Amend 118 to License NPF-57,revising TS 4.8.2.1.b.3 to Increase Minimum Battery Electrolyte Temp Limit from 60 F to 72 F
ML20205D359
Person / Time
Site: Hope Creek 
Issue date: 03/25/1999
From: Adensam E
NRC (Affiliation Not Assigned)
To:
Shared Package
ML20205D363 List:
References
NUDOCS 9904020175
Download: ML20205D359 (4)


Text

a Reg m

p u

UNITED STATES j

NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 3000H001 I

PUBUC SERVICE ELECTRIC & GAS COMPANY l

ATLANTIC CITY ELECTRIC COMPANY 4

DOCKET NO. 50 354 l

HOPE CREEK GENERATING STATION AMENAMENT TO FACILIT( OPERATING LICENSE Amendment No.118 License No. NPF-57 1.

The Nuclear Regulatory Commission (the Commission) has found that:

A.

The application for amendment filed by the Public Service Electric & Gas Company (PSE&G) dated October 22,1998, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commission's rules and regulations set forth in 10 CFR Chapter I; B.

The facility will operate in conformity with the application, the provisions of the Act,

)

and the rules and regulations of the Commission; C.

There is reasonable assurance: (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations set forth in 10 CFR Chapter I; D.

The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and i

E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.

2.

Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment, and paragraph 2.C.(2) of Facility Operatirm License No. NPF-57 is hereby amended to read as follows:

9904020175 990325 PDR ADOCK 05000354 P

PDR

,I i

--,,.w.

t

?

! (2)

Technical Soecifications and Environmental Protection Plan I

The Technical Specifications contained in Appendix A, as revised through Amendment No. 118. and the Environmental Protection Plan contained in Appendix B, are hereby incorporated into the license. PSE&G shall operate tne l

facility in accordance with the Technical Specifications and the Environmental Protection Plan.

l 3.

The license amendment is effective as of its date of issuance, and shall be implemented within 60 days.

FOR THE NUCLEAR REGULATORY COMMISSION Elinor G. Adensam, Director Project Directorate 1-2 Division of Licensing Project Management Office of Nuclear Reactor Regulation

Attachment:

Changes to the Technical Specifications Date of issuance: March 25, 1999 f

E i

['

\\

1 ATTACHMENT TO LICENSE AMENDMENT NO.118 FACILITY OPERATING LICENSE NO. NPF-57 DOCKET NO. 50-354 i

Replace the following page of the Appendix "A" Technical Specifications with the attached page.

The revised page is identified by Amendment number and contains vertical lines indicating the area of change.

Remove 1.n!g.r1 r

3/4 8-13 3/4 8-13 i

V.

l?.

ELECTRICAL POWER SYSTEMS SURVEILLANCE REQUIREMENTS 4.8.2.1 Each'of the above required batteries and chargers shall be i

demonstrated OPERABLE:

I a.

At least once per 7 days by verifying that:

1.

The parameters in Table 4.8.2.1-1 meet the Category A limits, and 2.

Total battery terminal voltage for.each 125-volt battery is greater than or equal to 129 volts on float charge and for each l

250-volt battery the terminal voltage is greater than or equal to 258 volts on float charge, b.

At least once per 92 days and within 7 days after a battery discharge I

with battery terminal voltage below los volts for a 125-volt battery or 210 volts for a 250-volt battery, or battery overcharge with l.

battery terminal voltage above-140 volts for a 125-volt battery or 280 volts for a 250-volt battery, by verifying that:

)

1.

.The parameters in Table 4.8.2.1-1 meet the Category B limits, 2.

There is no visible corrosion at either terminals or connectors, or the connection resistance of these items is less than 150' x 10 ohms, excluding cable intercell connections, and 3.

The average electrolyte temperature of each sixth cell of connected cells is above 72*F.

l c.

At least once per 18 months by verifying that:

1.

The cells, cell plates and battery racks show no visual y

indication of physical damage or abnormal deterioration, l

2.

The cell-to-cell and terminal connections are clean, tight, free of corrosion and coated with anti-corrosion material, 3.

The resistcace of each cell-to-cell and terminal connection is less than or ey;tal to 150 x 10 ohms, excluding cable intercell connections, and I

L 4.

The battery charger will supply the current listed below at the voltage listed be.?ow for.at least 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />.

CURRENT l

CHARGER Minimum voltaae (AMPERES) j i

1AD413, 1AD414 129 200 1BD413, 1BD414 1CD413, 1CD414 1CD444, 1DD414 1DD444, 1DD413

'10D423, 10D433 258 50 HOPE CREEK 3/4 8-13 Amendment No. 07,118 l