Text
__
ut:o UNITED STATES y
g j
NUCLEAR REGULATORY COMMISSION 2
WASHINGTON. D.C. 2080641001 V...../
ENTERGY GULF STATES. INC. "
AND ENTERGY OPERATIONS. INC.
p_QQKET NO. 50-458 RIVER BEND STATION. UNIT 1 i
~
AMENDMENT TO FACILITY OPERATING LICENSE l
Amendment No.103 License No. NPF-47 1.
The Nuclear Regulatory Commission (the Commission) has found that:
A.
The application for amendment by Entergy Gulf States, inc? (the licensee) dated September 23,1998, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Cornmission's rules and regulations set forth in 10 CFR Chapter I; B.
The facility will operate in conformity with the application, as amended, the provisions of the Act, and the rules and regulations of the Commission; C.
There is reasonable assurance: (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations; D.
The issuance of this license amendment will not be inimical to the common defense and security or to the health and safety of the public; and
- EOI is authorized to act as agent for Entergy Gulf States, Inc, and has exclusive responsibility and control over the physical construction, operation and maintenance of the facility.
"Entergy Gulf States, Inc., has merged with a wholly owned subsidiary of Entergy Corporation.
Entergy Gulf States, Inc. was the surviving company in the merger.
i 9903170004 990303 PDR ADOCK 05000458 p
4
?
.g.
l E.
The issuance of this amendment is in accordance with 10 CFR Part 51 of the l
Commission's regulations and all applicable requirements have been satisfied.
j 2.
Accordingly, the license is amended by changes to the Technical Specifications as Indicated in the attachment to this license amendment; and Paragraph 2.C.(2) of Facility l
j Operating License No. NPF-47 is hereby amended to read es follows:
f (2)
Technical Soecifications and Environmental Protection Plan
]
The Technical Specifications contained in Appendix A, as revised through j
i Amendment No.103 and the Environmental Protection Plan contained in l
Appendix B, are hereby incorporated in the license. EOl shall operate the facility j
in accordance with the Technical Specifications and the Environmental l
Protection Plan.
3.
The license amendment is effective upon the date of issuance and shall be implemented j
within 90 days.
I FOR THE NUCLEAR REGULATORY COMMISSION j
i i
obert J. Fretz, Project Manager Project Directorate IV-1 i
Division of Licensing Project Management Office of Nuclear Reactor Regulation
Attachment:
Changes to the Technical
]
Specifications Date of issuance: March 3, 1999 l
l i
}
j
.j l
2
.i b
s d
e 1
L l
i
.u-2
j ATTACHMENT TO LICENSE AMENDMENT NO.103
)
FACILITY OPERATING LICENSE NO. NPF-47 4
DOCKET NO. 50-458 1
l Replace the following pages of the Appendix A Technical Specifications with the attached pages. The revised pages are identified by Amendment Number and contain marginallines indicating the areas of change.
REMOVE INSERT 3.8-34 3.8-34 B 3.8-67 B 3.8-67 B 3.8-68 B 3.8-68 3
i 1
i
..~
.. _ ~ _.. ~
~
~. - -.
l a
' Battery Cell Parameters-3.8.6 i
!.j Table 3.8.6-1 (page 1 of 1)~
Battery Cell Parameter Requirements j
l q
CATEGORY A:
LIMITS FOR EACH CATEGORY B:
CATEGORY C:
l DESIGNATED PILOT lit 1ITS FOR EACH LIMITS FOR EACH' PARAMETER CELL CONNECTED CELL-CONNECTED CELL
+
Electrolyte
> Minimum level
> Minimum level.
Above, top of-Level indication mark.
indication mark, plates, and not and s 1/4 inch and s 1/4 inch overflowing above raaximum above maximum level indication level indication mark (a) mark (a)
Float Voltage 2 2.13 V 2 2.13 V 2 2.07 V Specific 2 1.200 2 1.195 Not more than 0.020 Gravity (b)(c) below average of M
all connected. cells Average of all M
connected cells 2 1.205 Average of all connected cells a 1.195 (a)
It is acceptable for the electrolyte level to temporarily increase ~above.
the specified maximum level during equalizing charges provided it is' not overflowing.
