i GecT4 R7*v Ccrepany rost Off<e Box 282 W:ynestera Georg a 30e3o

' ~.

TeVone 404 554 9961. Ente son 3413 I

404 723 4114 ELiterson 3413 z.

, I *. 3 7 GeorgiaPower p, a ng,

,,,,n v<e Present Mt19 rf 0ffCl ge n e v:e~e,c w:

November 7,1988 United States Nuclear Regulatory Commission ATTN: Document Control Desk File:

X78G10 Washington, D. C.

20555 Log: GN-1505

Reference:

Vogtle Electric Generatinc Plant - Unit 2 USHRC Inspection Report 50-425/88-48 l

Georgia Power Company wishes to submit the following information concerning the violation identified in the referenced inspection report.

i Violation 50-425/88-48-01 Failure to Properly Tighten Flexible Conduit in Containment.

l Georgia Power Company (GPC) acknowledges the violation as identified in the USNRC report.

The connections were apparently loosened during the Containment wash down evaluation.

The connections identified in the inspection report were retightened during the required walkdown prior to the room / area release for testing on September 15 1988.

In addition, all the flexible conduit connections on Level One of i

the Containment were checked for tightness and found to be snug tight i

i on October 24 and 25, 1988.

j To avoid further violations, a review of the present program for snug i

tightness was performed and no changes were deemed necessary.

However.

at the time of future room / area turnovers, field engineering has been i

I instructed to place additional emphasis on verifying the proper installation of flexible conduits.

Full compliance was achieved November 3. 1988.

1 l

f i

I i

I i

8811230230 081107 PDR ADOCK 05000425 O

PNV

[

R( /

e.

C C

File:

X78G10 Log:

GN-1505 November 7. 1988 Page two These responses contain no proprietary infonnation and may be placed in the USNRC Public Document Room.

f M W /< v P. D. Rice PDR/wk1 xe:

USNRC - Region II Suite 2900 101 Marietta Street. N. W.

Atlanta, GA 30323 H. G. Baker, Jr.

D. R. Altman J. P. Kane R. P. Mcdonald J. A. Bailey C. W. Hayes R. H. Pinson G. Bockhold, Jr.

R. W. McManus C. K. McCoy G. R. Frederick Sr. Resident (NRC)

E. D. Groover J. E. Swartzwelder C. F. Wreath (OPC)

A. B. Gallant R. A. Thomas J. E. Joiner (TSLA)

NORMS i

h I

I i

9.