Text
Peach Bottom Atomic Pmwer Ctation' s..g_
RECO! NUCLEAR nm ~v c-1848 Lay Road -
Na PAj7314 oo32.
- A Unit of PECO Energy!
g December 4,1997 U.S. Nuclear Regulatory Commission Document Control Desk
- Washington, D.C. 20555 Docket Nos. 50-277 and 50-278-
' Gentlemen:
Enclosed is the monthly operating report for Peach Bottom Units 2 and 3 for the month of November
~ 1997 forwarded pursuant to Technical Specification 5.6.4 under the guidance of Regulatory Guide 10.1,
' Revision 4.
' Sincerely,-
r r
t Mark E. Wamer Director, Site Ecgineering Peach Bottom Atomic Power Station
../
- MEW /M JM:dmkg') n %
pdW Enclosures
. cc:
N.J. Sproul, Public Service Electric & Gas E. Salowitz, Public Service Electric & Gas W.P, Domsife, Commonwealth of Pennsylvania
- R.I. McLean, State of Maryland T.T. Martin, Administrator, Region I, USNRC W.L. Schmidt, USNRC, Senior Resident inspector T. M. Messick, Atlantic Electric -
A.F. Kirby,'ll!, Delmarva Power & Light INPO Records C6nter '
T. N. Mitchell, PECO Nuclear, Vice President, Peach Bottom Atomic Power Station
/
f &) I
/
39
- ccn 9714071'-
l i,
.., a n [' '.2 0 9712220062 971130~
PDR.ADOCK 05000277'
' R :.
PDR.
Pc:ch Bottom Atomic Power St tion
)
Unit 2 November 1 through November 30,1997 1.
Narrative Sy_q1 mary of Operatina Experiences Unit 2 began the month of November at a nominal 100 % of rated thermal power (RTP).
On November 5,1997 at 2000 hours0.0231 days <br />0.556 hours <br />0.00331 weeks <br />7.61e-4 months <br />, power was reduced to 04% of RTP for SB Feedwater Heater steam leak repair. Power was restored to 100% on November 7,1997 at 000 hours0 days <br />0 hours <br />0 weeks <br />0 months <br />.
On November 9,1997 at 15:25 U/2 automatic scram occurred due to loss of DC voltage during swap nf battery chargers. Power was restored to 100% on November 11, at 500 hours0.00579 days <br />0.139 hours <br />8.267196e-4 weeks <br />1.9025e-4 months <br />.
Unit 2 ended this month operating at 100% RTP.
i
l Attichm:nt to Monthly Operating Report for November 1997
_ UNIT 2 REFUELING INFORMATION 1.
Name of facility.
Peach Bottom Unit 2 2.
Schcduled date for next refueling shutdown:
Reload 12 is scheduled for October 2,1998.
3.
Scheduled date for restart following refueling:
Restart following refueling forecast for October 30,1998.
4.
Will refueling or resumption of operation therefore require a technical specification change or other license amendment?
N/A If answer is yes, what, in general, will these be?
N/A 5.
Scheduled date(s) for submitting proposed licensing act:an and supporting information:
6.
Important licensing consi-le ations associated w3 refueling, e.g., new or Efferent fuel design or supplier, unreviewed design or performance analysis methods, significant changes in fuel design, new operating procedures:
w 7.
The number of f.iel assemblies (a) in the core and (b) in the spent fuel storage pool:
- a) Core - 764 Fuel Assemblies (b) Fuel Pool-2720 Fuel Assemblies,52 Fuel Rods
_ - ii._
Dock:t No. 50-277 Attrchm:nt to Monthly Operating Report for November 1997 Page 2 UNIT 2 REFUEt ING INFORMATION (Continued) 8.
The present licensed spent fuel pool storage capacity and it a size of any increase in licensed storage capacity that has been requested or is plan.1ed, in number of fuel assemblies:
The spent fuel pool t,torage capacity has been relicensed for 3819 fuel assemblies.
9.
The projected date of the last refueling that can be discharged to the spent fuel pool assuming the present capacity:
September 2002 without full core offload capability.
September 1998 with full core of00ad capability.
l
AVERAGE DAILY POWER LEVEL
' DOCKET NO. 50-277 UNIT PEACH BOTTOM UNIT 2 DATE DECEMBER 3,1997 '
COMPANY PECO EN"EGY COMPAf#
f E. A. DUNNING l.
