Summary of 861203 Meeting W/Util in Bethesda,Md Re Steam Generator Tube Insp.List of Attendees & Util Presentation Encl
ML20207H611
Person / Time
Site: Millstone 
Issue date: 12/22/1986
From: Jaffe D
Office of Nuclear Reactor Regulation
To: Thadani A
Office of Nuclear Reactor Regulation
References
NUDOCS 8701070575
Download: ML20207H611 (40)


Text

{{#Wiki_filter:, o DEC 2 21986 Docket No. 50-336 MEMORANDUM FOR: Ashok C. Thadani, Director PWR Project Directorate #8 Division of PUR Licensing-B FROM: D. H. Jaffe, Project Manager PWR Project Directorate #8 Division of PWR Licensing-B

SUBJECT:

SUMMARY

OF THE DECEMBER 3, 1986 MEETING WITH NORTHEAST NUCLEAR ENERGY COMPANY (NNECo) TO DISCUSS STEAM GENERATOR TUBE INSPECTION On December 3, 1986, representatives of NNEco and the NRC staff met in Room P-412 in the Phillips Building, Bethesda, Maryland. The purpose of the meeting was to hear a presentation by NNECo concerning the recent steam generator tube inspection at Millstone Unit 2. A list of attendees is shown in Enclosure 1. The staff had requested that NNECo provide a presentation concerning the Millstone Unit 2 steam generator tube inspection as a result of early indications which seemed to be significant. The NNECo presentation is summarized in Enclosure 2. The main points of the presentation were as follows: o Improvements in eddy-current test (ECT) techniques resulted in positive definition of distorted indications located near the top of the tubesheet, and identification of an increased number of flaws. o Essentially all pits continue to be related to sludge / deposit build-up located in the region above the tubesheets. o Countermeasures are apparently successful in reducing or arresting pitting: Copper continues to be removed from the condensate /feedwater system. During the outage, the main condenser was retubed with titanium. Improved chemistry control / reverse osmosis during Cycle 7 was beneficial. Chemical cleaning during the 1985 refueling outage was also beneficial. o An order of magnitude defect reduction (2366 to 246) was observed. o No significant pit growth appeared to be taking place. k[ [ O J

o Meeting Summary o Batwing region defects seemed to be anomalous, apparently isolated occurrence in three tubes. o Dent progression is minimal; NNECo expects complete arrest in the near future as a result of countermeasures including those listed above. o A total of 245 tube ends received sleeves. o A total of nine tubes were plugged. In conclusion, NNECo appeared quite positive regarding the results of the inspection and seemed to feel that their steam generator program was yielding pcsitive results. No outstanding issues resulted from the meeting. crigmal agr*1 Dy D. H. 'Jaffe, Project Manager PWR Project Directorate #8 Division of PWR Licensing-B

Enclosures:

As stated cc w/ enclosures: See next page [s [ j PBD#8, PBD7s PBD# PK' vdzer DJafN AThadani l'r2//[/86 12/(//8 12/11/86 l /

Mr. John F. Opeka Millstone Nuclear Power Station Northeast Nuclear Energy Company Unit No. 2 cc: Gerald Garfield, Esq. Mr. Wayne D. Romberg Day, Berry & Howard Superintendent Counselors at Law Millstone Nuclear Power Station City Place P. O. Box 128 Hartford, Connecticut 06103-3499 Waterford, Connecticut 06385 Regional Administrator, Region I Mr. Edward J. Mroczka U.S. Nuclear Regulatory Commission Vice President, Nuclear Operations Office of Executive Director for Northeast Nuclear Energy Company Operations P. O. Box 270 631 Park Avenue Hartford, Connecticut 06141-0270 King of Prussia, Pennsylvania 19406 Mr. John F. Opeka, Senior Vice President Mr. Charles Brinkman, Manager Nuclear Engineering and Operations Washington Nuclear Operations Northeast Nuclear Energy Company C-E Power Systems P. O. Box 270 Combustion Engineering, Inc. ,Nartford, Connecticut 06141-0270 7910 Woodmont Avenue Bethesda, Maryland 20814 Mr. Lawrence Bettencourt, First Selectman Town of Waterford Hall of Records - 200 Boston Post Road Waterford, Connecticut 06385 Northeast Utilities Service Company ATTN: Mr. Richard R. Laudenat, Manager Generation Facilities Licensing Post Office Box 270 Hartford, Connecticut 06141-0270 Kevin McCarthy, Director Radiation Control Unit Department of Environmental Protection State Office Building Hartford, Connecticut 06106 Mr. Theodore Rebelowski U.S. NRC P. O. Box 615 Waterford, Connecticut 06385-0615 Office of Policy & Management ATTN: Under Secretary Energy Division 80 Washington Street Hartford, Connecticut 06106

' ~ LIST OF ATTENDEES NNECo N. Azevedo J.-Benson. J. Fackelmann E. Perkins NRC G. Brown-ACRS C. Y. Cheng . D. Crutchfield D. Jaffe L. Marsh G. Staley M. Wegner R. Wright I a l 1

as .r d 1- -L 1a ,m A 1-i NORTHEAST NUCLEAR ENERGY COMPANY MILLSTONE UNIT NO. 2 [ DOCKET #50-336 f \\ i DECEMBER 3, 1986 MEETING-WITH NRC STAFF .1 STEAM GENERATOR TUBE ECT RESULTS s wn ,.,-e ---,.~,.e ---.-.--m.---.-m-,.

MEETING AGENDA MILLSTONE UNIT NO. 2 - STEAM GENERATOR EDDY CURRENT TESTING RESULTS o INTRODUCTION E. P. (CHIP) PERKINS LICENSING o OVERVIEW 0F ECT RESULTS JOSEPH M. FACKELMANN - NUCLEAR MATERIALS AND CHEMISTRY o RESULTS OF EDDY CURRENT JAMES M. BENSON - TESTING NUCLEAR MATERIALS AND CHEMISTRY 1 o 1986 SLEEVING AND NELSON F. AZEVED0 - PLUGGING PROGRAM GENERATION MECHANICAL ENGINEERING o

SUMMARY

AND CONCLUSIONS E. P. (CHIP) PERKINS LICENSING r

i 3-PURPOSE OF MEETING o TO REPORT THE RESULTS OF EDDY CURRENT TESTING CONDUCTED DURING THE 1986 REFUELING OUTAGE' TESTING TECHNIQUES /RESULTS SLUDGE EVALUATION PLUGGING & SLEEVING PROGRAMS ~ o TO DEMONSTRATE THE NNEC0 CONCLUSION THAT MILLSTONE UNIT N0. 2 SG TUBE INTEGRITY IS ASSURED FOR OPERATION THROUGH CYCLE 8. 4 e e ,n--.... ---c._.--.-,-. ,,,,,,..,,,--.,...,,,,,,,---,,..--v-,. e,

