Corrected Amend 118 to License NPF-3,consisting of Tech Spec Page 3/4 3-28 Re Steam & Feedwater Rupture Control Sys Instrumentation Trip Setpoints
ML20207P073
Person / Time
Site: Davis Besse 
(NPF-03-A-118, NPF-3-A-118)
Issue date: 10/13/1988
From:
NRC
To:
Shared Package
ML20207P075 List:
References
NUDOCS 8810200056
Download: ML20207P073 (2)


Text

'

)

i l

TABLE 3.3-11 (Continued)

TABLt NOTATION

  • May be bypassed when steam pressure is below 650 psig.

Sypass shall be automatically removed when the steam pressure exseeds 650 psig, i The previsions of Specification 3.0.4 are not applicable.

ACTION STATEMENTS ACTION 13 - With the number of OPERABLE Channels one less than the Total Nurser of' Channels, startup and/or power operation may proceed until performance of the next required CHANNEL FUNCTIONAL TEST provided the inoperable sec-tion of the channel is placed in the tripped condition within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />.

ACTION 14 - With the number of OPERABLE Channels one less than the Total Number of Channels, restore the inoperable channel to 0.PERABLE status within 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN

)

within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

i f

DAVIS-BESSE. UNIT 1 3/4 3-27 Amendment te. 37 0810200056 881013 PDR ADOCK 05000346 P

PDC

A.,

)

2 5

s

?

E E

TABLE 3.3-12 I

l T

STEAM AND FEEDWATER RUPTURE CCNTRO'. SYSTEM g

INSTRUMENTATION TRIP SETPOINTS FUNCTIONAL UNITS TRIP SETPOINTS ALLOWABLE VALUES 1.

Steam Line Pressure - Low 1 591.6 psig 1 591.6 psig*.

h 586.6 psig**

2.

Steam Generator Level - Low (I}

2 16.4" 1 15.6"*

_ 12.9"**

3.

Steam. Generator Feedwater Differential Pressure - High (

$ 197.6 psid i 197.6 psid*

w4

-< 199.6 psid**

co 4.

Reactor Coolant Pumps - Loss of High $ 1354.6 amps

$ 1384.6 ampsi Low 1 106.5 amps 1 106.5 ampsi l

l l

(1) Actual water level above the lower steam generator tubesheet.

l l

2) Where dif ferential pressure is steam generator minus feedwater pressure.

p E

  • Allowable Value for CHANNEL FUNCTIONAL TEST
    • Allowable Value for CHANNEL CALIBRATION
  1. Allowable Value for CHANNEL FUNCTIONAL TEST and CHANNEL CALIBRATION

~