BUSINESS SERVICES
$1TE S'JPPORT DMSION PEACH BOTTOM ATOMIC FCWER STATION ~
TELEPHONE (717)456-3412 MONTH NOVEMBER,1997 DAY AVERAGE DAILY POWER LEVEL DAY AVERAGE DAILY POWER LEVEL l
(MWE-NET)
(MWE-NET) 1 1119 17 1123 2
5113 18 1122 l
3 1117 19 1127 4
1123 20 1114 5
1120 21 1130 6
1072 22 1126 7
1125 23 1122 8
1120 24 1126 9
720 25 1118 to 0
26 1122 11 322 27 1126 12 962 28 1121 13 1094 29 1116 14 1127 30 1120 15 1122 16 1122
l OPERATING DATA REPORT DOCKET NO.53-277 DATE DECEMBER 3,199'
~
COMPLETED BY PECO ENERGY COMPANY E. A. DUNNING BUSINESS SERVICES SITE SUPPORT DMSION PEACH BOTTOM ATOM)C POWER STATION (717) 7 6-3412 TELEPHONE 2
OPERATING STATUS.
- 1. UNIT NAME: _ _ _. _ _ _ _. _ _... _. _ -. _.. _ _... _ _ _ ~ _. P. EA._CH BO. TT..OM.U. NI.T. 2..
- 2. REPORTING PERIOD:, _ _. _. _ _
_ _ NOVEMBER,1997,
- 3. LICENSED THERMAL POWER (MWT):
_ _ _ _ __3458_
4 NAMEPLATE RATING (GROSS MWE): _
. _ _ _ 1221
- 5. DESIGN ELECTRICAL RATlHG (NET MWE): __ ___ _._ _ _ _ __.__ __..____ _1119
- 6. MAXIMUM DEPENDABLE CAPAC!TY (GROSS MWE):
_ _.,_ __. _ _ _._ _ 1159
- 7. MAXIMUM DEPENDABLE CAPACITY (NET IME):
1093
- 8. IF CHANGES OCCUR IN C,.
.ATINGS (ITEMS 3 THROUGH 7 ) SINCE LAST REPORT, GIVE REASONS:
- 9. POWER LEVEL TO VvHICH RESTRICTED, IF ANY (NET MWE):
M REASONS FOR RESTRICTIONS,IF ANY:
THIS MONTH YR-TO-DATE CUMULATIVE
- 11. HOURS IN REPORTING PERIOD 720 8,016 205,200
- 12. NUMBER OF HOURS REACTOR WAS CRITICAL 691.6 7,987.6 138,903.1
- 13. REACTOR RESERVE SHUTDOWN HOURS 0.0 0.0 0.0
- 14. HOURS GENERATOR ON-LINE -
683 0 7,979 0 134,756 2 l
- 15. UNIT RESERVE SHUTDOWN HOURS 0.0 0.0 0.0
- 16. GROSS THERMAL ENERGY GENERATED (MWH) 3,049,987 28,007,942 409,983.522
- 17. GROSS ELECTRICAL ENERGY GENERATED (MWH) 766,200 9.044,500 134,514,090
- 18. NET ELECTRICAL ENERGY GENEhATED (MWH) 745,978 8,810,958 129,277,410 l
PAGE 1 OF 2
~
+
s m
. n-s.. -v-m
..-s m
- ~
w
. s.
e-4 4
+..
su 1
OPERATING DATA REPORT (CONTINLED)
',j 1
t
. !50 - 277 :
sJ i.p DOCKET NO.
i DATEi DECEMBER 3.1997 TC
.s.
fa L
THIS MONTH L YR-TO-DATE '
' CUMULATNE i 19. UNIT SERVICE FACTOR..
- 94.9 %,.
