Amend 100 to License DPR-51,revising Tech Specs by Deleting Tabular Listings of Shock Suppressors Per Generic Ltr 84-13
ML20206U470
Person / Time
Site: Arkansas Nuclear 
Issue date: 09/19/1986
From: Stolz J
Office of Nuclear Reactor Regulation
To:
Arkansas Power & Light Co
Shared Package
ML20206U475 List:
References
DPR-51-A-100, GL-84-013 NUDOCS 8610070510
Download: ML20206U470 (7)


Text

.

p Ktc

=

e

/

UNITED STATES

/1 NUCLEAR REGULATORY COMMISSION

{

WASHINGTON, D. C. 20555 j?

ARKANSAS P0h'ER AND LIGHT COMPANY DOCKET NO. 50-313 APKANSAS NUCLEAR ONE, l' NIT 1 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No.100 License No. DPR-51 1.

The Nuclear Regulatory Commission (the Commission) has found that:

A.

The application for amendment by Arkansas Power and Light Company (the licensee) dated January 24, 1986, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commission's rules and regulations set forth in 10 CFR Chapter I; B.

The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commissica; C.

There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and

]

safety of the public, and (ii) that such activities wil.1 be conducted

~'

in compliance with the Commission's regulations; D.

The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E.

The issuance of this anendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.

2.

Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment, and paragraph 2.c.(2) of Facility Operating License No. DPR-51 is hereby amended to read as follows:

I gains Beu,h P

-7 Technical Specifications The Technical Specifications contained in Appendices A and B, as revised through Amendment No.100, are hereby incorporated in the license. The licensee shall operate the facility in accordance with the Technicsl Specifications.

3.

This license amendment is effective as of its date of issuance.

FOR THE NUCLEAR REGULATORY COV. MISSION 5N John F. Stolz, Director PWR Project Directorate #6 Division of PWR Licensing-B

Attachment:

Changes to the Technical Specifications Date of Issuance: September 19, 1986 h

ATTACHMENT TO LICENSE AMENDMENT NO.100 FACILITY OPERATING LICENSE N0. DPR-51 LOCKET N0. 50-313 Replace the following pages of the Appendix "A" Technical Specifications with the attached pages. The revised pages are identified by Amendment number and contain vertical lines indicating the area of change.

Pemove Insert 661 661 1

66j 66j 66k 661 661-1 661-2 661-3 661-4 661-5 661-6 661-7 110e 110e 129 129

3.16 Shock Suppressors (Snubbers)

Applicability This technical specification applies to all shock suppressors (snubbers).

The only snubbers excluded from this requirement are those installed on nonsafety-related systems and then only if their failure or failure of the system on which they are installed, would have no adverse effect on any safety-related system.

Objective To assure adequate shock suppression protection for primary coolant system piping and any other safety related system or component under dynamic loads as might occur during an earthquake or severe transient, while allowing normal thermal motion during startup and shutdown.

This is done by assuring the operability of those shock suppressors installed for that purpose.

Specification 3.16.1 The reactor shall not be heated above 200F if any applicable shock l suppressor is known to be inoperable.

3.16.2 If any applicable shock suppressor is determined to be inoperable l

during power operation, that shock suppressor shall be made operable or replaced within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or the reactor shall be placed in the cold shutdown condition within an additional 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br />.

Bases Shock suppressors are designed to prevent unrestrained pipe motion under dynamic loads as might occur during an earthquake or severe transient, while allowing normal thermal motion during startup and shutdown.

The consequence of an inoperable shock suppressor is an increase in the probability of structural damage to piping as a result of a seismic or other event initiating dynamic loads.

It is therefore required that all shock suppressors required to protect the primary coolant system or any other

/

safety system or component be operable during reactor operation.

Because the shock suppressor protect. ion is required only during low probability events, a period of 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> is allowed for repairs or replacements.

In case a shutdown is required, the allowance of 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br /> to reach a cold shutdown condition will permit an orderly shutdown consistent with standard operating procedures.

Since plant startup should not commence with knowingly defective safety related equipment, Specification 3.16.1 prohibits startup with inoperable shock suppressors.

