ML20207B811
| ML20207B811 | |
| Person / Time | |
|---|---|
| Site: | Vogtle |
| Issue date: | 07/15/1986 |
| From: | Bailey J GEORGIA POWER CO. |
| To: | Youngblood B Office of Nuclear Reactor Regulation |
| References | |
| 0595V, 595V, GN-1000, NUDOCS 8607180250 | |
| Download: ML20207B811 (10) | |
Text
-
Georgia Rwrer Company Pbst Offico Box 282 Waynesborn Georgi 2 30830 Telephone 404 554-9961 404 724-8114 Southem Company Services. Inc Post Office Box 2625 Birmingham, Alabama 35202 reiepnene 20s 8** "
Vogtle Project July 15, 1986 Director of Nuclear Reactor Regulation File: X7BC35 Attention:
Mr. B. J. Youngblood Log:
GN-1000 PWR Project Directorate #4 Division of PWR Licensing A U. S. Nuclear Regulatory Commission Washington, D.C.
20555 NRC DOCKET NUMBERS 50 -424 AND 50-425 CONSTRUCTION PERMIT NUMBERS CPPR-108 AND CPPR-109 V0GTLE ELECTRIC CENERATING PIANT - UNITS 1 AND 2 SER OPEN ITEMS 7 & 8:
FIRE PROTECTION
Dear Mr. Denton:
I an attaching a synopsis of the changes made to FSAR Appendix 9A as presented in Amendment 24. Within one week I expect to have a synopsis of the Appendix 9B cha.tges as presented in Amendments 23 and 24. The Appendix 9B synopsis will be sent to the NRC when it becomes available.
If your staff requires any additional information, please do not hesitate to contact me.
Since rely, J. A. Bailey Project Licensing Manager JAB /sm Attachment xc:
R. E. Conway NRC Regional Administrator R. A. Thomas NRC Resident Inspector J. E. Joiner, Esquire D. C. Teper B. W. Churchill, Esquire W. C. Ramsey (w/o att.)
M. A. Miller (2)
L. T. Cucwa B. Jones, Esquire Vogtle Project File G. Bockhold,'Jr.
0595V g
8607180250 860715 k
PDR ADOCK 05000424 E
t
{
t l
l AMENDMENT 24 CHANGES TO APPENDIX 9A 1.
General a.
Revised the analysis to reinstate the fire zone within a fire area concept to allow proper:
o Quantification of combustibles o
Identification of fire detection systems o
Identification of fire suppression systems b.
Updated the analysis with current combustible loading information.
c.
Replaced the postulated fire evaluation with an evaluation of the safe shutdown capability for a fire in the area.
This new approach:
o Assumes a " worst case" postulated fire o
Defines the safe shutdown train that is free of fire damage o
Defines any special operational and design considerations o
Defines the spurious actuation considerations d.
Defined the existence and specifics of the fire detection systems in each fire area on a fire zone
- basis, e.
Defined the existence and specifics of the fire suppression systems in each fire area on a fire zone
- basis, f.
Updated the ventilation discussion to reflect the availability of the smoke removal system.
The I
discussion specifically identifies where a smoke removal system may not function due to the existence of electrical power and control cables for the system
)
within the area.
g.
Updated the emergency lighting discussion to define the existence of fixtures necessary for fire event safe shutdown operational considerations.
1 J
r h.
Updated the deviations and justifications discussion to reflect the finalization of the safe and alternate shutdown evaluation and the changes made to the fire area boundaries.
Table 1 identifies the existence and type of deviations included in the updated submittal on a fire area basis.
i.
Updated the safe shutdown component listing-in each fire area to include intermediate components (i.e.,
solenoid valves for air operated valves, interlock instruments for pumps, etc.) consistent with the listing of components presented in FSAR Table 9.5.1-1.
J.
Updated the area descriptions to define the existence of rated barriers internal to a fire area provided for life safety considerations.
k.
Updated the area descriptions to define the existence of rated barriers internal to a fire area for the purpose of providing separation of safe shutdown trains.
1.
Updated the area descriptions to define the existence of rated barriers internal to a fire area provided for fire suppression system design considerations.
2.
Combined fire areas to eliminate unrated hatches in fire area boundary barriers:
Amendment 15 Fire Area Amendment 24 Fire Area 1-AB-LC-G (partial) combined with 1-AB-LD-G 1-AB-LC-F combined with 1-AB-LD-G 1-AB-LB-B combined with 1-AB-LD-G 1-AB-LA-C combined with 1-AB-LD-G 1-AB-L1-A combined with 1-AB-LD-B 1-AB-L1-E combined with 1-AB-LA-B 1-AB-L1-D combined with 1-AB-LD-G 1-AB-L2-D combined with 1-AB-LA-B 1-AB-L2-F combined with 1-AB-LD-G 3
Combined fire areas to eliminate oversize fire dampers in fire area boundary barrier:
Amendment 15 Fire Area Amendment 24 Fire Area 1-AB-L2-B combined with 1-AB-L2-A 1-EB-A combined with 1-AB-L2-A 2
4.