D 9 9 OVERVIEW 0F ECT RESULTS l JOSEPH M. FACKELMANN

. DVERVIEW 0F ECT RESULTS 0 IMPROVEMENTS IN ECT TECHNIQUES RESULTED IN POSITIVE DEFINITION OF DISTORTED INDICATIONS LOCATED NEAR THE TOP 0F THE TUBESHEET, AND IDENTIFICATION OF AN INCREASED NUMBER OF FLAWS. 0 ESSENTIALLY ALL PITS CONTINUE TO BE RELATED TO SLUDGE / DEPOSIT BUILD-UP LOCATED IN THE REGION ABOVE THE TUBESHEETS. O MP2 COUNTERMEASURES APPARENTLY SUCCESSFUL IN REDUCING OR ARRESTING PITTING: COPPER REMOVAL B0P/ TITANIUM CONDENSER 1986 IMPROVED CHEMISTRY CONTROL / REVERSE OSMOSIS DURING CYCLE 7 CHEMICAL CLEANING 1985 ORDER OF MAGNITUDE DEFECT REDUCTION (2366 TO 246) N0 SIGNIFICANT PIT GROWTH 0 BATWING REGION DEFECTS ANOMALOUS, APPARENTLY ISOLATED OCCURRENCE IN THREE TUBES. O DENT PROGRESSION MINIMAL, EXPECT COMPLETE ARREST IN NEAR FUTURE AS A RESULT OF COUNTERMEASURES INCLUDING THOSE LISTED AB0VE. <- m u.- e .....,.,g n,,,, %,, m

m. 4 1986 REFUELING OUTAGE EDDY CURRENT TEST RESULTS .l 1 t j JAMES M. BENSON 4 I f i b f i r

. MILLSTONE 2 STEAM GENERATOR EDDY CURRENT TEST RESULTS (1986 REFUELING OUTAGE) O TEST TECHNIQUES 0 TEST RESULTS 0 COMPARISON TO PREVIOUS TESTS 0

SUMMARY

/ CONCLUSIONS 0

/ \\ )

EDDY CURRENT TEST TECHNIQUES 1986 REFUELING OUTA6E 0 MlZ-18 DIGITAL EDDY CURRENT TESTER SYSTEM 0 DDA-4 DIGITAL ANALYSIS SYSTEM 0 DOUBLE DATA ANALYSIS POTENTIAL DAMAGE FORMS ADDRESSED BY SPECIAllZED PROBES O 0 SIGNIFICANT IMPROVEMENTS APPLIED TO 1986 EXAM: 3-FREQUENCY MIXING: SUPPRESSION OF INTERFERING DENT AND TOP-0F-TUBESHEET SIGNALS. ROTATING SURFACE RIDING PROBES: FLAW GE0 METRY. SELF ORIENTING SEGMENTED B0BBIN: FLAW ORIENTATION. LARGER DIAMETER PROBE FOR 100 PERCENT INSPECTION: IMPROVED S/N.

e. l NV=3Yihh .__x_ee _.xant!MMiMHiM !!! Miibk ! I. l i .x.G R4 MMsfMEKlMMBRMMEE! !!!! i

==s:jiii!# REM 2MRRj!M8i!22MRMiMiRM!!!! i 420:We4MMMDMkMER!lMiMH!RNRMl isi! 1 2:!4?" 1 MMikl#M2MHgMHMEiMHBi!!! m I Ai? iE _ L2Mi!!ERMiMfMiM22M9BE!!!!! w

g "

~ " " y g ]8{i W 5 9 M 6 R M Hj!!NiMMMEt isi

  1. 8M M9M22MEist i!!

2 .:si.. 's

Amt, 4.4 @ trig:Mi:58

- - g;g - ~sM4MsM,jp$'+gg.;p iM!9MM2 !!!! g g.=c.. ;; ggg%N j, ggg TT$=dR%=. a.. ~ 3f "~ =- =J- "'. .=.:.=4 :: - i z

9..
qnygg

. gg = 'M he f--

::_;4. :-
==,{.g.,.+.-

,l'-V hh E I fg 4 g lro '"" 3 E..s.,- .__.____e____ .. ~ -. * * = ' _. _..:lE h i!r F2 $E ,kk ,h:k-M, _ k:hhfk-c. ;$f,"c*~!h h,- e.:. - ... p ,$ =,., C++++++-++da ge-, = _ l**. e 3 k hhk*l**. **

  • h,3,.

ww +++ s. . b, ~ '5 vo- ~8 8 e

  • W ** *

~ ^=-::p-f.g:::gm:::3-=. =:: = xsc=. c' ys se.a a= =, F E

== o -s gg ._.gaemp;ge .c = !a': g

c. - -...p

.... _ =,, _4BA j!M1 .iM$$$y:L"$RR$ix;Jni + J.%x i mg;2-3 =

  1. gg.:.sg;w!kM$$i!$L VB ll g

= =_. ..p$.1.l . c.wx.: y ~ z ?:! 1_==jl t; ~_ # = s .;g =e.s e :.g::ggg=:ggg;:gg:$. l llg3 g ':;i;i, h

7' gggk2E 5
A *v.

~q~ ~~ $$$A::4P# B 2iM M B: S !! / e 2.v.. .y +

  • +vf, I

".:E+.. 'M E6 e =g9:.y l g$=sy Sg l '+l':- XV 5 ^^ _~ ' g!l -.~~j ~ <-

  • ". ' ~

g~~ gj l n .y ,s l ., gg l s o. i (e *- - -;Q 44 i s. S ~~ 4 %l ! I. l 2 i 1 ie = e e


,--.--.----,,,,_,7


w a,,m

I Adehe!!Hi mit#MBBB9H21 !H! _._ ee __.w3SBNfRMMNSMMMBl!Hi 'Ii i A HiWi339?l M M MiM 2!NH M M W:i@lH! Iili I._..4&HMMisfBM2MfBnBH8inBBfiiM@lHi i .asMMM!MR!NHHHRHHH9F#MHMMRl !!!! l .s!!,!:i:!$MMBiWMnHHH811BWi45 MIN @iMBiMB !Hi ]$ i

===iE== 8s_3M=t3M_iWig' Rx ~ ' ~ ~ ~ ~ M88 !s 4:i8

== =- .::i:!$:38;iM2H#2Ri_

sMi" EH iig,

._ f8BM68MiMMiB.MMMMPHii8igs4%i.'s:!8.s_ #$2W& K MMN2W82We#! !!i; 42W%BBN ~ Wi$,.w.fMHM!HE_ E. E !!i @d M g B F '~' M:W&,r i! L 58s.ti3 ~ =g 5si:f.,2w:it8sg--=f2W.3=n...

= =

== =

=

J h. i:,

== i ~.= ~ "; i.i#3=V4,tR_=U.$.i48 #iM M 8 # #:6' _. =. L =:i r.!, i, ~ l2.. s 4.m = =. - - - - -

= -.. -

= p. egc. _ o u. N,.: -. = '. u

=

.:eMW:=_BiW. si ). __.Co g- =

l

~ v ~- - - ifI l'Rd8_2882$$$$2=987 = = = = =.. =W$$MN@=e ~ e. ff4: $ 233iliiiM!NNS$$$i!N!%iMI!8i:li!$i:ii$.fi:$$35!N.A !i I -. q. m WMMM_.MPAM8?i.$$$..sM.M..#2_M#" 9 -3 w-0 'f.- H

ll

.__ _=

=

l *.i.. S pz@. ~.s_s@xls..... ~~~- p.E o. ~ = = $'H !! < f. u$iS.v@a "

F *X=6 f

/ *- = ~

.s

= i ~~E #w $,b S M M= ~R R =3

== - :: = $ d i.f. ~'. " ~ -- h 55 = = ;,.,

==--

- - = = - y

  • ::.:.:.:.:. s

= = - - - - - - - H l. .y IIII "32.. =. - _ M_ _ _S_ _ E ~ %g i "4% ,_=.;_ i I I@ 5: ,g y E:: c .,,.3 y _==== l i .._........uggg -- g 2 j .? = 1 1 Rh a suiic_h_b_ d..iE2.eh.th.Mnidtifikudiibbnbhiihoindidikih66 46

s i i a.ew =! I n$2MRiMRMBB!!!! _ x.,.a !l ._.g49ei;Ms!!@!M!!!s!2Hi32!$f!!!l i 1ii !!!i!!I M @ss$n;$i;gngM 2i3MRNMHg2 !!!! !I IIIIl:4SH589BMMMM3iEfiHMM39MR;!!!!! iii-L5ssiiM95lMWBGM#M HHME M !!R#HRE !!! I: I 83i!###M _ 1 ~ _.__ J._MSSMiMRM!!!!! IIIM:!sistiH(Hif~~~ ~fMM$MnEM$i2 !!!! I I I 45362!#6M68W ~b ~~

disl!.Mit3EREi;B$l i!!!

