w VALTEK April 8, 1986 Director, Office of Inspection and Enforcement US Nuclear Regulatory Commission Washington, D.C.

20555

Dear Director:

This is in response to our letter to you of March 11, 1986.

(Copy attached).

As a result of information from Cardinal Ind-ustrial Products, we have determined the bolting supplied to Bechtel for Houston Lighting and Power (South Texas Project) has been upgraded by Cardinal and therefore is acceptable and will have so notified our customer.

The material supplied to Carolina Power and Light on the Brunswick Steam Electric Plant has been tested by Cardinal to assure it is what it purports to be.

Cardinal has not been able to audit the supplier (Huntington Alloys) and will no longer use them.

We also believe this material is acceptable.

Copies of each of these communications is also attached.

Sincerely, L.L.

Schroeppel V.P.

Administration cc:

Director of Region IV i

Office of Inspection and Enforcement US Nuclear Regulatory Commission j

611 Ryan Plaza Drive, Suite 1000 y.

l

  • h Arlington, Texas 76012 O{'Ih3

'Of

gr988a at88Hr S

Mountain Springs Parkway N

Box 2200 / Springville Utah 84663-2200 USA / Phone 801-489-8611/ Telex 388-458

\\

03/11/86 VALTEK Director, Office of Inspection and Enforcement US Nuclear Regulatory Commission Washington, D.C. 20555 Dear Director We have been advised by letter received on Feb.

27,

1986, by a former vendor, Cardinal Industrial Products Corporation (3873 West Oquendo, Las Vegas, Nevada 89118) that material on several purchase orders furnished by Cardinal to Valtek Incorporated deviated from ASME Section III, NCA-3800 in that " Improper Qualification of Stock Materials: (NCA-3866.3 (a)) Materials certified as meeting Section III where the stock material was either purchased from a non-qualified source or the audit used to qualify the source was inadequate.

No subsequent upgrading was performed." Cardinal has also reported this problem to the NRC. Our investigation has determined that these parts were furnished to the following customers on the following valves:

Carolina Power & Light - Brunswick Steam Electric Plant Valves serial no.

35411-1-1, 35411-1-2 (This only Nuclear intent, not N-Stamp)

Houston Lighting & Power - South Texas Project valves serial no.

34752.004, 34752.009, 34752.010, 34752.011, 34752.012, 34752.014, 34752.015, 34752.016, 34752.017, 34752.020, 34752.039, 34753.009, 34753.010, 34753.011, 34753.012, 34753.014, 34752.015, 34753.016, 34753.017, 34752.039, Each of these customers are also being notified of this problem.

We still have in stock additional quantities of some of these parts which will be tested.

As soon as those test reports are complete you will be notified of the applicable valve and customer.

Sincerely L L Schroeppel V.P. Administration g e.

c Director of Region IV g

Office of Inspection and Enforcement p,y US Nuclear Regulatory Commission 4-611 Ryan Plaza Drive, Suite 1000 Arlington, Texas 76012 Mountain Springs Parkway Box 2200 / Springville. Utah 84663-2200 USA / Phone 801-489-8611/ Telex 388-458

Page 2 Director, Office of Inspection and Enforcement 03/11/86 CC Mr. Gary G. Zech,

^

Chief Vendor Program Branch Division of Quality Assurance Nuclear Regulatory Commission Washington, D.C 20555 Re: Docket No. 99900840/84-01 Attachments 1.

Letter to Carolina Power & Light (Brunswick Steam Electric Plant) 2.

Letter to Bechtel Energy Corp.;

I Agents for Houston Light and Power (South Texas Project) l

,iiii.,,,,

\\/ALL.1rEEPC April 4, 1986 Carolina Power & Light Company Brunswick Steam Electric Plant P.O.

Box 11060 Southport, North Carolina 28461 Attn:

L. H.

Dishman, Principle Buyer

Subject:

Valtok letter of March 12, 1986 regarding bolting from cardinal Industrial Products.

Valtek, Inc. has now received additional information from cardinal regarding material contained in the above referenced notification.

The bolting was all made from material rolled by Huntington Alloys who has not been audited as a vendor.