(b) Corrected for electrolyte temperature and level.
Level correction is not required, however, when battery charging is < 2 amps when on float charge.
(c) A battery charging current of < 2 amps when on float charge is acceptable for meeting specific gravity limits following a battery recharge, for a maximum of 31 days.When charging current-is used to satisfy specific gravity requirements, specific gravity of each connected
-cell shall be measured prior to expiration of the 31 day allowar.ce.
RIVER BEND 3.8-34 Amendment No. Bl.103 l
,_m _,
Battery Cell Parameters
'B 3.8.6 BASES SURVEILLANCE Table 3.8.6-1 (continued) it is not overflowing. These limits ensure that the plates suffer no physical damage. and that adequate electron-transfer capability is maintained in the event of transient -
conditions. IEEE-450 (Ref. 3) recommends that electrolyte level readings should be made only after the battery has been at float charge for at least 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />.
The Category A limit specified for float voltage is 2.13 V per cell. This value is based on the recommendation of IEEE-450 (Ref. 3), which states that prolonged operation of cells below 2.13 V can reduce the life expectancy of cells.
The Category A limit specified for specific gravity for each pilot cell is 1.200 (0.015 below the manufacturer's fully 3
charged nominal specific gravity). This value is characteristic of a charged cell with adequate capacity.
According to IEEE-450 (Ref. 3), the specific gravity readings are based on a temperature of 77 F (25 C).
The specific gravity readings are corrected for actual electrolyte temperature and level. For each 3 F (1.67 C) above 77 F (25 C). 1 point (0.001) is added to the reading:
1 point is subtracted for each 3 F below 77 F.
The specific gravity of the electrolyte in a cell increases with a loss of water due to electrolysis or evaporation. Level correction will be in accordance with manufacturer's recommendations.
Category B defines the normal parameter limits for each connected cell. The term " connected cell" excludes any battery cell that may be jumpered out.
The Category B limits specified for electrolyte level and float voltage are the same as those specified for Category A j.
and have been discussed above. The Category B limit specified for specific gravity for each connected cell is l
1.195 (0.020 below the manufacturer's fully charged, nominal specific gravity) with the average of all connected cells l
1.205 (0.010 below the manufacturer's fully charged, nominal specific gravity). These values are based on manufacturer's (continued)
RIVER BEND B 3.8 67 Revision No. 1
~
Battery Cell Parameters B a.8.6
)
BASES j
SURVEILLANCE Table 3.8.6-1 (continued)
REQUIREMENTS
' recommendations. The minimum specific gravity value required for each cell ensures that the effects of a highly charged or l
newly installed cell do not mask overal' degradation of the battery.
Category C defines the limit for each connected cell. These j
values, although reduced, provice assurance that sufficient v
capacity exists to perform the intended function and maintain a margin of safety When any battery parameter is outside the Category C limit, the assurance of sufficient capacity described above no longer exists, and the battery must be l
declared inoperable.
The Catetory C limit specified for electrolyte level (above the top of the plates and not overflowing) ensures that the i
i plates suffer no physical damage and maintain adequate electron transfer capability. The Category C limit for float i
voltage is based on IEEE-450 (Ref. 3), which states that a i
cell voltage of 2.07 V or below, undar float conditions and -
not caused by elevated temperature of the cell, indicates l
internal cell problems and may require cell replacement.
i 1
The Category C limit of average specific gravity is based on 4
manufacturer's recommendations (0.020 below the manufacturer's recomended fully charged, nominal specific gravity). In addition to that limit, it is required that the specific gravity for each connected cell must be no less than 0.020 below the average of all connected cells. This limit ensures that the effect of a highly charged or ne, cell does not mask overall degradation of the battery.
l t
i The footnotes to Table 3.8.6-1 that apply to specific gravity j
are applicable to Category A, B, and C specific gravity.
l 4
Footnote b in Table 3,8.6-1 requires the above mentioned-l correction for electrolyte level and temperature, with the exception that level correction is not required when battery 1
charging current is < 2 amps on float charge. This current 3
provides, in general, an indication of overall battery
~
condition.
(continued) l l
RIVER BEND B 3.8-68 Revirion N3 1 l