Text
Y Northem States Power Company Prairie f aland Nuclear Generating Plant 1717 Wakonado Dr. East Weh Maywoota s5089 December 15,1997 Prairio Island Technical Specifications Section 6.7.A.3 US Nuclear Regulatory Commission Attn: Document Control Desk Washington, DC 20555 PRAIRIE ISLAND NUCLEAR GENERATING PLANT Docket Nos. 50-282 Liceitse Nos. DPR-42 50-306 DPR 60 Narrative Summary of Operating Experience November 1997 Attached is the Narrative Summary of Operating Experience for November 1997 for the Priarie Island Nuclear Generating Plant.
A cf M
i f l' el P Sorensen Plant Manager Prairie Island Nuclear Generating Plant c:
Regional Administrator Ill, NRC f((
NRR Project Manager, NRC NRC Resident inspector State of Minnesota. Kris Sanda Attachment il.l!.,I!I: : ill.!!.ll l 9712100407 971130 PDR ADOCK 05000202 R
l PRINTED 12/1597 l
.[ NRC MONTHLY REPORT Page 1 l
3 DOCKET NO. S282 i
UNIT PRAIRIE ISLAND NO.1 l
DATE 12/1597 COMPLETED BY DALE DUGSTAD
. TELEPHONE 612 38811214378 -
f NMutAINESUMIMAY OF OPERAllRG_EXE15lENCE MONTH: NOVEMBER 1M7 Unit 1 was in a refueling / maintenance outage for the entire month of November.
t
(
4 f
I I
N T
4 4
1 CURRENT CONTINUOUS OPERATING RUN OF 0 DAYS r
Y i
.- w,
...g..-
,.,m, m.
m..
..,.._._m._,
NRC MONTHLY REPORT PRINTED 13/1597 Pcpe 2 DOCKET NO. 50-282 UNIT PRAIRIE ISLAND NO.1
[
DATE 12/1597 COMPLETED BY DALE DOGSTAS TELEPHONE 612 38811214376 j
AYERAGE_ DAILY POWER LEVEL f
UNIT _1 t
MONIHWQYEMBER_199I f
DAll AYERAGEDAILY POWER 1EYEL 11/01/97 1
11/02/97 1
f 11/03/97 1
f 11/04/97 1
11/0$/97 1
11/06/97 0
11/07/97 0
11/08/97 1
11/09/97 2
11/10/97 1
11/11/97 2
11/12/97 2
11/13/97 2
11/14/97 2
11/15/97 2
11/16/97 2
11/17/97 2
11/18/97 2
11/19/97 2
11/20/97 1
11/21/97 1
11/22/97 1
11/23/97 1
11/24/97 1
11/25/97 1
11/26/97 1
11/27/97 0
11/28/97 0
11/29/97 0
11/30/97 0
I AVERAGF LOADS ABOVE 513 MWE NET ARE DUE TO COOLER CONDENSER CIRCULATING WATER
NRC MONTHLY REPORT PRINTE012/1997 Page 3 DOCKET NO. 50 282 i
UNIT PRAIRIE ISLAND NO.1 i
DATE 12/1997 1
COMPLETED BY DALE
)
DUGSTAD t
OREBAIMO DATAREEDR1 i
OPERAllNG.8IATUS
- 1. UNIT NAME:
PRAIRIE ISLAND NO.1
- 2. REPORTING PERIOD:
NOVEMBER 1997
- 3. LICENSED THERMAL POWER (MWT): 1650-
- 4. NAMEPLATE RATING (GROSS MWE): 593
- 5. DESIGN ELECTRICAL RATING (NET MWE): 530 0 MAXIMUM DEPENDABLE CAPACITY (GROSS MWE):
545
- 7. MAY.lMUM DEPENDABLE CAPACITY (NET MWE):
513
- 8. IF CHANGES OCCUR IN CAPACITY RATINGS (ITEMS 3 7) SINCE LAST REPORT, GIVE REASON:
NONE
- 9. POWER LEVEL TO WHICH RESTRICTED, IF ANY (NET MWE): NONE
- 10. REASONS FOR RESTRICTIONS. IF ANY:
NONE IHitJdQNIH YS TO DATE CUMULATWE
- 11. HOURS IN REPORTING PERIOD 720 8016 210024 12 NUMBER OF HOURS REACTOR CRITICAL 0.0 6581.3 180322.0
- 13. REACTOR RESERVE SHUTDOWN HOUP.S 0.0 0.00 5571.1
- 14. HOURS GENERATOR ON LINE 0.0 6509.6 178591.3
- 15. UNIT RESERVL SHUTDOWN HOURS 0.0 0.00 0.00
- 16. GROSS THERMAL ENERGY GENERATED (MWH) 0 10648708 283702221
- 17. GROSS ELECTRICAL ENERGY GENERATED (MWH) 0 3538340 93018950 18, NET ELECTRICAL ENERGY GENERATED (MWH) 763 3336523 88048803
- 19. UNIT SERVICE FACTOR 0
82 85
- 20. UNIT AVAILABILITY FACTOR 0
82 85
- 21. UNIT CAPACITY FACTOR ( MDC NET) 0.2 81.1 83.1
- 22. UNIT CAPACITY FACTOR ( DER NET) 0.2 78.5 79.1
- 23. UNIT FORCED OUTAGE RATE O
5.1 4.6
- 24. FORCED OUTAGE HOURS 0.0 353.6 8540.7
- 25. SHUTDOWNS SCHEDULED OVER NEXT SIX MONTHS (TYPE, DATE, AND DURATION OF EACH):
in refueling outage at present time.
