Amend 80 to License NPF-4,correcting Errors in Tech Spec for Seismic Instrument Range & Testing Requirements & Deleting Functional Test Requirements for Auxiliary Bldg Mat & Reactor Heat Removal Pipe Support
ML20205S651
Person / Time
Site: North Anna 
Issue date: 05/27/1986
From: Rubenstein L
Office of Nuclear Reactor Regulation
To:
Shared Package
ML20205S652 List:
References
NUDOCS 8606120733
Download: ML20205S651 (5)


Text

.

pauc, o

[f g

UNITED STATES

+

g NUCLEAR REGULATORY COMMISSION 5

"j WASHING TON, D. C. 20555

\\....+/

VIRGINIA ELECTRIC AND POWER CO'4PANY OLD DOMINION ELECTRIC COOPERATIVE DOCKET NO. 50-338 N0r.TH At:NA POWEP STATION, UNIT NO.1 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. 30 License No. NFF-4 1.

The Nuclear Regulatory Commission (the Commission) has found that:

A.

The application for amendment by Virginia Electric and Pcwer Company et al., (the licenseel dated May 17, 1985 as superseded November 15, 19B5, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commission's rules and regulations set forth in 10 CFR Chapter I; B.

The facility will operate in conformity with the application, the orovisions of the Act, and the rules and regulations of the Commission; C.

There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without erdangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Coninission's regulations; D.

The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E.

The issuance of this amendn.ent is in accordance with 10 CFR Part 51 of the Comnission's regulations and all applicable reouirements have been satisfied.

l l

8606120733 860527 PDR ADOCK 05000338 P

PDR

. I

. 2. _ Accordingly, the license is amended by changes to the Technical Speci-fications as indicated in the attachment to this license amendment, and paragraph 2.D.(2) of Facility Operating License No. NPF-4 is hereby amended to read as follows:

(2) Technical Specifications The Technical Specifications contained in Appendices A and B, as revised through Amendment No. 80, are hereby incorporated in the license. The licensee shall operate the facility in accordance with the Technical Specifications.

3.

This license amendment is effective as of the date of its issuance.

~

FOR THE NUCLEAR REGULATORY COMMISSION

....k 6)$bILester S. Rubenstein, Director tyd1PWRProjectDirectorate#2 Division of PWR Licensing-A

Attachment:

Changes to the Technical Specifications Date of Issuance: May 27, 1986 l

ATTACHMENT TO LICENSE AMENDMENT NO. 80 TO FACILITY OPERATING LICENSE NO. NPF-4 DOCKET NO. 50-338 Replace the following pages of the Appendix "A" Technical Specifications with the enclosed pages as indicated. The revised pages are_ identified by amendment number and contain vertical lines indicating the area of change.

The corresponding overleaf pages are also provided to maintain document completeness.

4 3/4 3-41 3/4 3-42 l

l r

r -- -

TABLE 3.3-7 SEISMIC MONITORING INSTRUMEllTATION MINIMUM MEASUREMENT INSTRUMENTS INSTRUMENTS AND SENSOR LOCATIONS RANGE OPERABLE
1. Triaxial Time-History Accelerographs
a. Containment Mat
  • 0 - 1.0 g 1
b. Containment Operating Level
  • 0 - 1.0 g 1
2. Triaxial Peak Accelerographs
a. RHR Heat, Exchanger 0 - 5.0 g 1
b. Safety Injection pipe 0 - 5.0 g 1
c. Component Cooling Heat Exchanger 0 - 5.0 g 1
3. Triaxial Seismic Switches
a. Containment Mat
  • NA NA
4. Triaxial Response-Spectrum Recorders
a. Containment Mat
  • 1 - 30 Hz 1
b. Auxiliary Building Mat 1 - 30 Hz 1
c. RHR Pipe Support 1 - 30 Hz 1
d. Component Cooling Heat Exchanger 1 - 30 Hz I

Support f

  • With reactor control room indication l

l l

l NORTH ANNA - UNIT 1 3/4 3-41 Amendment No. 80

(

i..

TABLE 4.3-4 SEISMIC MONITORING INSTRUMENTATION SURVEILLANCE REQUIREMENTS CHANNEL CHANNEL CHANNEL FUNCTIONAL INSTRUMENTS AND SENSOR LOCATIONS CHECK CALIBRATION TEST

1. Triaxial Time-History Accelerographs
a. Containment Mat M*

R SA*

b. Containment Operating Level M*

R SA*

2. Triaxial Peak Accelerographs
a. RHR Heat Exchanger NA R

NA

b. Safety Injection Pipe NA R

NA

c. Component Cooling Heat Exchanger NA R

NA

3. Triaxial Seismic Switches
a. Containment Mat NA R

SA

4. Triaxial Response-Spectrum Recorders
a. Containment Mat M**

R NA

b. Auxiliary Building Mat M***

R NA

c. RHR Pipe Support NA R

MA

d. Component Cooling Heat Exchanger Support M***

R NA

  • Except seismic trigger
      • Testing will only include a visual inspection to detect for signs of obvious physical damage NORTH ANNA - UNIT 1 3/4 3-42 Amendment No. 80