$*hO$$$$5!hM8$@@@ $hfE8l!lM:ME$$!!PeM@5@ !!!5 ~ .qttjpE *

n. ? "

g gg.5fbggpg !!! u mm aa8 =- JS:W G $t A %iB(MsnBH^'= 2MiiiR!EiK@N !![8! Ni_h._ A ~MifMMr !!i I:Ut4W$$: vie 8i:$ssi3F - ~~ ..-: m :x 3 t.. si!g.r' h ~ m y a, .m $s ^ .J 3 # M!:#i?$ M C '... .:.3! _. _ii !! E = g Ws. - si e hk } i. !$5 o Mi.F:.G@d@:p,gs@E8MEE:a is###!MY . i ]..L?%. si i-[ EE i! y ~ :. - ;gpyjjg.s be. l, "l = , ";g= p lel e=ss.=w=,=s;.;=;:=: ssp 0 =:==- e-l m si i-e

Mi##:?$M.

M 4;s ;,;... -=~ m--x -li!sM R. !! =. e <;. --:g, -- -M-g, 5 m i ea n l Ih .k lh!@sN$!! !! s s.....wi-6 u .:.:.:.ys g2 fi I^653. !M3 E! 7 ,=.;.:. . gg

== !"T4,%Mi~~ NM21.% !! rc .ta l l' l i! 1 ~~ u ngt. e_cgtjg g WR l; j; ~ !? t 3 r l i g 1 fississssssssssassinuni=intura=:dhi:idiis tisiA An**=issi:de"%;

PRELIMINARY MILLSTONE 2 STEAM 6ENERATOR ECT INSPECTION

SUMMARY

(DATA THROUGH NOVEMBER 29, 1986) STEAM GENERATOR WUMBER 1 DESCRIPTION HOT SIDE COLD alDE HOT & COLD SIDE 10 NUMBER TUBE 6964 5546 12,510 SIDES TESTED 20 NUMBER TUBE SIDES WITH FLAWS 21 > = 20% ' 1356 407 1763 22 > ' 40% 82 83 165 30 NUMBER TUBE SIDE WITH DISTORTED INDICATIONS 0 0 0 4.0 NUMBER OF FLAWS > = 20% (SOME TUBES HAVE MORE THAN ONE FLAW) 41 0-1" 1291 290 1581 42 1"-13" 228 260 488 43 13"-28" 2 0 2 l 4 4-OTHER 4" 0 4 45 TOTAL 1525 550 2075 50 NUMBER PLUGGABLE RESTRICTIONS 1 0 1 (GAUGES DENTING) i LOCATED AT FIRST DIAGONAL SUPPORT STRAP HOT LEG SIDE. l l

_i3 PRELIMINARY MILLSTONE 2 STEAM GENERATOR ECT INSPECTION

SUMMARY

(DATA THROUGH NOVEMBER 29, 1986) STEAM GENERATOR NUMBER 2 DESCRIPTION HOT SIDE COLD SIDE HOT t COLD SIDE 1.0 NUMBER TUBE 7576 5534 13,110 SIDES TESTED 2.0 NUMBER TUBE SIDES WITH FLAWS 2.1 > = 20 % 474 296 770 4 22 > = 40% 26 55 81 3.0 NUMBER TUBE SIDE WITH DISTORTED INDICATIONS 0 0 0 4.0 NUMBER OF FLAWS > =~20% (SOME TUBES HAVE MORE THAN ONE FLAW) 4.1 0-1" 404 87 491 4.2 1"-13" 127 264 391 43 13"-28" 2 1 3 44 OTHER 0 0 0 45 TOTAL. 533 352 885 h 50 NUMBER PLUGGABLE' RESTRICTIONS 2 0 2 l l l

. MILLSTONE 2 BATWING REGION INSPECTION 1986 REFUELING OUTA6E O APPR0XIMATELY 20 PERCENT OF ALL TUBES TESTED THROUGH BATWING REGION (1585 IN SG 1, 1528 IN SG 2). ALL UNPLUGGED TUBES IN R0WS-35-38 AND R0WS 66-67 WERE TESTED IN BATWING REGION. TUBES IN OTHER R0WS WERE RAND 0MLY INSPECTED 1.N BATWING REGION AS PART OF FULL LENGTH INSPECTION. 0 THREE TUBES CONTAINED FLAWS AT FIRST HOT LEG BATWING SUPPORT: SG 1 (HL) 15.1 86%, 5 VOLTS, 0.0" SG 1 (HL) 154 75%, 4 VOLTS, 1 3" - 78%, 2 VOLTS, 1 9" SG 1 (HL) 145 83%, 2 VOLTS, 0 0" O FLAW CHARACTERISTICS: DD INITIATED. LOCATED ON EXTRADOS OF 90 BEND. WEAR RULED OUT. LIMITED TO R0WS 36 AND 37 0F SG 1 PROBABLY CAUSED BY SOME FORM 0F CORROSION, APPARENTLY STRESS RELATED.

/ ' 4.10 Tubes and Tube Supports B. Geometry L Y 1 kww. M M 14 0 g j: rfja -4* l' //G .= 4 O 90

  • e l

I l s I \\ l 46 -N I l m u 4 N a i \\ N = / F 16 L e b e t-1 m e g e e o a I - a s.s..

. i

SUMMARY

OF STEAM GENERATOR TUBE SLEEVING AND PLU6GING CANDIDATES MILLSTONE 2 1986 REFUELING OUTAGE SLEEVING

SUMMARY

REASON FOR SLEEVING 1_CL l_HL 2_CL 2_HL TOTAL DEFECT 140% THROUGHWALL 83 79 55 26 243 INCOMPLETE TEST _2 _Q _Q _Q __2 TOTAL 85 79 55 26 245 PLUGGING

SUMMARY

REASON FOR PLUGGING 1G_1 16_1 TOTAL DEFECT 1 40 PERCENT 3 0 3 THROUGHWALL 0 540 INCH DIAMETER 1 2 3 PROBE RESTRICTION 0 520 INCH DIAMETER 0 1 1 . SLEEVE PROBE RESTRICTION INCOMPLETE TEST

  • 0 1

1 l l PROBE STUCK IN TUBE 1 11 1 TOTAL 5 4 9 TEST OR REPAIR

t

f. I I 1.0 'e t.i e e

LIl 8 *) m5 L.U 7 E.-W.e.,: A..:. g d .d ..p. P',l'.P g LO C1. g M n ,.4 ~ L.1 n m.A s %..e, CQ m.e -ag .m. %. : ' r.. %.w, 5 e' w ....e e, w e.a ' L'U de.# 4 .%m.,, .d < v. u. 0*4

3..' e :.-...,,w w..p. c : c..

e,,.....%..c. e.-. + wx.cc..m.mh.c e.; e....w e. e. ec.c.... m, s.c.e c

c. c.

w s.ts.ww w e..N ~.n %.n.e. ruA.%.>.*A-e4.%.e.yw.w.w.m.ie.ges we e.se A A.nA= ANs wh-A*h e. w )< ([f -wh {,.,j

  • sms >.h-we A.n.w e A

~ A nE h MA h... w.' - w.we. n

s..

