Monthly Operating Rept for Jan 1987
ML20205C496
Person / Time
Site: Cook 
Issue date: 01/31/1987
From: Climer, Will Smith, St Amand J
INDIANA MICHIGAN POWER CO. (FORMERLY INDIANA & MICHIG
To:
NRC OFFICE OF RESOURCE MANAGEMENT (ORM)
References
NUDOCS 8703300197
Download: ML20205C496 (6)


Text

.

N.R.C. OPERATING DATA REPORT DOCKET NO.

50-316 DATE 2/3/87 COMPLETED BY CLIMER TELEPHONE 616-465-b901 OPERATING STATUS

1. Unit Name D. C. Cook Unit 2
2. Reporting Period JAN 87 l notes
3. Licensed Thermal Power (MWt) 3411 l l
4. Name Plate kating (Gross HWe) 1133 l l

b.

Design Electrical Rating (Net MWe) 1100 l l

6. Maximum Dependable Capacity (GROSS MWe) 1100 7.

Maximum Dependable Capacity (Net MWe) 1060 -----------------------

8.

If Changes Occur in Capacity Ratings (Items no. 3 through 7) Since Last Report Give Reasons __

9.

Power Level To Which Restricted. It Any (Net MWe)..,. _.

10. Reasons For Restrictions. It Any:...

This Mo.

Tr. to Date Gumm.

11. Hours in Reporting Period 744.0 744.0 79632.0
12. No. of Hrs. Reactor Was Critical 744.0 744.0 65333.3
13. Reactor Reserve Shutdown Hours 0.0 0.0 0.0
14. Hours Generator on Line 744.0 744.0 63987.3 lb. Unit Reserve Shutdown Hours U.0 0.0 0.0
16. Gross Therm. Energy Gen. (MWH) 2039325 2039325 167730529
17. Gross Elect. Energy Gen. (MWH) 668210 668210 54886250
18. Net Elect. Energy Gen. (MWH) 640790 640790 5287b626
19. Unit Service Factor 100.0 100.0 70.0
20. Unit Availability Factor 100.0 100.0 70.0
21. Unit Capacity Factor (MDC Net) 81.3 81.3 64.6
22. Unit Capacity Factor (DER Net) 78.3 78.3 63.1
23. Unit Forced Outage kate 0.0 0.0 14.5
24. Shutdowns Scheduled over Next Six Months (Type Date,and Duration):.

A Technical Specification Surveil _ lance _and minor _ Maintenance _ outage is scheduled-to start ttte_ secondjlalf of April _._1981._.for_an_estima.ted 3 week _ duration

26. If Shut Down At End of Report Period, Estimated Date of Startup:
26. Units in Test Status (Prior to Commercial Operation):

Forcast Achieved INITIAL CRITICALITY INITIAL ELECTRICITY COMMERCIAL OPERATION

\\k(

B703300197 B70131 PDR ADOCK 05000316 R

PDR

..m l

l AVERAGE DAILY POWER LEVEL (HWe-Net)

DOCKET NO.60-316 UNIT TWO DATE 2/3/87 COMPLETED BY Cl.IMER TELEPHONE 616-466-b901 MONTH JAN 87 AVERAGE DAILY AVERAGE DAILY DAY POWER LEVEL DAY POWER LEVEL 1

869 17 859 2

860 18 862 3

869 19 862 4

860 20 663 6

861 21 863 6

861 22 666 7

860 23 663 8

860 24 660 9

863 2b 863 10 861 26 861 11 863 27 869 12 860 28 861 13 861 29 863 14 863 30 862 lb 863 31 860 16 861 i

.. - _, - - -,,. -.. - - _. ~ -. - - -, -,.. -,. _. - -

e IMMIE1 PMt.

50-3.16 IINIT SIMlHWlWNS AND POWEN RUMN1H)NS UNII NAME D.C. Conk linit 2 J. L. St. Amand nATE 2-11-87 MDMPI ETED by alroal aspMHI January, 1987 TEl.tFlIONE 616/465-5901 4

L

  • t

=

g ranse A fewectelve

_$ g

'h

} @h'j I icensee E-e, gn, Atu.we en i

N.e.

