NPDES Noncompliance Notification:On 870128,fecal Coliform Greater than 400 colonies/100 Milliliters.Caused by Very Low Flow in Chlorinator Tablet Tube Spacers.Spacers Removed from Tablet Tubes to Allow for Low Flow
ML20210H574
Person / Time
Site: Quad Cities  Constellation icon.png
Issue date: 01/30/1987
From: Robey R
COMMONWEALTH EDISON CO.
To:
ENVIRONMENTAL PROTECTION AGENCY, ILLINOIS, STATE OF
References
RAR-87-6, NUDOCS 8702110445
Download: ML20210H574 (2)


Text

.

a

't Mf6 ouad Cities Nuclear Power Station O Commonwealth Edison 22710 206 Avenue North Cordova. lilinois 61242 Telephone 309/es4-2241 January 30, 1987, RAR-87-6 UI.IJ C'ihe J

p Sy 3 Illinois Environmental Protection Agency 4 fy(

Division of Water Pollution Control U:L <

Compliance Management Unit 0% 7 (dLp 2200 Churchill Road m-Springfield, Illinois 62706 &

U.S. Environmental Protection Agency

._flLEA' _'S ,

Region V, Enforcement Division Attention: Chief, Compliance Unit 230 South Dearborn Street Chicago, Illinois 60604

Subject:

NPDES Non-Compliances for Quad-Cities Generating Station IL-0005037

Dear Sirs:

In accordance with Standard Condition 12 we wish to submit the following notice of non-compliances:

DISCHARGE: 005 Sanitary Treatment Plant PARAMETER AND PERMIT LIMIT: Fecal Coliform 400 colonies / 100 ml NON-COMPLIANCE AND DATE: Fecal Collform > 400 colonies / 100 ml on January 28, 1987 Too Numerous To Count (T.N.T.C.)

CAUSE: The chlorinator tablet tubes have spacers in the bottom of them to control Cl concentration. Very low flow caused the effluent not to come in contact with the tablets. A concentration was 0.4 ppm on the day of the non-compi1 ante.

CORRECTIVE ACTION: Removed spacers from both tablet tubes to allow for low flows, no pumps on, to come in contact with tablets to maintain adequate Cl residual.

If there are any questions, please call Ray Moore of my staff at 309-654-2241, Extension 2731.

Sincerely, vb ['

ichard A. Robe Services Superintendent '

Quad-Cities cc: J. Keppler, NRC Director of Water Quality, j

Environmental Affairs  %

0210R 8702110445 070130 PDR S ADOCK 05000254 FEB -

PDR " I987

F

.s u . .

February 2,1987 Attached please find the corrected copy of the NPDES Non-Compliances for Quad-Cities Generating Station letter number RAR-86-42. The letter number was assigned in the 1986 book by mistake -- therefore it had to be re-numbered.

Please replace your copy of the letter with the one attached -- RAR-87-6.

b A