2rry gg ggg gaujuu O CommonwealthEdison

' h te W

Quad Cities Nuclear Power Station fiFz w>z 22710 206 Avenue North 4

Corcova. lilinois 61242 g

Telephone 309/654-2241

[R g

Z L

um RAR-86-07 IIL Q May 2, 1986 lilinois Environmental Protection Agency Division of Water Pollution Control Comptiance Management Unit 2200 Churchill Road Springfield, Illinois 62706 U.S. Environmental Protection Agency Region V, Enforcement Division At ten ti on:

Chief, Compliance Unit 230 South Dearborn Street Chicago, Illinois 60604 Subj ect:

NPDES Non-Compliances for Quad-Cities Generating Station IL-0005037

)

Dear Sirs:

in accordance with Standard Condition 12, we wish to submi t the following notice of non-compliances:

DISCHARGE: 005 Sani tary Treatment Plant PARAMETER AND PERMIT LIMIT:

Total Suspended Solids - Daily Maximum 60 ppm, Monthly Average 30 ppm Requi red 2/ month NON-COMPLIANCE AND DATE:

005 Sani tary Treatment Plant TSS averaged 33 ppm / month for April, 1986.

CAUSE:

Hydraulic overloading of the system caused the bio-mass to wash off the filter media in the trickling filter.

CORRECTIVE ACTION:

Plans are to remodel existing facilities to handle larger loads or replace existing facilities with new system sized to handle larger loads.

If there are any questions, please call Ray Moore of my staf f at 309-654-2241, extension 2731.

Sincerely, D

R. A. Ro'oet Servi ~ces Superin tendent Quad-Cities Station y,

j RAR/RM/tlf

'fD cc:

J. Keppler - NRC

, ;, y 3tp 8605140229 860502 PDR ADOCK 05000254 S

PDR A