99.5 %
' 95.7 % ;
~
- 20. UNIT AVAILABILITY FACTOR
- 94.9 % '
99.5 % '
05.7 % ' ~
H 21.- (THIT CAPACITY FACTOR (USING MDC NET) '
94.8 %
100.6 %-
. 59.5 % '
~
L 22. UNIT CAPACITY FACTOR (USING DER NET) '
. 92.6 %
98_2 % -
J. 58.5 %
t 11.1 %'-
' 23. UNIT FORCED OUTAGE RATE -
5.1 %
.5 % -
r
- 24. SHUTDOWNS SCHEDULED OVER THE NEXT 6 MONTHS' (TYPE, DATE AND DURATION OF EACH):
. i 1
- 25. IF SHUTDOWN AT THE END OF REPORT PERIOD, ESTIMATED DATE OF STARTUP
- ;
- 26. UNITS IN TEST STATUS (PRIOR TO COMMERCIAL OPERATIONS):
FORECAST' ACHtEVED
' INITIAL CRITICAUTY 09/16/73 INITIAL ELECTRICITY
. 02/18/74
, COMMERCIAL OPERATION -
07/05/74 -
r 1
i-
,, l i
PAGE 20F 2h 1
w
~m
.v~-
v,v 4,
s..4,-
g g
1
,u...,
4
-n.
-.n.,.4
...w,,.
++w--
,m
,. wN-e.
s,se,-
..w
, m.s
l.
UNIT SHUTDOWNS AND POWER REDUCTIONS
)l
. DOCKET NO. 50-277
' UfET MAME PEACH BOTTOM UNIT 2 DATE DECEMBER 3,1997 COMPLETED BY PECO ENERGY COMPANY E. A. DUNNING BUSINESS SERVICES SITE SUPPORT DMSION PEACH BOTTOM ATOMC POWER STATION REPORT MONTH NOVEMBER,1997 TELEFHONE (717)456-3412
{
METHOD OF L!CENSEE SYSTEM COMPONENT CAUSE AND CORRECTIVE TYPE-DURATION REASON. SHUTTING DOWN EVENT CODE CODE ACTION TO NO.
DATE (1).
(HOURS)
(2)
REACTOR (3)
REPORT #
(4)
(5)
FREVENT RECURRENCE Q
971109 F
37.0 H
3 BATTRY less of DC voltage during swap of battery chargers f
TOTAL HOURS 37.0 l
I l
l l
l (1)
(2)
(3)
(4) l F-FORCED REASON METHOD EXH! BIT G-INSTRUCTIONS l-S-SCHEDULED A - EQUIPMENT FAILURE (EXPLAIN) 1 - MANUAL FOR PREPARATION OF DATA B - MAINTENANCE OR TEST 2-MANUAL SCRAM ENTRY SHEETS FOR UCET.SEE C - REFUEUNG 3-AUTOMATIC SCRAM EVENT REPORT (LER)
D - REGULATORY l" STR!CTION 4-OTHER (EXPLAIN)
FILE (NUREGC81)
E - OPERATOR TRAINING + LICENSE EXAMINATION l
(5) i-F ADMINiSTRATMI EXHIBIT I-SAME SOURCE l
G - OPERATIONAL ERROR (EXPLAIN)
H - OTHER (EXPLAIN)
l P: ch Bottom Atomic Power St tion Unit 3 November i through November 30,1997 1.
Narrative Summary of Operatina Experiences Unit 3 began the month of November at 0% of rated thermal power (RTP) due to refueling 4
outage.
On November 8,1997 at 1200 hours0.0139 days <br />0.333 hours <br />0.00198 weeks <br />4.566e-4 months <br /> the Unit reached 93% of RTP. The Unit was held at 03% RTP due to jet pump riser weld cracking indications. The Unit was raised to 100% on November 12 at 0400 hours0.00463 days <br />0.111 hours <br />6.613757e-4 weeks <br />1.522e-4 months <br />.
On November 14,1997 at 2100 hours0.0243 days <br />0.583 hours <br />0.00347 weeks <br />7.9905e-4 months <br /> the Unit was reduced back to 93% of RTP due to jet pump riser weld cracking indications.
On November 28,1997 at 1500 hours0.0174 days <br />0.417 hours <br />0.00248 weeks <br />5.7075e-4 months <br /> the Unit was manually shutdown to repair the "E" Steam Relief Valve. The Unit remained shutdown throughout the remainder of the month.
l
Dock;t No. 50-270 I
Attichment to Monthly Operating Report for November 1997 UNIT 3 REFUELING INFORMATION 1.
Name of facility:
Peach Bottom Unit 3 2,
Scheduled date for next refueling shutdown:
- s Reload 11 scheduled for October 3,1997 is in progress 3.
