ML20210N015
| ML20210N015 | |
| Person / Time | |
|---|---|
| Site: | Susquehanna |
| Issue date: | 04/28/1986 |
| From: | Fields J PENNSYLVANIA POWER & LIGHT CO. |
| To: | Koval P PENNSYLVANIA, COMMONWEALTH OF |
| Shared Package | |
| ML20210N018 | List: |
| References | |
| PLE-8259, NUDOCS 8605020432 | |
| Download: ML20210N015 (2) | |
Text
i
.n.
$h Pennsylvania Powcr & Light Company Two North Ninth Street
- Allentown, PA 18101 e 215 / 770L5151 1
April 28, 1986 Mr. Paul Koval Chief, Operations Section Bureau of Water Quality Management Pennsylvania Department of Environmental Resources 90 East Union Street, Second Floor Wilkes-Barre, PA 18701-3296 SUSQUEHANNA STEAM ELECTRIC STATION DISCHARGE MONITORING REPORT NPDES PERMIT NO PA 0047325/ MARCH 1986 CCN 741326 FILE R9-8A PLE-8259
Dear Mr. Koval:
).
Enclosed is a copy of the March 1986 Discharge Monitoring Repart for Permit No. PA 0047325.
The following information details data and/or 3
noncompliances for some of the permitted oc t. falls:
Outfall 071:
Cooling Tower Blowdown Discharge flows were estimated.
Outfall 072: S & A Building Sump There were two discharges from this outfall in March with the monthly average for total suspended solids (TSS) of 69 mg/1.
The high levels of solids were attributed to parking lot runoff.
See Note 2 on Outfall 072 DMR.
I b
R 8
y
/
p Mr. P. Koval 1
PLE-8259
}
CCf4 741326 File 012-4 April 28, 1986 e
Page two Outfall 271 - Low Volume Waste Filter Bypass:
This outfall was diverted on March 21, 1986, to the sewage treatment plant with Pennsylvania Department of Environmental Resources approval. A TSS sample collected on March 21, 1986, however was 53.4 mg/l exceeding the monthly average of 30 mg/1.
I If you have any questions, please call me at (215) 770-7889.
i Respectfully yours, s
4 Jerome S. Fields Senior Environmental Scientist - Nuclear i
JSF/msh 1
(
Enclosure l
cc: EPA, Region III E.Adensam-NRCt/