Provides Info Re Number of Tubes Plugged in Each Sg,As Required by TS 4.4.5.5.ISI of SGs B & C Completed on 990424,resulting in Mechanical Plugging of One Tube in SG B & Five Tubes in SG C
ML20206K514
Person / Time
Site: Wolf Creek 
Issue date: 05/07/1999
From: Muench R
WOLF CREEK NUCLEAR OPERATING CORP.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
ET-99-0020, ET-99-20, NUDOCS 9905130185
Download: ML20206K514 (1)


Text

e i

LF CREEK W8) NUCLEAR OPERATING l

Richard A. Muench Vice President Engineering 7gggg ET 99-0020 U. S. Nuclear Regulatory Commission ATTN:

Document Control Desk Mail Station P1-137 Washington, D.

C.

20555

Subject:

Docket No. 50-482:

Special Report 99-001 - Steam Generator Tube Plugging Report Gentlemen:

This letter provides information regarding the number of tubes plugged in each steam generator as required by Wolf Creek Generating Station Technical Specification 4.4.5.5.

This technical specification requires, in part, that i

'the number of tubes plugged in each steam generator be reported to the Nuclear Regulatory Commission within 15 days following the cortpletion of each j

inservice inspection of the steam generator tubes, The inservice inspection of Steam Generators "B" and "C" was completed on i

April 24, 1993

'This inservice inspection resulted in the mechanical plugging of one tube in Steam Generator "B" and five tubes in Steam Generator "C".

Mechanical plugging was necessary because of indications of anti-vibration bar wear found during the inservice inspection.

Steam Generators "A" and "D" were not inspected during this inservice inspection.

Including the tubes plugged during this inservice inspection, the total number of tubes plugged, due to inservice degradation, in each steam generator to date are as follows:

Steam Generator "A" 15 tubes Steam Generator "B" 19 tubes Steam Generator "C" 12 tubes Steam Generator "D" 51 tubes If you have any questions concerning this matter, please contact me at (316) 364-4034, or Mr. Michael J. Angus, at (316) 364-4077.

Very truly yours, 4