(All material was furnished under Valtok P.O.

  1. 84N0044 with heat no.'s M0700B, M0708B and M0756B).

Cardinal had performed testing on each piece of starting bar.

copies of the results of these tests are attached.

Cardinal contends that the tests performed are sufficient to show that the material meets the requirements of the material specification.

Valtok supports that viewpoint.

These tests also support the orig-inally submitted certifications for the material.

Sincerely, m

L.L.

Schrooppel V.P.

Administration and Quality Assu nce Manager Enc.

Test reports on heats

()

M0700s, M0708B, M0756B.

Mountain Spnngs Parkway Box 2200 / S pringville. Utah 84663-2200 USA / Phone 801-489-8611/ Telex 388-458

03/12/86 VALTEK Carolina Power & Light Company Brunswick Steam Electric Plant P.O. Box 11060 Southport, North Carolina 28461 ATTN: L.H. Dishman, Principal Buyer RE: Brunswick Steam Electric Plant valtok was advised by letter from Cardinal Industrial Products Corporation who has supplied us with bolting materials that materials used in some bolting deviated from ASME Section III, NCA 3800 in that " Improper Qualification of Stock Materials: (NCA-3866.3 (a)) Materials certified as meeting Section III where the stock material was either purchased from a non-qualified source or the audit used to qualify the source was inadequate.

No subsequent upgrading was performed." They also indicated they have reported this condition to NRC.

~The following valves shipped to you on this project even though they are not "N-Stamp" they have used the questioned bolting:

VALVE SN QTY PART NO.

DEM:RIPTION TRACE NO.

35411-1-1 24 2383.542.0009021 1 1/4-8 SB 164 139 Monel Heavy Hex Nut 21 9979.542.0009021 1 1/4-8x8 SB 164 4G32

~~'"

Monel Stud 3

25568.542.0009021 1 1/4-8-8 1/2 SB 164 4G17 TJOO Monel Stud 35411-1-2 24 2383.542.0009021 1 1/4-8SB 164 139 Monel Heavy Hex Nut 21 9979.542.0009021 1 1/4-8x8 SB 164 4G32 Monel Stud 3

25568.542.0009021 1 1/4-8x8 1/2 SB 164 4G17 Monel Stud We have additional quantities of these parts which will be tested to determine if they can be acceptably upgraded.

NRC is being notified of this problem, including a copy of this letter.

Sincerely L L Schroeppel V.P. Administration Mountain Springs Parkway Box 2200 / Springville. Utah 84663-2200 USA / Phone 801-489-8611/ Telex 388-458

w April 4, 1986 VALTEK E.D.

Bailey IFFO Manager Bechtel International P.O. Box 2166 Houston, TX 77252-2166

Subject:

Valtok letter of March 12, 1986 regarding bolting from Cardinal Industrial Products.

only on valve was involved, cur serial number 23866-4-6.

This was Bechtel P.O.

  1. 13081-3-J-601, item 110, Bechtel tag number A-8J-AB-PV301, shipped 5/14/84, invoice number 134296.

Also there was only one (1) 1-1/4-8 nut manufactured using starting material from a heat produced by a vendor where the audit used to qualify the vendor was not complete or sufficient in depth.

N.R.C.

has accepted Cardinal's program which includes reverification of all Chemical and Physical reports and of the vendor.

Cardinal confirms all of this has been satisfactorily accomplished.

In view of this upgrade of the questioned material, we support Cardinal Industrial Product's claim that this is acceptable material.

Sincerely, L.L.

Schroeppel V.P.

Administration and Quality Assurance Manager Enc:

Letter from N.R.C.

Cardinal Industrial Products Report #3.

CD C0 v

Mountain Spnngs Parkway Box 2200 / Springville. Utah 84663-2200 US A / Phone 801-489-8611/ Telex 388-458

03/12/86 VALTEK Bechtel Incorporated Yeonggwang Jobsite Sang Hari, Hong Nong Yeong Gwang Gun, Jun Nam Korea 501-27 RE: Korea Electric Project Korea Nuclear Units 7 C 8 Valtok was advised by letter from Cardinal Industrial Products Corporation who has supplied us with bolting materials that materials used in seme bolting deviated from ASME Section III, NCA 3800 in that " Improper Qualification of Stock Materials:

(NCA-3866.3 (a)) Materials certified as meeting Section III where the stock material was either purchased from a non-qualified source or the audit used to qualify the source was inadequate.