e .%.w w.w hms.A.A.A ceA e h em A.. a sa .%.=.= wpw.% %.% q .e *A=.%%.e -w >sA -A.: w.w.% e. N v .r..N pN.es.w.w N.N %.%.e.m.: g.w.w.w.w p...w.w < & AJ N d w.em.e-A-w n,.cs.es w k w w AWA AAwA.e.g.%.pg.A.wA J %.e= %%=.w A.g. A.A.wA%. . %g%% ge %w p QR s..%:.se is % % S =wys.a w.spw.s w wp f.f ' .%.>.h :.ech.%.e k.N..A.%.%,% F. A,N.%w., %.wp~A..wpwe p%..e..es%.%a.r%=.Awsere.Nep...w ygn%%.>.c w.> -b A.M. w w -1 m. w .%.=N.>.w%.> w %w w i A.. A-A A.wwe. A w % >.h h cs m W.. .rw 's.ex .we. AE.% e-e o.A, g d g W -..%.ws ;e.. e.pw,%.%.%% %ww.we .w.%.www.w.w.wpge. 7 :.N wsc.www.wg.s e p%.. %.w . A y A. A we.. k A A A a= A.w.sm.w.ees%.e,l>e>rme cehws. 4.+w.e.ws%.we. >..e w> wes%. A.K.e dwa g.s.pw.% w%.o.A % Y"'" A .w.c., e :.A .N.s% w .we w ab i.w.w.w.w.% a:.N. e.we.sp.a,.=% %=%.e e de ww w gw %.h.c. w.% L >.W.=r. >:.K. ..p.. A.r%. > - w..% A.m s w )=.%.%.es4.% s..>.Ns..n.ee.A %,.%..,w.w.w y.%.3s.wp%.cys. ~.%..n:aau ~ ~ ~:-:~.w.'w~ ~ - -w.w a3

pw rg w

Q .e. 'y A.am. A h.h-eswhw ~. w k.e.A. s ..=#.%

== e t %.em....e. %.AA.w.N.w.g. A.A..em wa wh.%.mw= eg.,,%A. A..%.we A.A.3%.e.,. A~.w.N %.%e.( %.'p%.=w rst.s A.- A.w wi , y s b ,, J .. e e..owy..d..N.wgew.e.%..e

e. es.p..A A. e er.w:ega.e..%d%.dN.r<.w.

em.%.im. A wAws..A.. w .tv.w.m N si N.m wt %%%.www.N%w w~.m % e.. em'. {g,, W

a.. J t e

.~ --:~ ...~ e N :re 's q I wg,.e. em. eAAw.w.s.%A.s.wwe..,Ar.A,> A A.s..A.AW.A.>s.si www.e.x h.%.,.A.N,,

  • W CCs

. e A wJ =A ^ q }-

e.. o

...wg'. '"n. ...w e e e..A.A.e... N.e e w.w.%.e.e e :.w.e wA. A.c-.r.w.s.:3. e nw .w e.w.%. ww w we .w., w e ee.3p o. psp %.s .e. ...o.e. ..ps e..e. e A=e %.%.A,a.A..u.a, w g 'a n, y 3 3c.. i {ge cgggg;ggggege A-w e.wem-.%w Aw. re -wwwe.- wA-~ A-eeAww. m O -t Ca t. , T. LU w

  • -4 g *.

C .3 g imusi% is-iw6.i.i; ar%is.A.ii-i,i.-i%.ao:iwpQiwswi%.i iWim i M *J Q is V i. '.M .Aiwwh*.A A wA A AA.sc.A nwA**JN.2% in w'wn -> s%%%.% e-:d.ie.=N. e e m,,r.I ..m.%.% A-A Ass %t .%.w w %%%. %%%e %p% m h es.' %..-Ne-% %..A m.e. %s.ip%e Y., s e. %=A wwe%- ~ %-%:.eswe.. N.7 w ..a . w e.e

e..m ~,.

ww. h-s% h A-A4 A eXAwesw'e.-A.f';g.., O.i %*A wi= A -e. - A w%.r %fw%.%ss.es.e. wA.ree %.%.% e y%.en w%.s.sp.Q.N: () T -s= A.%wp e4 s. =% M% w e=A..w.w.w w w.w eswwAwA .3

e. -

w %%%.%:p. e...%.c.%wpw.. ..we..w rwi. o..q Nw er.: e s e N..e.%.%-A.' hw%. A. .e.oe.4%-esh.A->..e.w wes. A.A.h.es .w i.%%

r. A. y t.% =%.w.rs

. pw e%.%py.' ww.% N. s 9 w A-A w em A-A w %.A s.3%..%.s%wwa-wer.%.e., A ee,.%.ss y e A-A.3%we.i

==* A A%. am A .wp%:.% -c%.e:: =%.rupw ..r Nys . e..we.. %.x =.Pw.e..bsA we.g.geq=%,wr N,prm.;. w.% A w w A.A. wA.w N Npy o epto.e%.As,, wA j1** %% ww% ye Np% %e e. .g g, % o 3%%%Ns %w.w e 4s% p . psp %.N4.re A=.A.w=n.wwere. XA.A . A rs e - w.%%% e.em Nr.~.% %% w n. cts.w.w Npse .wp 3 e.s4.%.N.A-h%.%s,..X.w.3n e5==em-h.wt I I.e. a .A=we

.wec %.w.c m.ce> A.e.pwpN.h-wer.s we (g4 f

wAwneeA ce

e. 3%

py: % .M.%3ww e .w % N we.:.e.r. w%'s..eeA ( -. A A*e+% wa e

g....,g
  • 9

.%g .w =A.w A.A*h A.%:.%.=e.rhw.N o.pst.w.w s.p %%%%.%.t.%%%%wwwAA.e. %wA=A weesmeA3w%. e a,* g c em w w'=.%..N.)n d.d%%.r.=n =% w %,.:.%p w w .re.N Aeh igg %ipge)%%%.%%%.g..A%%.~h.'w w%w e,g,Jg' Tu ' s E. A*J.m

  • J.

J%% A *h w A%%=M '.*[ 1 N_ bb _Y[I_ E [NI

  • [ b'....

CJ Ci a. m m~ _ _v: 3 - cn o p 6#4 i L.1

9. ~.'

Lij C7 M4 amm F i l I i i i es Ca e o e es es cD -O G G C9 G G G tn CD ED CD I,D CD D = = rol 19 CN C.J w--4 4 fElBIUd3M SBEn.L do ' 3EWnN d

. MILLSTONE 2 STEAM GENERATOR TUBE FLAW PROGRESSION MARCH 1985 TO NOVEMBER 1986 FOR FLAWS >20 PERCENT THROUGHWALL IN SG 1 AND SG 2 COLD SIDE ELEVATION NUMBER AVERAGE STD. DEV. TTS (0" TO 1") 34 3% 14% ATS (>1') 160 1% 10% HOT SIDE ELEVATION NUMBER AVERAGE STD. DEV. TTS (0" TO 1") 405 0% 8% ATS (>1") 79 0% 9% l

_19_ MILLSTONE 2 STEAM GENERATOR TUBE FLAW PROGRESSION DECEMBER 1981 TO NOVEMBER 1986 FOR FLAWS >20 PERCENT THROUGHWALL IN SG 1 AND SG 2 TTS (0" TO 1") NUMBER AVERAGE STD. DEV. DEC '81-JUN '83 102 3% 11% JUN '83-MAR '85 124 2% 10% MAR '85-NOV '86 439 0% 9% ATS (>1") NUMBER AVERAGE STD. DEV. DEC '81-JUN '83 49 29% 18% JUN '83-MAR '85 41 17% 17% MAR '85-NOV '86 239 1% 9% t ( 1 l l

MP2 STEAM GENERATOR TUBE FLAW DEPTH 9 COMPARISON OF 1985 L 1986 EDDY CURRENT TEST RESULTS 2,500- 'YE !!!H!!!! w h 2,000-II!!$$f lgg 190b i,p!!!:4}i m tm i w q> c

.{.an.1 a.