Scheduled date for restart following refueling Restart following refueling scheduled for November 1,1997 4.
Will refueling or resumption of operation thereafter require a technical specification change or other license amendment?
N/A 4
If answer is yes, what, in general, will these be?
5.
All items have been submitted.
6.
Important licensing considerations ass (clated with refueling, e.g., new or different fuel design or supplier, unreviewed design or performa nce analysis methods, significant changes in fuel design, new operating procedures:
(a) The 292 new 3R11 bundles are GE 13 design new to Unit 3 7.
The number of fuel assemblies (a) in the core and (b)in the spent fuel storage pool:
(a) Core - 764 Fuel Assemblies (b) Fuel Pool-2777 Fuel Assemblies,16 Fuel Rods (292 new 3R11 bundles)
( one of the 2777 is a skeleton which contains less than a full complement of fuel rods) 8.
The present licensed spent fuel pool storage capacity and the size of any increase in licensed storage capacity that has been requested or is planned,in number of fuel assemblies-The spent fuel pool storage capacity has been relicensed for 3819 fuel assemblies.
l 1
- Docket No ' 50-278
' Attachment 13 :
. Monthly Operating --
-- +
Repon for November 1997 7
Page 2 4
4 UNIT.3 REFUELING INFORMATlON (Continued)-
= 9.
- The projected date of the last refueling that can be discharged to the spent fuel pool assuming.-
- the present capacity:
G ptember 2003 withcut full core offload capability, a
September 1999 with full core offload capebility.
1 t
7
. t t
't h'
Y W
i w
-e
+
w
AVER".GE DA!LY POWER LEVEL DOCKETNO. 50-278 UNIT PEACH BOC UNIT 3 DATE Dr EMegg.
jg7 -
COMPANY PECO ENEnuY COMPANY E. A. DUNfilNG BUSINES$ SERVICES SITE SUPPORT D' VISION PEACH BOTTOM ATOMC POWER STATION TELEPHONE (717)4560412 MONTH NOVEMBER,1997 DAY AVERAGE DA!LY POWER LEVEL DAY AVEP. AGE DAILY POWER LEVEL (MWE-NET)
(MWE-NET) 1 0
17 1039 2
37 18 1039 1' 5 19 1039 J
3 4
491 20 1027 l
5 938 21 1048 6
941 22 1038 7
1044 23 1037 8
1040 24 1041 9
1042 25 1033 i
25 1038 10 1025 11 1038 27 1042 12 1105 28 741 13 1112 29 0
14 1104 N
O 15 1031 16 1044
OPERATING DATA REPORT DOCKET NO 50- 7/8 CATE DECEMBER 3,1997 COMPLETED BY PECO ENERGY COM'ANY E. A. DUNNING BUS.* NESS SERVICES SITE SUP' ORT DIVISION PEACH BOTTOM ATOMIC POWER STATION TELEPHONE (717)456-3412 l
l OPERATING STATUS l
- 1. UNIT NAME: _ _ _ _ _. __,
_, _._ _, _ PEACH BOTTOM U. NIT 3 NOTES:
- 2. REPORTING PERIOD: _. _ _ _
NOVEMBER,1997_
- 3. LICENSED THERMAL POWER (FENT): __._
_3458
- 4. NAMEPLATE RATING (GROSS MWE): ____
- 1221,
- 5. DESIGN ELECTRICAL RATING (NET MWE):
_111,9
' 6. MAX' MUM DEPENDABLE CAPACITY (GROSS MWE):
_ _ _ _ _._1159
- 7. MAXIMUM DEPENDABLE CAPACITY (NET MWE):
,_ _1093
- 8. IF CHANGES OCCUR IN CAPACITY RATINGS (ITEMS 3 THROUGH 7 ) SINCE LAST REPORT, GIVE REASONS:
- 9. POWER LEVEL TO WHICH RESTRICTED,IF ANY (NET MWE):
10 REASONS FOR RESTRICTIONS,IF ANY:
THIS MONTH YR-TO-DATE CUMULATIVE
- 11. HOURS IN REPORTING PERIOD 720 8,016 201.096
- 12. NUMBER OF HOURS REACTOR WAS CRITICAL 667.1 7,227.6 137,209.9
- 13. REACTOR RESERVE SHUTDOWN HOURS 00 0.0 0.0
- 14. HOURS GENERATOR OrJ-LINE 631.0 7,179 0 133,614 2
- 15. UNIT RESERVE SHUTDOWN HOURS 0.0 0.0 0.0
- 16. GROSS THERM *'. ENERGY GENERATED (MWH) 1,903.121 21,925,404 400,927,382
- 17. GROSS ELECTRICAL ENERGY GENERAT ED (MWH) 624,700 7,043,100 131,361,532
- 18. NET ELECTRICAL ENERGY GENERATED (MWH) 607,756 6,825,513 126.264,053 PAGE 1 OF 2
m.
