o cp,.~
EDISON DRIVE MAIRE HARHEE ATOMIOPOWER00RIPAllUe Y
sww^3^,luef,,
- O March 18, 1987 MN-87-36 GDH-87-68 Region I l
United States Nuclear Regulatory Commission Office of Inspection and Enforcement 631 Park Avenue King of Prussia, Pennsylvania 19406 Attention: Dr. Thomas E. Hurley, Regional Administrator
References:
(a) License No. DPR-36 (Docket No. 50-309)
Subject:
Inspection Report No. 50-309/86-20 Gentlemen:
This letter is in response to Inspection Report No. 50-309/86-20.
The cover letter to your inspection report required Maine Yankee to inform you of any measures that were being taken to prevent an incident, similar to the inadvertent release that occurred on December 30, 1986, from occurring.
Our investigation of the incident determined the root cause of the occurrence to be the improper installation of a blank flange on a nitrogen feed line to the Volume Control Tank. After refuelings a spool piece is removed from the nitrogen feed line ar.d a blank flange is installed to prevent inadvertent feed of nitrogen to the tank during normal operation.
It was normal practice to have Operations personnel remove this spool piece and install the blank flange.
To prevent the occurrence of similar incidents, the Operations Department procedure calling for this evolution to be performed has been revised to require Operations to request the work be done by the Maintenance Department utilizing the management controls which Maine Yankee uses for this type of maintenance work, including post maintenance leak checking.
8704020069 870319 PDR ADOCK 05000309 O
PDR 8537L-DS i
T_tr e l
- O
a \\;
e
.o MAINE YANKEE ATOMIC POWER COMPANY Region I MN-87-36 United States Nuclear Regulatory Commission Page Two Attention: Dr. Thomas E. Murley, Regional Administrator
- I g
t.
A leaking check valve, upstream of the blank flange, was identified as a 2
contributing cause of this incident. The check valve has been scheduled for inspection and repair during the upcoming outage.
He believe these actions are sufficient to prevent recurrence of a similar 1
event. Please feel free to contact me if you should have any questions.
Very truly yours, MAINE YANKEE ATOMIC POWER COMPANY 1
}fAV G. D. Whittier, Manager Nuclear Engineering and Licensing i GDH/p1b cc: Mr. Ashok C. Thadani J Fl Mr. Pat Sears Mr. Cornelius F. Holden f, 4 3 s l ,) f 4 1 8537L-DS _- --}}