ML20207K913

From kanterella
Jump to navigation Jump to search
Safety Evaluation Supporting Amend 25 to License NPF-49
ML20207K913
Person / Time
Site: Millstone 
Issue date: 10/03/1988
From:
Office of Nuclear Reactor Regulation
To:
Shared Package
ML20207K907 List:
References
NUDOCS 8810170077
Download: ML20207K913 (2)


Text

. - _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ - _ _ _ _ _ _ _ _ _ _ _ _ - _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ - _ _ _ _ _ _ _ _ - _ _ _ _ _ _ _ _ _ _ _ _ _ - _ _ _ _ _ _

  1. pa %q'o UNITED STATES

{

s m [,f l'

NUCLE AR REGULATORY COMMISSION r

WASHINGTON D. C. 20S55 s,;

f

+.....

E A F E T Y EJ,A L,U,A,T I,0 N,,B,Y,1,b,E, O FfJ C E, O F, p,U,C L,E,A,R,,R E A,C,T 0 R,,R,E,G,0,L A,TJ,0p RELATED TO AHENOMENT NO, 25 T0 F ACl_LJ,T,Y,,0f E,PA,TJp,G,,LJ,CEp,5J, p,0,, pPF,,4,9 h,Cf.T,F.E,A,S,T, p,0,C L,E,A,R, Jp E R G,Y,,CCP,P ANY,, E.T,A!.,.

P ! L L S T O h,E,,h,0,C L E,A R,,P,0,W E R,,5T,A,TJ,0,N,,

0,N,1,T,,N 0,.,,3 DOCKET NO, 50 423 J NTf,0, DUCTION By application for license arendnent dated June 21,19PP, Northeast Nuclear Energy Corpany (NNFCC) proposed changes to Pillstone Unit 3 Technical Specification (TS) 3/4,7,la, "Air Temperature Ponitoring," to redefine the terperature zer.es inside certainrent and establish temperature litrits for these zones as listed in Table 3,7-6, DJ,5.C}!55J,0f(,AND, EV,AL,UAT10N License condition T.C(3) in the Pillstere Unit 3 Operating License NPF-49 requires that, "Frior to start-up follcwing the first refueling cutage. the qualified life of electrical equipent within tre scope of 10 CFP 50,49 located inside containnent sball be recalculated based on the actual tcrperature tonitcred inside certaior(et during the first cycle of operation " License Condition ?,C(3) was satisfied by the licensee by submittal of a report dated January 21, 19FP, The June 21, 19FP application would incorporate the conclusion of the January 01,19C8 report into TS 3/4,7,14 which ccntains terperature lir11ts, and assnciated reredial requirwents, and furveillarce Requirererts, for varicus plant areas that contain tenperature sensitive, safety related, electrical equiprent.

Exceeding the tenperature limits of TS 3/4,7,14 could affect the qualified lifetine of safety-related electrical equiprent as defined "i

ir 10 CFR 50,49, "Environmental qualificatico of electric equipent irpertant te safety fer ruclear power plarts,"

At the present tine. TS 3/4,7.14 defines two tenperature zeres within containrent:

(1) Zone C-01. "Inside Crare Wall - All Elevations," ard (t)

Ione C-02 "Outside Crane Wall - All Elevations." Both C-01 and C-02 have Q

ten perature lirnits of 120"F, The preposed change to TS 3/4,7,14 would PWS establish fcur contairment terpera*ure zores, containing equiprent presently i

8, '

located in Zeres C-01 and C-00, as follcws:

So

  • CS-01. "Inside Crane Wall - all elevations except CS-03 ard CS-04"

^

CS-02, "Cutside Crane Wall all elevatiens" M

CS-03 "Pressurizer Cubicle all elevations" CS-04, "Inside Crare Wall - elevatics 51'4" except CS-03 and m a n, steam generator enclosures"

1 i

b 4 I

Tenperature limits for Zones C-01, C-02 and C-C4 would be 120*F. The i

temperature limit for Zone C-03 would be 130*F.

The licensee has recalculated 1

the qualified lifetire of safety related electrical equiptent in Zone C 03 I

with acceptasle results as described in the licensee's submittal dettd i

j January 21, 1988.

We have completeo our evaluation of the licensee's January 21, 1988 submittal concerning the qualified life of the equipoent affected by the higher than predicted ter peraturc.

The new qualified life is in accordance with the guice-lines of t;UREG-0$F8 and ![EE standard 323-1974 The staff has reviewed all

{

the information provided in the licensee's letter dated January (21,1968 and finds that the licensee h65 satisfied the license condition 2.C 3) by reestablishing the qualified life of all affected equipment in an acceptable manner. Accordingly, the proposed change to the TS which ir.corporates the i

i results of the licensee's January 21, 1988 submittalintoTS3/4.7.14,is j

acceptable.

ENVIRCM1 ENTAL CONSIDERATION 1

r i

This amendment changes a recuirement with respect to installation or use of a facility component located within the restricted area as defined in 10 CFR l

part 20. The staff has determined that the arendment involves no significant i

increase in the arnounts and no significant change in the types, of any effluents thatraybereleasedoffsite,andthatthereisnosignificantincreasein individual or curulative occupational radiation exposure.

The Comission bas i

l previously published a proposed findirs that the arnendment involves no significant hazards consideration and there has been no public ccreent on such t

finding.

Accordingly, the arendment meets the eli i

categorical exclusion set forth in 10 CFR 51.22(c)gibility criteria for (9).

Pursuant to 10 CFR 51.22(b), no environmental impact statement or environmental assessrent need be prepared in connection with the issuance of the amendnent.

l CONCLUSION j

t We have concluced, based on the considerations discussed above, that (1) there is reasonable assurance that the health and safety of the public will not be l

er. dangered by operation in the proposed manner, and (2) such activities will be conducted in corpliance with the Comission's regulations, and the issuance of l

l the amencrent will not be inimical tn the cormon defense and security or to the t

I health and safety of the public.

l 1

i I

tra ted: October 3, 1988 l

]

principal Contributor:

1 O. H. Jaffe r

}

t i

l

- - - - -