lv.
- u
.{
c
-r-OPERATING DATA REPORT (CONTir1UED)....
r
.g --
' DOCKET NO..
50 -278 DATE
" DECEMBER 3.1997 ;
._m3
THIS MONTH
~ YR-TCMMTE.
CUMULATNE L-
' r
.19.. UNIT SERVICE FACTOR.-
87.6 %
89.6 %
es.4 %;
i.20. UNIT AVAlt.ABluTY FACTOR '
87.6 % -
89.6 %
. 66.4 %
L 21. UNIT CAPACITY FACTOR (USING MDC NET) -
77.2 %
- 77.9 %
60.2 %
! 22. ' UNIT CAPACITY FACTOR (USING DER NET) '
75 4 %
~ 76.1 % '
56.6 %
- 23. UNIT FORCED OUTAGE RATE -
.0 %
1.0 %
10.0 %
' 24. SHUTDOWNS SCHEDULED OVER THE NEXT 6 MONTHS (TYPE, DATE AND DURATION OF EACH):
L 25. IF SHUTDOWN AT THE END OF REPORT PERIOD, ESTIMATED DATE OF STARTUP;
^
f 26. UNITS IN TEST STATUS (PRIOR TO COMMERCIAL OPEPATIONS):
-FORECAST ACHIEVED L INITIAL CRITICALITY 0807/74
' !NmAI. ELECTRICITY 0001/74
' COMMERCIAL OPERATION
-12/23/74 '
l 1
' PAGE'2"OF 2.
UNIT SHUTDOWNS AND POWER REDUCTIONS DOCKET NO. 50-278 UNTT NAME PEACH BOTTOM UNIT 3 DATE DECEMBER 1't,1997 COMPLETED BY PECO ENERGY COMPANY.
E. A. DUNNING BUSINESS SERVICES
^
SITE SUPPORT DIVISION PEACH BOTTOM ATOMIC POWER STATION TELEPHONE (717)4563412 REPORT MONTH NOVEMBER,1997 METHOD OF LICENSEE SYSTEM COMPONEht CAUSE AND CORRECTIVE f
TYPE DURATION REASON SHUTTING DOWN EVENT CODE CODE ACTION TO l
NO.
DATE (1)
(HOURS)
(2)
REACTOR (3)
REPORT 8 (4)
(5)
PREVENT RECURRENCE.
'10 971101 S
34 3 C
2 ZZ 777777 Refuehng Outage 11 971108 S
0.0 H
4 RA PUMPXX Jet pump riser weld cracidng (duration shown enfy for shutdown) 12 971128 S
55 0 A
2 CC VALVEX T SRVieelong I
(durabon to shown only for shutdown)
TOTAL HOURS 89 0 (3)
(4)
(1)
(2)
METHOD EXHIBIT G-INSTRUCTIONS F-FORCED REASON FOR PREPARATION OF DATA 1-MANUAL S - SCHEDULED A -EQUIPMENT FAILURE (EXPLAIN)
ENTRY SHEETS FOR UCENSEE 2-MANUAL SCRAM B-MAINTENANCE OR TEST 3-AUTOMATIC SCRAM EVENT REPORT (LER)
C - REFUELING 4-OTHER (EXPLAIN)
FILE (NUREG4161)
D - REGULATORY RESTRICTION E - OPERATOR TRAIN!NG + LICENSE EXAMINATION (5)
F-ADMINISTRATIVE EXHIBIT I-SAME SOURCE G-OPE ~4TIONAL ERROR (EXPLAIN)
H - OTHE". (EXPtAIN)