- _ _

j Wisconsin Electnc m coumr 231 W. MICHIG AN, P.O. 80X 2046, MILWAUKEE, WI S3201 (414)277-2345 VPNPD-87-99 March 11, 1987 FEDERAL EXPRESS Mr. Giuliano DeGrassi Department of Nuclear Energy BROOKHAVEN NATIONAL LABORATORY Building 129, 60 Cornell Street Upton, New York 11973

Dear Mr. DeGrassi:

ENERGY ABSORBER INFORMATION l

POINT BEACH NUCLEAR PLANT Per your verbal request on March 6, 1987, we are transmitting l

the following information related to the use of energy absorbers on the main steam dump system at Point Beach Nuclear Plant.

1)

Bechtel Specification 10447-042(Q), Revision 0, Technical Specification for Energy Absorbers, which includes Fabrication / Assembly Drawings 7409, Revision A and 7410, Revision A.

2)

Bechtel Calculation E10447-1, Revision 0, Fatigue Evaluation I

of Energy Absorbers, Point Beach Nuclear Plant.

3)

Procedure NDE-750,' Revision 5, Visual Examination of Nuclear Power Plant Components.

l We proposed to include the energy absorbers in our ISI program on the following basis:

1)

Energy absorbers will be given a VT-3 examination on an annual basis for a period of 3 (three) years after initial installation.

2)

After 3 (three) years, the energy absorbers will be placed on a rotating ISI program such that each one receives a VT-3 examination within a 10-year period.

Assuming only the 5 (five) energy absorbers covered by our current application are installed at PBNP - Unit 1, this means that at least one energy absorber would be inspected every two years to identify any generic design or operability problems.

N\\

8703200019 B70311 I

g\\g g) {$dk{ggj PDR ADOCK 05000266 G

PDR

\\

r j..

Mr. Giuliano DeGrassi

' March 11, 1987' Page 2 Ldescribes Wisconsin l Electric's VT-3 examination procedures including personnel qualifications, methods, examination,-interpretation, and documentation' requirements.

Weltrust that-this. submittal.will' provide you the1information.

necessary for you to complete your SER.-

We request'that

' Attachment'l be returned to WE after your review since the

'information is considered proprietary by Bechtel.

-Very truly yours,

/

[

C. - W.

Fay Vice President

. Nuclear Power.

Enclosures.

4,-C6py.to Mr. George Lear, Project DirectorL(w/o/e)

PWR Project Directorate 1 c -.

-