! NH 19 85 . att i 'S NN!;! 1'500-f.i 42 2 c l@{ i . 4 ? f L

i. z u j

i> m Da 4 [' f h dg6"!i 3, sh w A DI I, MIME k:!fft 31,000- $Ti IEEI ws $!$ j!f.17If! lifkf [%@ u. hk)l d'N!I EE 0 ll$If 9sh; dh lgg$t I m i w su gpgE

}'

t g;iky m 500-nm 6 = no t [=N .l hIII i$fl d.. $31 5 $$f8! z rdksy! '1 sp

5,,-{i{gp g8 l

r ic lrfal M i EMR .t F. E tu J @pp% l.1 ! e m . p' $.[$ M it . I.! lh)hil d i sa g mm m .t e a em i I I I l (20% 20%-39% 40*'-R'3v 40% FLAW DEPTH G.' THRU WALL)

MILLSTONE 2 STEAM GENERATOR ECT INSPECTION

SUMMARY

FOR NEWLY IDENTIFIED FLAWS NUMBER OF TUBES SIDES WITH FLAWS >20% SGI-HL SGI-CL SG-HL SG-CL TOTAL 20-40% 860 277 350 172 1659 ~ 40-60% 65 46 19 30 160 2101 3 _22 __2 _la as TOTAL 928 345 371 220 1864 NOTE: 70 PERCENT OF NEW FLAWS WERE LOCATED WITHIN 1 INCH OF TOP-0F-TUBESHEET.

Je Ir* - 2 2-- c3 cri rTJ CTe r H ,- 4 1 CD (rg SI!! F Mt W

4... ; M.....

A y gg gs.4 D 2;!1 M*d (n W E Ln

  • ~

5 ).- i- . ig

., p z (n

~ O Lil ,..,_4 w eme ?......,, ei F 74 M M M i4%?'#2i 8 W 3M,,. W-W..s., 4..%..... cr.' I 3p,. ~) W A j pa 3 W _q ~-, q m _d ._J E - p LL D Ei 3 m w U [L, to m. m US 9 >' 3 iMscSW44 m ED F tM4MeMMr.e.v:v, cc JA ou w w w w w w - w p e Ct trj g OD w t- - to ^ 3-L't:N u ( cts 8 'fffChi a g,4 U 'M o-3 H uj 1 v

c3

,wa erggwp w 44 4 usma WG "I g mre o<n.a{.eXc.44h'n [1.)

m, a.m.;

u_ CD h co -.g-g ef UI f3 m H e t"u." aus.e

2-CC LD D m

m _b ~ l w x .o= r, u. H TE CL ...-..o.. . __. __._..._.._ _____.# c n ;c c c c 2-c c c c c c c k w e c c c r. q% c c c c y.C C c r-ccmucccR2 v

X452.cTsccO2O?%2EcCWCRMcccg

+-r r me-vwww-~cww.-vn-vm-m msev em-v -men-wm :.w: --v-w < O U -- p Y I I I I I cs s em em o es C3 G CB C3 S LO CS II") C3 LD .= Ob Db W SMOld 3E01 210 83EWON

23-NEWLY IDENTIFIED FLAWS 0. IMPROVED ECT METHODS 0 FULLER UTILIZATION OF DDA-4 O. MOST PRESENT~1985 (BASED ON REVIEW 0F A LIMITED SAMPLE OF TUBES) e D 9 8 4 4 4 e 6 9 --r- -e-,--- -, - r - -, + - -w---- -w- -ww--, w.,- -wr.v- -v-,

. MILLSTONE 2 STEAM GENERATOR SLUDGE HEIGHT COMPARISON (1985 AFTER LANCING * - 1986 AFTER LANCIN6) SGI-CL _S61-HL SG-CL SG-HL SGI a SG NUMBER OF 350 492 371 510 1723 TUBE ENDS TESTED BOTH YEARS AVERAGE -0 6" -1 0" -0.8' -1 2" -0 9' CHANGE IN HEIGHT (1985-1986) FOLLOWING CHEMICAL CLEANING l l l l

~ . MILLSTONE 2 SLUDGE REMOVAL

SUMMARY

RAIE VENDOR DESCRIPTION LBS REMOVED all IL2 JUL '83 CE' FIRST TIME LANCING 800 800 MAR '85 X** PRECLEANING LANCING 298 228 CE CHEMICAL CLEANING 310 257 X** POST CLEANING LANCING _.B.E -lfiQ TOTAL 688 645 NOV '86 CE' LANCING 454 498 SPRAY FROM PERIPHERY (MULTI-DIRECTIONAL). SPRAY FROM BLOWDOWN LANE (ONE DIRECTION ONLY). e D 6 l l l M N $* ure - w %w a e i

. +. 1 ..e -e. a.R. L.A.A LM .~ M L, ~ ~20 ,'5_.'+t ,y; r;g ; --,X; w _Ac.su.,_: _ b C: 00 d OC d i :.::. Of ~ 0 1 ~ - w ~,. m rr ~, m . :3g

d. m. _.@N.b_,.h_k,- W@ W_..M_. _

f___ ' ~.. ". g;g M E e m.. -m , ee .,_,c_ ,-~,O,1 .m ~ ~- XT .~ m,0-,0,M,~, W'MMOf'dO,.n3,C,,. ap -:.D @, m,-~_w_-- _m 'c_,2XX f._ ~ =c - J _._.m, =a~.._ ~_, _'"1.

:M

=., - - e e. A, ,m,.,_~_,_- .'::1 ,, ~., ~,.,#ww .A,~ -00, 3d._ d._.,M..l2k. '.. '., '.,'. sk. '-. k',i t-_t.,00_1M__3O_U,3,_0_4_O_u ^r.Ga_KO7T, ,WA.,.~~,, 38 ~ s m_. m__.-.X-m W:_=' ,.W.J?'--

I'0

.LG4.MXbt.1XXL ?.;*) - "'O cetM ', ' ?""'N,. Uu:W. '. t _,_O y % _ Mc..acXN.M m,m +* M,m a w,,,T..IC,. ' -, O _ d:1 . tr t _m.,_ .~D

-m-e

-m- ,-v e J,.,...,.. v, s e_c. -- u,e-.,.J,,,.,,,,.D _s.n,.s ., n_u a- - .s... X1, - v, .o.u ,.......s., one w, .t~.h.,.. ..s ,e ~_ -e~. c ._-_0,.,._. + _ .+ .w u-a-nn E_. : _= .,w.w.,., n -m

e. _

s -me _.. _ ~,

==

===' ~

' - ~ = 'ei,W-tOs : E ** c._._ ~=^ E. _.. _ --,.,v- ' M., *,ZA.,.,'.M.'-;,, L.;6 : =~d m ~=" J;',

=

2=

=

u

O__0_ _00,*r, _ _ -. -.. ' ' '., '

%po, -_,mr= c:= d u.,=sm <=~ <=m <=< s., m t :.=r.:=r a _ _a. _ _.2a . :: g n = -es-- -c=_vm=s_ n y=a x

=_.=m _, n, e, - r- --.