Amendment No. 73, #,100 661.

TABLE 3.16-1 i

SAFETY RELATED HYDRAULIC SHOCK SUPPRESSORS (SNUBBERS)

(DELETED) i TABLE 3.16-2 SAFETY RELATED MECHANICAL SHOCK SUPPRESSORS (SNUBBERS)

(DELETED) i l

i f

66j (NEXT PAGE 66m)

Amendment No. 23, #5, Ef,100 I

l<

4.16-

' SHOCK SUPPRESSORS (Snubb@rs)

Applicability This technical specification applies to all shock suppressors (snubbers).

The only snubbers excluded from this requirement are those installed on nonsafety-related systems and then only if their failure or failure of the system on which they are installed would have no adverse effect on any safety-related system.

Objective Verify an acceptable level of operability of the shock suppressors protecting the primary system and any other safety related system or component.

Specification 4.16.1 The following surveillance requirements apply to all applicable shock suppressors.

a.

Inspection Types As used in this specification, type of snubber shall mean snubbers of the same design and manufa turer, irrespective of capacity.

Snubbers are categorized as inaccessible or accessible during reactor operation.

b.

Visual Inspections Visual inspections shall be performed in accordance with the following schedule:

No. Inoperable Snubbers Subsequent Visual per Inspection Period Inspection Period 0

18 months 25%

1 12 months 25%

2 6 months 25%

3, 4 124 days 1 25%

5,6,7 62 days 25%

8 or more 31 days 25%

The snubbers may be categorized into groups based on type and accessibility.

Each group may be inspected independently in accordance with the above schedule.

The inspection interval for each type of snubber sball not be lengthened more than one step at a time unless a generic problem has been identified and corrected; in that event the inspection interval may be lengthened one step the first time and two steps thereafter if no inoperable snubbers of that type are found.

The provisions of Specification 4 regarding surveillance intervals are not applicable.

Amendment No. 23, pp,100

1 i

1 h.

Records of in-service inspections performed pursuant to these Technical Specifications.

i.

Records of Quality Assurance activities required by Section 17 of the Quality Assurance Manual for Operations, j.

Records of reviews performed for changes made to procedures or equipment or reviews of tests and experiments pursuant to 10CFR50.59.

k.

Records of meetings of the PSC and the SRC.

1.

Records for Environmental Qualification which are covered under the provisions of paragraph 6.13.

m.

Records of the service lives of the seals of all hydraulic snubbers applicable to Specification 3.16 including the date at which the service life commences and associated installation and maintenance records.

n.

Records of the analyses required by the Radiological Environmental Monitoring Program.

6.10 RADIATION PROTECTION PROGRAM Procedures for personnel radiation protection shall be prepared consistent with the requirements of 10CFR Part 20 and shall be approved, maintained and adhered to for all operations involving personnel radiation exposure.

6.11 HIGH RADIATION AREA 6.11.1 In lieu of the " control device" or " alarm signal" required by paragraph 20.203(c)(2) of 10CFR20, each high radiation area (as defined in 20.202(b)(3) of 10CFR20) in which the intensity of radiation is 1000 mrem /hr or less shall be barricaded and conspicuously posted as a high radiation area and shall be controlled by requiring the issuance of a radiation work permit.

Any individual or group of individuals permitted to enter such areas shall 'e provided with or accompanied by one or more of the following:

o a.

A radiation monitoring device which continuously indicates the radiation dose rate in the area.

b.

A radiation monitoring device which continuously integrates the radiation dose rate in the area and alarms when a pre-set integrated dose is received.

Entry into such areas with this monitoring device may be made after the dose rate level in the area has been established and personnel have been made knowledgeable of them.

c.

An individual qualified in radiation protection procedures who is equipped with a radiation dose rate monitoring device.

This individual

? hall be responsible for providing positive control over the activities within the area and shall perform periodic radiation surveillance at the frequency specified in the radiation work permit.

129 Amendment No. JS, Af, 53, 10/24/S0 Ordci, 64, S4, S3,100