Combined fire areas to eliminate. unrated watertight doors in
. fire area boundary barriers:
Amendment 15 Fire Area Amendment 24 Fire Area 1-AB-LC-G (partial) combined with 1-AB-LD-G 5.
Combined fire areas to eliminate unsealed openings in fire area boundary barriers:
Amendment 15 Fire Area Amendment 24 Fire Area 1-AB-LD-A (partial) combined with 1-AB-LA-D 1-AB-LD-A (partial) combined with 1-AB-LB-B (new) 1-AB-LC-G (partial) combined with 1-AB-LD-A 1-AB-LB-A (partial) combined with 1-AB-LB-B (new) 1-AB-L1-B (partial) combined with 1-AB-LD-A 1-CB-LC-B (partial) combined with 1-CB-L3-M 1-CB-LB-D (partial) combined with 1-CB-LB-A 1-CB-L2-C combined with 1-CB-L1-C
':l":l":l
- ":"lll" 1-CB-L3-G combined with 1-CB-L4-A 1-CB-L3-I combined with 1-CB-LC-A 2-CB-L1-B combined with 1-CB-L1-B 2-CB-L2-D (partial) combined with 1-CB-L4-A 2-CB-L2-E (partial) combined with 1-CB-L2-E 1-FB-LC-A combined with 1-AB-LD-B 1-FB-LB-A combined with 1-FB-LC-A 1-DPB-C combined with 1-DPB-B 1-AFB-D (partial) combined with 1-AFB-C 1-RWST combined with 1-NSP-LA-B 6.
Created new fire areas (added rated barriers in some cases) to obtain adequate separation between safe shutdown trains or to address unique plant locations:
l 3
r o
Amendment 24 Fire Area Amendment 15 Fire Area 1-AB-LB-B (relocated) previously 1-AB-LC-G (partial) 1-AB-LB-A (partial) 1-AB-LD-A (partial) 1-AB-LA-C (relocated) previously 1-AB-LD-A (partial) 1-AB-LA-E previously 1-AB-LD-A (partial) 1-CB-LB-T previously 1-CB-LB-A (partial) 1-CB-LA-U previously 1-CB-LA-I (partial) 2-CB-L3-E previously 1-CB-L3-E 2-CB-L3-F previously 1-CB-L3-F 1-AFB-E previously 1-AFB-A (partial) 1-AFB-F previously 1-AFB-B (partial) 1-NSP-LA-C previously 1-NSP-LA-B (partial) i 4
T Table 1 DEVIATIONS JUSTIFIED IN FSAR APPENDIX 9A (AMENDMENT 24)
Unrated Unrated Unlabeled Distance FSAR Exterior Containment Unrated Oversize.
Separation Appendix 9A Fire Area Fire Area Watertight Unlabeled Fire w/o Full Area Fire Area Section Boundary Boundary Door Fire Door Damper Suppression 1-AB-LD-A 9A.1.1 X
X X
1-AB-LD-B 9A.1.2 X
X X
X X
1-AB-LD-C 9A.1.3 1-AB-LD-D 9A.1.4 X
1-AB1:4-E 9A.1.5 1-AB-LD-F 9A.1.6 X
1-AB-LD-G' 9A.1.7 X
X X
1-AB-LD-H 9A.1.8 X
1-AB-LD-I 9A.1.9 X
X.
X 1-AB-LD-J 9A.1.10 X
1-AB-LD-PC 9A.1.11 1-AB-LC-A 9A.1.12 1-AB-LC-B 9A.1.13 X
1-AB-LC-C 9A.1.14 1-AB-LC-D 9A.1.15 1-AB-LC-E 9A.1.16 1-AB-LB-A 9A.1.19
- Unrated Hatch Deviation 1
Unrated Unrated Unlabeled Distance FSAR Exterior Containment Unrated Oversize Separation Appendix 9A Fire Area Fire Area Watertight Unlabeled Fire w/o Full Area Fire Area Section Boundary Boundary Door Fire Door Damper Suppression l
1-AB-LB-B 9A.1.20 X
l 1-AB-LA-A 9A.1.22 1-AB-LA-B*
9A.1.23 X
X 1-AB-LA-C 9A.1.24 1-AB-LA-D 9A.1.25 X
X X
1-AB-LA-E 9A.1.26 X
X X
1-AB-L1-B 9A.1.27 X
X i
1-AB-L1-C 9A.1.28 l
1-AB-L1-G 9A.1.31 X
1-AB-L1-H 9A.1.32 X