._.u 0yy~02- - ~. =

== =.a.z r,=1_,

w.._c,.;=,s, -.=_=_=s._.r_

e w : . =.< = =_ s_ o.1_=m_= _: =. r J._,7.,~3_m, .=. _.=f._; = .=_r _ = t '_4.a,, r, m g-+--

E$

'-Tf.y,.., .m C t*_." r

==

=:

- - = - - .t" r-==r=r _=c'"*. _S~- c'" " ,.c.,:., ' fil-si #=".gsD : ::.- y TJ====#-' #A"r?J==r U===Ji =r==T#c =1._=a_= w _= :- = r = ;), F-<1-WW F-W. ..=.=_ - 'c.,* u ~,_g -ai m =r,. ,J u22,_ = =,t -,r m,- t,_r a c; c,_; _,.x -::q-, -m~ ~ -, - m--- r- = = + -, -t,-- m m ay. e- --,c...,. y.r,s.m e-t e -, w- - m 4_OC, = Ju._-. =. _ =. = =,. - =.=.cc=.= =__===y<==_=_=y<=_u ~_4_ ,Fu;.r.;F, ~"u ,.,u_, mY. -_'.'_33., --,w. mmw JU _r, ~. + t, ,r.JL,as J,.F A,., n4.W.n.g -.c n r 1r ,t_.. JUR,t --~r.e~rv,~r-r i m _mm_ _.. _,, _ _ _

,g,

r~-,"+~---,-,-rr ,sy <e g

a m,,

.,.g m= = ;= r = = tara.acc-w ..;;r.-i. . --n, ,O,,,yL.e,n Pet.=1 = = a = =.= = m=== - = m,u ===. : = = ===_ r.,. b. m :====== m = u -.2 = n = h+aAar.,=.ax,=r - = =r r = = =r =- ; =- =- t tt = = := m -,3

.

u==m===c

.r a

_m.m. N _n_-xx g,.g ~ m __< '-.r-~-~_=m-=====c~+..=.=.m=2 -=---=m=m-2== -r ---.i R p a, g a ' c,.-;y,; =m=._.=.._=_=.==m-====5x.~=_= _5_=_ =a:=======;=_=_._..=r-_-.===._m. - '_=_=; =_=. =_. c=n = u

w. _ =

5,.~. m,

=

== ==m m -==, r==m m-

== p gw h_ _,,._,t.,.,_ .~,_.~,_O_ m, y _, _03,. m = -"l lg w e w .i mtv- m _YdWy, _, .1 w'*"*'r=-'P"'- 1tm=i -=-='m'-* g -~-t?===:

==..g ZS m t-%'< ! ,#? # # l'#=i"# #= T #r' %<W +&HiikVc'41-<==rh==VJJ Jtf l*

=-

ai

===r a".- @g@ $.,._.@m,.~--a - n~rn~w W_. n..;N. -; r.cmn:a.airas.tr,.m:-.ra,rmrap Q *B ~,%M_WW$,~gxy .T,

  • 'T

- m . - ~ -+r-- r=-s 14 r,.._.mm t H m,., m_ - ~ 4 .=_'=:=-- = M.*** n=#Jb= =J 5 " =JA=#==#i===2 =J E C 3 ..g'. eo@u = 3.g an.a;u 1

.sacu,.t;u,c

,.s.; man.sms = -l ~S *~_n _,_m, _m. a . ~ GX= = ?"~"'q" uEm===== = = - r,X,T. G K'Ga XXAs;;.;, u.an.a u.ar; aAr,s.w2 ,.t c_=- r i f.,- 32 ,,e. em a P Tv,., '#=, - m $.g. W_ _O_ O_._g;*:;'.3=#= me-#.i n!'.,cF+%+1t = = =.-ik l'lE {E-cw+>-ene**m ww_m. ._.=_;.,=.__=a_=_ts._, y I l(( "".. _ -. a-=-~-_"t ,s,.,m,_,. .",^[=====~-d~':==h~-=

= =

g-Y=^ h~~=^ rd*"h n Er J'=,m r,'t. N_ ~ W i ~y" I g om._.,,....%9'._.p4[*#Sd. ,a l @g"d*#1#*# =

r

= =

=

- - = = =

==u=

Ev y = = =..=.==_=,,m ;s.=r, mar,=s _n eR m=-r

=

=.m <u. rw. - _ =, ~ -Mhf6+ E ME-k *h_ m T.,. e _, 8 m-- M @.;.~, e,. ? p^ g p.m,--r"3 e (,.r,- u,.n x,M-,_,.e_g,.sg*,,.cIv ..s, _=+ - m m R1n a.;'Fi L,=;u.RLs-IO. w r rs s sesa c - 1'p;S.; gy ~ = = = h d14 a 8 M ' g_eg_m tm_gM qg s URR.LR.ai.;. = = e I gg W. .$5G_., _,WE'M EQ't' M*-'E, g, W R$ " I

yf

@ghwg58=_=.- ~_ Jt,rau;uta,.awr,A,.q.aa,A;u aax.n.au Rr. 3*4g ar =r n NTf" :

n

,_;;.#, t'Y*#tMdT*d""*:#a===A==%-i'##JuMVHEWt-req s s nD;WU#d=##=-1b###&iF&5BFEEEMJJ#J_ m g W,g8 v_,._.,_,c m_,_,, - r ~~,n r ~m.rn~-n==m= F1_ 'A. Ra u____ i 0 wy'5 y ;= $$M_ i -m e M'DO t t r g-y ,O,M..M,M.~s - -m,v,a,,n;;c.,~rs.,~,a annanAns w=_m ~ a.an ,.r,A;ual ,,,, W ,g p m ~ 1 = = m. = m.- y .u E,585 m v e. -g 00EOM.CCE.E Rr+F+A3iBrMi M T===##=Vr=M JEJ di-32 .D. c.,a= r=s##==#=H m.,". ' ' '.. =, T

-q_r_= = ar,cm= ===u;.ars,, c r=o

= = =._.P g,g g,) 3 ,',,Mtit.+a s. t'.O..MOC ag,g ,,%,s.m. n.m,,,- ,.3,.,w m,~y, =-z- . - mn

w..,.,

' ##==r-###JJ# # # # #==finF 6F Ba=#rL=J;=r JJJ f=#d!-i F4 '.t an. 3g = O, -MOX,_ 5 ".; -t5 '." .nns E 40M 3M M t t 1 EE uns,ar,.La:sut m,r,.n.;u,-Aar,arxr== = =,= ='= = m,~---t-r -r - --~ r-:==== .=n . ce Q "6 33 1~ r-v_ -,mm -* -r

  • tr m

s - m r=r =c

un

==

_-x.=

or=,-=c

., 3 ', _,'m.,v,n,, l Y',5.C"'.'L, r_.,.,, q=r m a: rnr -1 m==o====f.r=_,=_ -.y;===,c== =_r. 2 1 s=' r e~ ,=x=m._=_=a m= =. _:f. o v r f E.g ..ef, L ...~- . ;=.. e m -tryte, esc wrn ,1,u,. 7,rity,- ~ w n tl.- --

r-m -.-

w-r - -><r---s= k__.,hmM.M._,$,9 3]3.,6 v -,-i

5. W# ~.es,r_tryrNi* k,; -MWM=I= =M W

q IOs a EO J,f e- ?.~=?@E= =Y.Y,. = m ~- _8. w %00..'y G dU %M e, ors ess,.-.,,.--7 wv.shJ m m YT'Te'#1Y'==. rgMF'i-"TQ. f,gXC. E$ y, .petcyte, Met a

h., sn'00-.

