3 01/06/84 11:35 E-WIN W D L. s.-.sA.
JAN 065 19M NOTE FOR: Don Sreniawski, RIII SU8 JECT:
EDLOW WWtDIOUSE. EAST ST. LOUIS. IL DOCKET 70-2955 I have read the 3-11-82 application and:the.6-21-82 supplement for Licenses SIM-1903 and suggest the following. items. for enforcemer.t action:
i 6-21-82 Supolament Para 3 Chocks on both sides of cylinders.will be nailed to ties:
observed. cylinders wtthout chocks.
Para 7 No flammahle liquidss observed auto in warehouse.
Para 8 No com6ustible material and daily inspections observed office stmeture (ex-office room)., building.not occup;ied daily, woodse files burning burned auto Para 11 2nd person assures clinders properly chockeds observed.qylinders without chocks.
w Para 13 Autcentic sprinkler system would.be activated and offsite ala'ris company will notify fire department. Fire department can pain inmundiate access. Observation of fire damage indicates sprinkler system was not activrted, offsite alarm company did not pene fire department and fire department had to force entry to site.
3-11-82 Application y,
Page 2 Storage in East St. Louis. Fim was in facility located in Washington Park.
U This statement contribut.ed to. inadequate review of amergency plan to assure coordination between ESL and WP Ffm Departments.
ih L,h
~
a DISTRIBUiION:
\\
f J/
Docket Ffle 70-2955 R
II' '
NMSS R/F LTharpe' JA7 FCUP R/F p
GBidinger rjf.
%TCrow
// y N
\\c M
RGPage
[
// [8 s
/
/
f gg
.u w
=>
- "" "* L' ".:::r" "::
L-
- . ' ~.:......
f 01/06/84 11:35 RC-u1LLSTE NO.009 003 J2N o 51BM Page 2 Burns was security agency. Security agerky identiffed as Police A Page 5 Page 11 occupied dayfly.See Industry personnel vill inspect. daily;. site was no Page 6 Valve protectors required; observed. bare valves on cylinders.
origina.. *~ ~
s mygs u.
George M. Bfdtnger l
e.
- c. >.. rene.
- 6 E rrn
"'> R53djnse/.p
.........e........
rs>.1l3.l84.....
uo.,2.....
co o,,
A 01/06/84 -
11:36 RC-(JILLSTE NO.009 004 1.
Replace the main sprinkler control. valves with post indicator valves so located that the OPEN/$ HUT ~ target can be seen.
I 2.
Lock the valve in the open position..
s 3.
Install central station supervision on the main sprinkler control.
valves.
4 Assure that the central station supervision:on the sprinkler
~
^
systems (low air, water flow and main control valve position) are supervised for line trouble and circuit integrity.
- 5.. Provide 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> watchman service whenever any of the aut tic sprinkler systems are out-of-service.
David P. Notley Electrical Engineering Branch Divisibn of Engineering Technology Officei of Nuclear Regulatory Research no en i