Special Rept:On 860616,fire Dampers VS-D-93,95A & 95B Declared Inoperable After Not Fully Closing During Testing. Caused by Damper Binding.After Mechanical Adjustments, Lubrication & Testing,Dampers Returned to Svc on 860707
ML20207C976
Person / Time
Site: Beaver Valley
Issue date: 07/09/1986
From: Lacey W
DUQUESNE LIGHT CO.
To:
NRC OFFICE OF ADMINISTRATION (ADM)
References
ND1SS1:2847, NUDOCS 8607210465
Download: ML20207C976 (2)


Text

-

'Af M

Telephone (412) 393-6000 Nuclear Division P. O. Box 4 SNopingport, PA 15077-0004 July 9, 1986 NDISS1:2847 Beaver Valley Power Station, Unit No. 1 Docket No. 50-334, License No. DPR-66 Special Report United States Nuclear Regulatory Commission Document Control Desk Washington, DC 20555 Gentlemen:

In accordance with Appendix A, Beaver Valley Technical Specification 3.7.15 " Fire Rated Assemblies", the following Special Report is submitted. This report is required when the conditions specified in Technical Specification 3.7.15.a are not satisfied.

On June 16, 1986, during the performance of Beaver Valley's Fire Rated Assemblies Visual Inspection, Beaver Valley Test 1.3-1.33.5, three (3) fire dampers (VS-D-93, 95A, and 95B) were declared inoperable after not fully closing during testing. A fire watch was already in effect in the area due to construction activities. Fire detection in the area was verified to be operable. A Maintenance Work Request was initiated. The dampers were determined to be binding and required minor mechanical adjustments and lubrication. On July 7, 1986, after successful re-testing, the dampers were returned to service. There were no safety implications due to this event as the fire detection system remained operable at all times and the fire watch remained in effect throughout this event.

Very truly yours, i

Wm.

. Lacey Plant Manager DSC/ vat

$$b 060721046S 860707 i

PDR ADOCK 0500 4

I (1

a

July 9, 1986 ND1SS1:2847 Page two i

cc: Dr. Thomas E. Murle:y Regional Administrator United Ste'es Nuclear Regulatory Commission i

Region 1 King of Prussia, PA 19406 C. A. Roteck, Ohio Edison Mr. Peter Tam, BVPS Licensing Project Manager United States Nuclear Regulatory Commission Washington, DC 20555 W. Troskoski, Nuclear Regulatory Commission, BVPS Site Inspector Mr. Alex Timme, CAPCO Nuclear Projects Coordinator, Toledo Edison j

INPO Records Center Suite 1500 1100 circle 75 Parkway Atlanta, GA 30339 G. E. Muckle, Factory Mutual Engineering, Pittsburgh I

Mr. J. A. Triggiani, Operating Plant Projects Manager Mid Atlantic Area Westinghouse Electric Corporation Nuclear Services Integration Division Box 2728 Pittsburgh, PA 15230 American Nuclear Insurers i

c/o Dottie Sherman, ANI Library The Exchange Suite 245 270 Farmington Avenue Farmington, CT 06032 i

I

.I

..