M7 ss a r,s.rrcu-a r =.e.r, 2.a.;,c.a,,u,;ua,cs.. MkN-r. _ --. vu . ^., ~ - . ;e i.',AF,.rg; Arsgs,Ar,6=J. =.= #r OJQC U t:5*<,m_M_E r L :_;crr.r.r-inM t". t'W P-' .e j., sew --s ywsw ee. - ----


.T-5.b.

ss.us-s vu. ',p, wy -s , ww.,.vv s M_m,Mh.,,,5 b '. )=Ek# =Nb.~,.5;u =m.cNhk_dk.

n. -,

m,. s-5,,.b. [m __.mh,_.M M .a _ M h - a c.u . - -.s --..c.m.c. ..w- -5 . r.w eo m .~ev._ gg ,..eup - g ,,~,,.s, w. p.;f-- y :^:- 5,5,- J.s.4.e ic_M

  • s,.-

'y'~ u,Ui.c.-.

qy y-f J_~_k z-37---

er s,.s - ~,.r,,r,.s_e: ,,s r .r ._ g g- -] u.r.a.-i ..d; r.;C a ,,w. s- ,w s~ w.N

  • g wo an

'"W _ M" .L t**1n*C,H ~i^=l _a,: -=-__J waw

_=-=---=-

e 2. n =-= s~st tme

  • w.;;y,,;,=.s; tv

~s m e~ . =gg--gj f._.E;-

f.,p =y_r.r r. n_M gn 00L.s, n,f,,-N_,7M m_a c

A ,s., J-v.s,.,s M- . g,; g p-._~.,.yp gg t_ c aar ;' " isY1 r.Ou.-3. CaXt n" tt+i bytr e-^' ,v,. q gg4_,.y h,v, .ChL, w 2,, y..m,.,,,,., _2.,.~, ae , m_u.,

s. <v =..y=

.7,J.a s.,.m.-M [ NO ..r 'O ~. ~e v - w%..- 84 8"i s.~,_,.s.,L w,, m.m=s, s., - = s,,_ ~, a. . _ - -. t0 n m.,o,,,.,=,,. ~~ - _m ~ m.i,~es.,, 3.r,%._ _.,._.a.,, .,,.,,.q .c.s 4,_ ,M_ _,. .k r'"a00._.,. 0,0_M._b,, 4-yvs_., _'_v. __.Od.MM.,. 7 .d _Q-C,. _c Mm.,e-. _ _wm__ e, v s 3_ _, ~2 n,w. .a ~_ wa.w ~ ~ ,., ~ 'b i .m.,m_.,,m._._ M_m;Mm. _ _ _. _ _.,_.,.gN,,. .,@+-m..,,.~,_

.:*e e

y 0.m0 W q 13 n

h.,,.,nM, h_E T,

.e 55 h_,M '5+

_ap

~ uu s_,;ms_q 1,;. bm _v. ~ =,a,.M~,,- , q(.,_.23@ .g _ _ ~, -_v3-M ,-.-p 2, a o -~YUIcg,g g-g3 g- 'thhttfvt*t* a o E. k s Ek ski 4 Eo 6 6.E.k.s E4 4 k n 6 4 Eh u s o s k o k e sk o E4 EEnkk sk o e 6 4k..o E4 4ksI4. a o 6 6. ? e.. nnnnnenwe... . n. n. n. n. e. n e. n......... o. o. o.o. n. e e e e e e e e e = ~ ~ ~ n m e e e e e e e m m aOB E33mwm i l l 1 l l

J.t'"', L"'1"!. EP."AL 2,n. "f'"45; :"; Ulll".1 1'.".".,l'i ">I,"f4."Bll' =n "".*n"n'"..unun=?mn;"n n..nia.nin.n. u n u n n.i. l*"...". n".". n** "* """"""finuu!* **""unnianimunninnianimnintimit !!*"""' ilmfmt nn nnunnununnn nn nn n 1%m>m W M 4M: @@W ;M ! gWppm M M M W M MDDMn $1 MR 3Mii! %U $ Uni a!9f' !N! l!i !! WSWN 312HRN $? MMM 35 1: I i

8 H9mB Emm;w w mn! uR8ti 3unn8F3NHmestim em wis il THng &Wi t: ::!: :M! 18l !4h;D 8bW K5 88W38:MUWWRlEw;nW
j il HHi E8 E ?]W :N4;U ;p-18 Rin8; 88 Jt:

CBMRHm 31ES!Mm m HR il !:HBJnrN & N!: EN!!8: 88 18l 88 3 8F : m w8 18;WWSiFU385 + 98m a 1 l Hp38EW Ruzmper Ji ggmu nwf9: :i8 18l lp! W 8!! 18; 88 1ln & am:1,;8l 88W.HW

mn 3m 2 lyna: 88. 88. 88amm ml 88 48e88 avnnaw-u
imiUM WN M !8< 8li !F!Mi @ 862f 8? M :MUE E R i8!M!W3!E3!EUm02buusi,'i!!

H M UPN 3T2 :U: 18' 88 18l 8MN. 18l pwmgin8; 8!rH!PIMEN!W8tumwons 18M wna & t8; 88 !8; 8!! Un 3dd 8!! !8f idn8l38 18; !U! 18; 81M8!3RESERUF 9 40$ li E 38 5 33 M84 18f RE #U 8BG i;OR! 88 $U 88 18i 8!M8l 8!! WWFF:BlFRMMDN NMW2r 485813MW nn 88 6 8hai 9 h!8l 8(n8; 88 3 Bl! 18l !HM8;3i!E1HBhtmeump di! J. Ri aB!i 3B E 88 18l 88 18Ei9n89$$ m O!! !8i8!n8l 88 W 88 38tlHHlU3BMtsss Upp '? l 213ea &@l 8!! W 8! 18lww M 8Ps8I 88 18l Bin 8; 88 WEUMWe m WH m es il." e M 3mm w 88w 8;n81m m 88 w 88w 88 18E88 s 88mesms wuw i: veu anwil: 18; 8li Un lp2l @ W8k # 88 18' 8!! 18; 81! E W mUnU!$MW ii 60 33!@HM 88 18l 88 W %d 88 18' 88 18l 8!! 18L81R8l31! M 3OblNf8 M$8 b MWE 308l 8li !8l 8h E % 18: 8!! 18; 88 18f 88 E 8P 18N RumEMW ii WB813E8i M! @ 88 181 ftNn8F8k 18; 88 @ 88 5 88M au m a sMp2 w 1 '" &nE! 3H31 8k 18l l?8 18; 88 !8: 8k Ulf 88 18f 88 M W381MManin Y _ di: i 543ES! 38 @ 8!! HF 88 !8: lMSMU fun 8; 88dpmei n@@ I eE 3MIM:t 18l 88 18f 88 D6 8EN 84M 31 mnsunWM MnP-i!! l u0818 E 368; 88 18l'8k 18; 88 @$nti &m$!@hel iM7 jji~ J UE 3858131!8l Bil i8; 8l! # 5 thel 33 mmfM81F 1 WEB 1 M! !8: 8E pH 88 ;#W3M ase@V '3fB808!! !8l 88 M 33R!3H81F - lii ~ 08tM8tBW 'N4t.W__8_ .m.,. Easv3 W38 als 2 3NOISTIIM 1Y S1HDISH 3DGmS l d it i n-

.. ~ i l s== ?"ai Y='=*'5"A~m:M' "El'os n I 't=i i: :;;; ".=i E."*',ns ' ras"!!:" t? uasen.s 3 11 "..'.".."..'.':."..I.n..n..n.."..n.."...!.n..i.n..i.n..n..e..n..n. n..i.n..i.n..tt."..i.n..l?.". 4""*'*"4"""'*"*n"f"nin n"En:"inun"n";innnnunnnntn!n. tifunt!"'""' '!j b W M W [MM MMW @ MMlf RM MIMURCMi MMME$85s%sRM i n is M rwiwRUd 14 glm R mmmRmpii sushnl8tMiqMim !, L l D IM Md@ M! [!MM@ff l@ f Y l ' M IR jlMW8@HdmMMifMiRO@yis5MihifMj *! l~ 5 MH MMlM MMFMId5 %l[ h@Me @W@[$f93I@l@l@@88%@$f@$M[f@_ j{ h h i li l 19H58t R@!@ rim 8M@l @MMl JMfM89@9lMlMUMO@8@Mt{f$$$f@L4l l" dB R@f dM i#WHfh Ib MIABNMR1lE@MR8::fM@4 HMR81.

81HHPE@l@FUl4NMR@48Mfit4MW in itif@h afflMRORM8890L88M888MMn8fHis*g pi!