No subsequent upgradinj was performed." They also indicated they have reported this condition to NRC.

The following valves shipped to you on this project have included the questionable bolting:

VALVE SN QTY PART NO.

DESCRIPTION TRACE NO.

23866-4-6 1

2383.014.0009005 1 1/4-8 SA 1942H Z57 Heavy Hex Nut Sincerely L L Schroeppel V.P. Administration Oo Mountain Springs Parkway Box 2200 / Springville. Utah 84663-2200 USA / Phone 801-489-8611/ Telex 388-458

v VALTEK April 4, 1986 Bechtel Energy Corporation Agents for Houston Light & Power Co.

P.O. Box 2166 Houston,.TX 77252-2166 Attn:

L.M.

Ray subject:

valtok letter of March 12, 1986 regarding bolting from Cardinal Industrial Products.

We have been informed by Cardinal that all of the bolting referenced by their letter to Valtok and also ours to you and the N.R.C.

Here manufactured using starting materials from a heat produced by a I

vendor, where the audit used to qualify the vendor was not complete or sufficient in depth.

N.R.C. has accepted Cardinal's program which includes reverification of all Chemical and Physical reports and of the vendor.

Cardinal confirms all of this has been satisfactorily accomplished.

In view of this upgrade of the questioned material, we support Cardinal Industrial Product's claim that this is acceptable material.

Sincerely, L.L. Schrooppel [

V.P. Administration and Quality Assurance Manager cc:

Letter from N.R.C.

Letter & attachments from Cardinal

)

Mountain Springs Parkway Box 2200 / Springville, Utah 84663-2200 USA / Phone 801-489-8611/ Telex 388-458

VALTEK 03/12/86 Bechtel Energy Corporation Agents for Houston Light S Power Co.

P.O. Box 2166 Houston, TX 77252-2166 Attn:

L.M. Ray i

RE: South Texas Project Valtek was advised by letter from Cardinal Industrial Products Corporation who has supplied us with bolting materials that materials used in some bolting deviated from ASME Section III, NCA 3800 in that " Improper Qualification of Stock Materials:

(NCA-3866.3 (a)) Materials certified as meeting Section III where the stock material was either purchased from a non-qualified source or the audit used to qualify the source was inadequate.

No subsequent upgrading was performed." They also indicated they have reported this condition to NRC.

The following valves shipped to you on this project have included the questionable bolting:

P.O. 84N0056, quantity 64, cert no.

42283, was used on 2" valves utilizing 4 nuts each valve (16 total valves)

Trace Letter: J25 Part Number:

1571.014.0009018 Valve SN:

34752.009, 34752.010, 34752.011, 34752.012, 34752.014, 34752.015, 34752.016, 34752.017 34753.009, 34753.010, 37453.011, 34753.013, 34753.014, 34753.015, 34753.016, 34753.017 0o Mountain Springs Parkway Box 2200 / Springville. Utah 84663-2200 USA / Phone 801-489-8611/ Telex 388-458

Page 2 Bechtel Energy Corporation 3/12/86 P.O.

85N0004, quantity 17, cert no.

43103, was used on 4" valves utilizing 8 studs each valve (2 total valves).

The extra stud has been removed from stock and placed on hold.

Trace Letter: 267 Part Number:

3680.012.0009007 Valve SN:

34752.004, 34752.020 P.O. 85N0022, quantity 8, cert no.

44156, was used on a 1" valve utili=ing 4 nu's each valve (2 total valves)

Trace Number:

H5 Part Number:

1571.014.0009018 valve SN 34752.039 34753.039 Sincerely L L Schroeppel V.P. Administration cc: Houston Light C Power South Texas Project P.O. Box 1700 Houston, TX 77001 Attn: Project *1anager NRC is being notified of this problem, including a copy of this letter.