f Dt?C b / M C f 1{N)

PRELIMINARY NOTIFICATION

(-

V i

November 23, in77 PRELIMINARY NOTIFICATION OF EVENT OR UNUSUAL OCCUR This preliminary notification constitutes EARLY notice of an event of POSSIBLE safety or public interest significance.

The information i

presented is as initially received without verification or evaluation and is basically all that is known by IE staff on this date, t

Facility: Arkansas Nuclear One-Unit No.1 P

(DN50-313) Arkansas Power and Light t

Subject:

FAILURE OF REACTOR BUILDING COOLING FANS q

The licensee reported the failure of the "B" Reactor Building Cooling Fan on November 22, 1977. The "A" fan had failed earlier on June 2, 1977 (LER 50-313/ 77-13).

does not meet the Facility Technical Specification, LCO 3.3.4, requires two fans powered from independent buses, since the remaining two Reactor Building Cooling Fans, "C&D" are powered from the same bus "B6."

In accordance with Facility Technical Specification, LCO 3.3.6, the plant will be placed in a hot shutdown within 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br />.

The plant will remain shutdown for approximately 10 days. Plans include replacement of one of the two failed fans.

i The licensee does' not plan to make a press release.

~

'~

E94i W I

RIV received notification regarding the fan failure 't 3:30 p.m. on a

November 22, 1977, from

'the Assistant Plant Superintendent, 1

ANO-Unit No. 1.

/

rontact: FKlingler, IE x28019 JSniezek, IE x28019

_ Distribution:

Transmitt' d H St /j/3 e

Chainnan Hendrie Commissioner Bradford Commissioner Kennedy S. J. Chilk, SECY C. C. Kammerer, CA Commissioner Gilinsky (For Distributit>n)

Transmitted: MNBB g ~.f P Bldg // /7 E. Volgenau IE L. V. Gossick, EDO E. G. C'ase,' NP.R

~

Regiong, / i AO }

\\

S. H. Hanauer, EDO O

J. J. Fouchard, PA SS Bldg / l /Cf (MAIL)

R. Hartfield, MIPC C. V. Smith, NMSS P.. J. McTiernan, 0IA i

R. G. Ryan, OSP H. K. Shapar ELD R. Minogue, SD

[,F PRELI,MINARY NOTIFICATION

  • 2 1

f

  • < n g o., -

9903120 46 77U23 210 PDR