1-AB-L2-A 9A.1.33 X
X X**
X 1-AB-L2-C 9A.1.35 X
1-AB-L2-E 9A.1 37 x
1-CB-LC-A 9A.1.39 X
X 1-CB-LC-B 9A.1.40 X
1-CB-LC-D 9A.1.41 1-CB-LB-A 9A.1.42 X
X X
1-GB-LB-B 9A.1.43 1-CB-LB-C 9A.1.44 1-CB-LB-D 9A.1.45 X
X X
1-CB-LB-E 9A.1.46
- Unrated Hatch Deviation l
- FSAR to be amended to reflect this mission l
2 1
T Unrated Unrated Unlabeled Distance FSAR Exterior Containment Unrated Oversize separation Appendix 9A Fire Area Fire Area Watertight Unlabeled Fire w/o Full Area Fire Area Section Boundary Boundary Door Fire Door Damper Suppression 1-CB-LB-F 9A.1.47 1-CB-LB-G 9A.1.48 X
1-CB-LB-H 9A.1.49 1-CB-LB-I 9A.1.50 1-CB-LB-J 9A.1.51 1-CB-LB-K 9A.1.52 1-CB-LB-L 9A.1.53 1-CB-LB-M 9A.1.54 1-CB-LB-N 9A.1.55 1-CB-LB-O 9A.1.56 1-CB-LB-P 9A.1.57 1-CB-LB-Q 9A.1.58 1-CB-LB-R 9A.1.59 1-CB-LB-S 9A.1.60 X
1-CB-LB-T 9A.1.60A X
1-CB-LA-A 9A.1.61 X
1-CB-LA-B 9A.1.62 X
1-CB-LA-C 9A.1.63 1-CB-LA-D 9A.1.64 X
X 1-CB-LA-E 9A.1.65 X
1-CB-LA-F 9A.1.66 X
X l
1-CB-LA-G 9A.1.67 l
1-CB-LA-H 9A.1.68 l
l 3
i a
Unrated Unrated Unlabehd Distance FSAR Exterior Containment Unrated Oversize Separation Appendix 9A Fire Area Fire Area Watertight Unlabeled Fire w/o Full Area Fire Area Section Boundary Boundary Door Fire Door Damper Suppression 1-CB-LA-I 9A.1.69 X
1-CB-LA-J 9A.1.70 1-CB-LA-K 9A.1.71 1-CB-LA-L 9A.1.72 1-CB-LA-M 9A.1.73 1-CB-LA-N 9A.1.74 X
X 1-CD-LA-O 9A.1.75 1-CB-LA-P 9A.1.76 1-CB-LA-Q 9A.1.77 1-CB-LA-R 9A.1.78 1-CB-LA-S 9A.1.79 X
1-CB-LA-T 9A.1.80 X
1-CB-LA-U 9A.1.80A 1-CB-L1-A 9A.1.81 X
X 1-CB-L1-B 9A.1.82 X
X 1-CB-L1-C 9A.1.83 X
1-CB-L1-D 9A.1.84 X
1-CB-L1-E 9A.1.85 X
1-CB-L1-F 9A.1.86 X
1-CB-L1-G 9A.1.87 X
1-CB-L1-TSC 9A.1.88 X
X 1-CB-L2-A 9A.1.89 X
1-CB-L2-B 9A.1.90 4
Unrated Unrated Unlabeled Distance FSAR Exterior Containment Unrated Oversize Separation Appendix 9A Fire Area Fire Area Watertight Unlabeled Fire w/o Full Area Fire Area Section Boundary Boundary Door Fire Door Damper Suppression 1-CB-L2-E 9A.1.93 X
X 1-CB-L3-A 9A.1.94 X
1-CB-L3-B 9A.1.95 X
1-CB-L3-C 9A.1.96 X
1-CB-L3-H 9A.1.101 X
1-CB-L3-J 9A.1.103 X
1-CB-L3-K 9A.1.104 X
X 1-CB-L3-L 9A.1.105 X
1-CB-L3-M 9A.1.105A X
1-CB-L4-A 9A.1.106 X
X 1-FB-LC-A 9A.1.107 X
1-FB-L3-A 9A.1.109 X
1-FB-L3-B 9A.1.110 X
1-CTB 9A.1.111 X
X 1-EB-B 9A.1.113 X
X 1-DB-L1-A 9A.1.114 X
X 1-DB-L1-B 9A.1.115 X
X 1-DB-L1-C 9A.1.116 X
1-DB-L1-D 9A.1.117 X
1-DPB-A 9A.I.118 X
1-DPB-B 9A.1.119 X
X 1-AFB-A 9A.1.121 X
1-AFB-B 9A.1.122 X
5
Unrated Unrated Unlabeled Distance FSAR Exterior Containment Unrated Oversize Separation Appendix 9A Fire Area Fire Area Watertight Unlabeled Fire w/o Full Area Fire Area Section Boundary Boundary Door Fire Door Damper Suppression 1-AFB-C 9A.1.123 X
1-AFB-D 9A.1.124 X
X 1-AFB-E 9A.1.124A X
1-AFB-F 9A.1.124B X
1-NSP-LA-A 9A.1.125 X
1-NSP-LA-B 9A.1.126 X
X 1-NSP-LA-c 9A.1.126A X
1-RB-LA-A 9A.1.127 X
1-HPB-L1-A 9A.1.128 X
1-RTB-L1-A 9A.1.129 X
6