408@@@@MIfRNRON@i:!%FOUf!Hlfl$ RMtE h Q8Ml@M1@fffj@08MN@Il@8HMUNi j P-En l 4%34Nlmpim38 tis Ri!HWHF1%W1MO@ ibiiM31%@ Ew @i@@HMsMMhm@ E ii 7 h WU$3M0$8MM d@l%UD R$ 4@@ @8MUW2 MRi R?M:.$15W@!8@Ml!8M81Mi3M$ Mil 8@@M@@ l{ l E IVMt RRR$MH8% DF8M8: M184@ %Mf W1&MWDWMfDW!WOfEUROM98H488E885ffE i g, RG8 FNr$%im R WW1M@%MH! :!@W1FUWPS$K8PM38MW3fM881HM888MiW llM 1]i NWW1F M30@NFF144 7 '08]00 m 1 @:IM8M845@0@88HF0HiB85in88P ${ i: WLJ mnv1*W*EwavHH 5a 1 rya 8c8Mes@EmmmamWup si5 wmMwm88MEU w8Farswvm: @ W89we8MmwRrm48M88$m888ms it. 'MRROMIMOW WU big 0i145 1%W Wi@ MMlM@8M84MGtMM88tMfHmP Of : MfWi U188W0101 1FW@1451%W$bMSK8MEMafs#88L MM88@@ di 9RR8MBMHMty@MEWW?PW W$0MO@%88MMR8BE pmff41p38> NMUMil4RMM4fHMEMM!1&@$i:51DM:fM8MfMMMMybMd@BlP li l TM9MWW f $141MRMH$3EK@ W8M8MW188%RfE3 R M881Mr ]!, SEMRORURRW8M10Nt8itr ReMAM888824888fh8 Mtw a:: l NR88JM jig @M$iM80iWinMilitMi MiSUM888R88 W 1:: f Qhi$[ %D$M1838fplM8%8$hMM4bj JgR$Mg&B$< 1N> 3!! l jf f i m 43 Mh8Mf9@WMR LRJ$803[f&Uffff@BW;181 / 4:: %D$ 401$)MfM@t$h3fMlfh8%qRW31 888 7 3i! %@nDWRMMRit T.3MM! NIM'd b W 11: ,m wanasMm.galynn88mm8a8e ~ " W XR,8J1 MUM 0jpF .jjj .oo. - ~accusim=- - 2 3MOISTIIM.I.V S1HDISH 3DGirls r

SUMMft 0 ALMOST ALL FLAWS ARE LOCATED AB0VE TUBESHEET IN HIGHEST SLUDGE REGION IN CENTER OF SGS. O MAJORITY OF FLAWS LOCATED ON HOT LEGS AT TDP 0F TUBESHEET. (THESE TENDED TO BE SHALLOW IN DEPTH.) 0 THREE OF 3113 TUBES TESTED IN BATWING REGION CONTAINED DEFECTS. O FLAWS WHICH EXISTED IN MARCH 1985 DISPLAYED ESSENTIALLY N0 GROWTH (0N THE AVERAGE) DURING CYCLE 7 TP!S IS MUCH LESS THAN THE FLAW PROGRESSION RATES OBSERVED DURING CYCLE 6 (17 PERCENT) AND CYCLE 5 (29 PERCENT). ~ 0 A REVIEW 0F 1985 ECT DATA TAPES FOR 43 TUBES WITH NEWLY IDENTIFIED FLAWS OF >60 PERCENT THROUGHWALL REVEALED THAT 31 OF THE FLAWS EXISTED PREVIOUSLY. O A FACTOR OF,12 DECREASE WAS OBSERVED FROM MARCH 1985 TO NOVEMBER 1986 IN THE NUMBER OF TUBE ENDS REQUIRING REPAIR. O SLUDGE' HEIGHTS ARE.AT THEIR LOWEST LEVEL SINCE. PITTING WAS FIRST IDENTIFIED AT MILLSTONE 2 IN 1981 .0 DENT P,ROGRESSION APPEARS MINIMAL BASED ON THREE RESTRICTED TUBES (SAME AS CYCLE 6) AND PRELIMINARY PROFILOMETRY DATA. .~ e ao - 1

== O O e e 1986 REFUELING OUTAGE SG TUBE SLEEVING AND PLUGGING PROGRAM NELSON F. AZEVED0 1 I 1

h a ek- >4 e, MILLSTONE UNIT NO 2 1986 SLEEVING AND PLUGGING PROGRAM 1. SLEEVABLES PLUGGABLES FROM ECT 245 9 ACTUAL 225 28 2. REASONS FOR PLUGGING STEAM GENERATOR #2 16 - HOT LEG RESTRICTIONS 2 - OUT OF C/L SLEEVING B0UNDARY l - UNINSPECTED TUBE STEAM GENERATOR #1 3 - BAT WING DEFECTS 1-OUT OF SLEEVING B0UNDARY l-COLD LEG RESTRICTION 1 - PROBE STUCK IN TUBE - BOTH ENDS SLEEVED 1-ECT RESTRICTION 1 - ADJACENT TO STAY R0D 1-UNACCEPTABLE SLEEVE INSTALLATION

SUMMARY

SLEEVES PLUGGED TUBES ACTUAL TO DATE 5154 1790 EQUIVALENT PLUGS TO DATE 2094 ALLOWABLE " EQUIVALENT" PLUGGING LIMITS REMAINING: + S/G #1 201 = S/G #2 317 = TOTAL 402 = 4 O- .h p, y-w m, m - e.-m, w T----a-w <-v-- -wv< --*w-m- - ~ - - -=m- -aee-p,ese g 9 -@ '" -

. + CONCLUSIONS: o S/G #2 HOT LEG RESTRICTIONS APPEAR TO BE A COMBINATION OF TUBE DENTING AND TUBE BENDING. o BOTTOM PORTION OF THE SLEEVES WHICH WERE REMOVED TO ALLOW FOR PLUGGING WERE BONDED TO TUBES AND HAD TO BE MACHINED. o THE MILLSTONE UNIT NO. 2 SAFETY ANALYSIS REMAINS VALID WITH THE PLUGGING AND SLEEVING CONDUCTED THIS OUTAGE. o THE CORRECTIVE ACTIONS TAKEN (PLUGGING OR SLEEVING) ENSURE TUBE INTEGRITY FOR OPERATION THROUGHOUT CYCLE 8. l l O

_x_ 1986 REFUELING OUTAGE ECT

SUMMARY

a CONCLUSIONS E. P. PERKINS i i I l l i

SUMMARY

& CONCLUSIONS o

IMPROVEMENTS IN ECT TECHNIQUES RESULTED IN POSITIVE DEFINITION OF DIST0RTED INDICATIONS LOCATED NEAR THE TOP 0F THE TUBESHEET, AND IDENTIFICATION OF AN INCREASED NUMBER OF FLAWS. o ESSENTIALLY ~ALL PITS CONTINUE TO BE RELATED TO SLUDGE / DEPOSIT BUILD-UP LOCATED IN THE REGION AB0VE THE TUBESHEETS. MP2 COUNTERMEASURES APPARENTLY SUCCESSFUL IN REDUCING OR o ARRESTING PITTING. o BATWING REGION DEFECTS ANOMALOUS, APPARENTLY ISOLATED OCCURRENCE IN THREE TUBES. o DENT PROGRESSION MINIMAL, EXPECT COMPLETE ARREST IN NEAR FUTURE AS A RESULT OF COUNTERMEASURES INCLUDING THOSE LISTED AB0VE. o WITH THE PLUGGING AND SLEEVING CONDUCTED THIS OUTAGE, THE MILLSTONE UNIT N0. 2 STEAM GENERATORS REMAIN IN CONFORMANCE WITH THE SAFETY ANALYSIS. o THE TESTING, EVALUATION AND CORRECTION CONDUCTED THIS OUTAGE ENSURES THAT SG TUBE INTEGRITY WILL BE MAINTAINED THROUGH CYCLE 8 OPERATION AT MILLSTONE UNIT NO. 2.