Ilaec k

gg g

I!vene gy gt'

, ac Psevens Heimrence jdig Nep.wt *

.n o d

oc-F 6

1 There were no unit shutdowns or power y

NONE reductions during the month. The unit 4

operated at a nominal 80% power limit j

administratively imposed to minimize j

j steam generator tube degradation, j

l 4

1 i

I 4

I 2

3 4

Meehinl:

Enhshie G-Instsenet.wis l': l'inseil Neasaws:

i S: Silicituiril A l'.guapmesis I aihue (f.mplain) 1 Maemal I.w l*scrasassim al 1848a la Ma6mtenance os Tess 2 Mani.at Saane.

Enesy Sheces l'on I k cusee

.1 Auenmatic Sirani.

Fvene Negnies il l'RIl'ile INitMI G.

j C Relucthig I

in Mcgulainey Resent tiam

-l t hlice IFnplamil nitill l

1 Opesasos Isaise6sig & Iitense I sansheat6am 5

11Ailminhosative d

I sluline I S.niec S me e G Opc aseeneal I.sse.e llimpi.aisel 4

l'8/lFi IlINiec Ilisplaisil J

i

O*

i' DOCKET NO:

50-316 UNIT NAME:

D. C. Cook Unit 2 COMPLETED BY:

J.

L.

St. Amand TELEPHONE:

(616) 465-5901 DATE:

February 3, 1987 PAGE:

1 of 1 MONTHLY OPERATING ACTIVITIES - JANUARY 1987 HIGHLIGHTS The unit operated the entire month at the nominal 80% power limit, (administrative 1y imposed to minimize steam generator tube degradation).

Gross electrical generation for the month of January was 668,210 MWH.

SUMMARY

There were no significant operating events during the month.

~

.m

..i-2.*

.e-DOCKET NO.

50-316 UNIT NAME.

D. C. Cook -- Unit No. : 2 -

DATE 2-11-86 COMPLETED BYL J.

L.

St. Amand TELEPHONE (616) 465-5901 PAGE

- 1 of 1 MAJOR SAFETY-RELATED MAINTENANCE JANUARY, 1987 I&C-1 FPI-240, #4 Steam. Generator Feedwater line pressure indicator was found reading 100'psig low.

A~ defective transducer and electronic circuit board.was found in pressure transmitter'FPI-240.

The board was-replaced, the. transmitter calibrated, and FPI-240 was returned to service.

Proper pressure indication was verified.

I&C-2 A defective limit-switch was found during valve testing-on control valve "B", which would not allow stop valve "B"

to close.

The limit switch was replaced and proper-valve operation verified.

M-1 A crack was found on a 14" Component Cooling Water.Line to the West Residual Heat Removal Heat Exchanger.

The CCW was isolated'from the Heat Exchanger and the crack repaired.

All components were tested and returned to service.

M-2 The gear drive speed increaser for the West Centrifugal l

Charging Pump was replaced due to excessive wear.

I After testing showed the new unit to be operating satisfactorily, the pump was returned to service.

M-3 The East Essential Service Water Pump was replaced after high vibrations revealed excessive wear.

The j

pump tested satisfactorily and was returned to service.

i I

)

)

?C m.e

,MNDIANA & MICHIGAN ELECTRH; COMPAllY DONALD C. COOK NUCLEAR PLANT P.O. Box 458, Bridgman, Michigan 49106 (616) 465-5901 February 11, 1987 1

t u

Director, Office of Management Information and Program Control U.

S. Nuclear Regulatory Commiss.$on Washington, D. C.

20555 Gentlemen:

Pursuant to the requirement of Donald C. Cook Nuclear plant Unit 2 Technical Specification 6.9.1.10, the attached Monti<ly'Operat-ing Report for the Month of January, 19S7 is submitted.

s Sincerely, i

blY/

u C$}

W. G.

Smith, Jr Plant Manager