- 26. lF CURRENTLY SHUTDOWN. ESTIMATED STARTUP DATE:
- Expected date generator on-line is the 16th of Decemt:ar.
ll 1l --..:.
- [
NRC MONTHLY R2 PORT PRINTED 12/1997 Pape4 l
DOCKET NO. 50-282 UNIT PRAlRIE ISLAND NO,1 DATE 12/15/97 -
COMPLETED BY DALE DUGSTAD i
TELEPHONE 612 388-11214376 UNIT SHUTDOWNS AND POWER REDUCTIONS MONTH: NQYAMBER 1997 DATE UNIT TYPE HOURS REASON METHOD LER NUM8ER SYSTEM COMPONENT 11/30/97 i
S 720 C
4 N/A N/A N/A NOTES:
Refueling Outage, cycle 19.
IYEE REASON MEIHQQ RYRIEM. CODE F FORCED A-EQUIPMENT FAILURE 1 MANUAL DRAFT lEEE STD S SCHEDULED 0 MAINTENANCE OR TEST 2-MANUAL TRIP C41EFUELING 3 AUTOTRIP l-D-REGULATORY RESTRICTION 4 CONTINUED E-OPERATOR TRAINING AND 5-REDUCED LOAD CQMP_QNENLCQDE LICENSE EXAMINATION 0-0THER IEEE STD 803A 1983 F ADMINISTRATIVE G-OPERATIONAL ERROR H-OTHER l
NRC MONTHLY REPORT PRINVED 13/15/97 Page9
+
.I DOCKET NO. 50 306
)
UNIT PRA!RIE ISLAND NO. 2 DATE 12/1597 COMPLETED BY DALE DUGSTAD TELEPHONE 612 386-1121-4376 j
NARRATNE
SUMMARY
OF OPERATING EXPERIENCE i
NORT&MOYEMBE!L19tZ Unit 2 was base loaded for the month of November. There were no shutdowns or power reductions.
i O
f CURRENT CONTINUOUS OPERATING RtJN OF 63 DAYS
NRC MONTHLY REPORT PRINTED 12/1$17.
Pap 6 DOCKET NO. 50 306 UNIT PRAIRIE ISLAND NO. 2 DATE 12/1$97 COMPLETED BY DALE DUGSTAD i
TELEPHONE 612 38811214376 AVEMGLDAILY PQWER LEVEL UNIL2 MONDtMQYEMBER_199I l
DAffa AVERAGE _ DAILY 20WERLEVEL 11/01/97 532 11/02/97 532 11/03/97 531 11/04/97 534 11/05/97 505 11/06/97 528 11/07/97 530 11/08/97 530 11/09/97 528 11/10/97 532 11/11/97 530 11/12/97 531 11/13/97 531 11/14/97 532 11/15/97 529 11/10/97 531 11/17/97 527 11/18/97 532 11/1997 530 11/20/97 530 11/21/97 529 11/22/97 530 11/23/97 530 11/24/97 528 11/25/97 530 11/20/97 528 11/27/97 529
)
11/28/97 527 11/29/97 528 11/30/97 527 I
t i
t l
(
AVERAGE LOADS ABOVE 512 MWE NET ARE DUE TO COOLER CONDENSER CIRCULATING WATER r
r
=
__y.
O NRC MONTHLY REPORT PRINTED 1MF97 5
f Pape7 DOCKET NO. 50 300 UNIT PRAIRIE ISLAND NO. 2 I
DATE 12/1997 l
COMPLETED BY DALE DUGSTAD i
TELEPHONE 012 38611214376 I
i DEERAT1NG_DAIAJtEEORI l
l DREMATMSIATUS l
i
-- 1. UNIT NAME:
PRAIRIE ISLAND NO.2
- 2. REPORTING PERIOD:
NOVEMBER 1997
[
- 3. LICENSED THERMAL POWER (MWT): 1650
- 4. NAMEPLATE RATING (GROSS MWE):
593 l
S. DESIGN ELECTRICAL RATING (NET MWE): 530
~
6, MAXIMUM DEPENDABLE CAPACITY (GROSS MWE):
544
- 7. MAXIMUM DEPENDABLE CAPACITY (NET MWE):
512
- 8. IF CHANGES OCCUR IN CAPACITY RATINGS (ITEMS 3 7) SINCE LAST REPORT. GIVE REASON:
NONE
- 9. POWER LEVEL TO WHICH RESTRICTED. lF ANY (NET MWE): NONE
- 10. REASONS FOR RESTRICTICNS,IF ANY:
NONE JHl8 EON 1d MTO-DATE CUMULAINE
- 11. HOURS IN REPORTING PERIOD 720 8018 201142
- 12. NUMBER OF HOURS REACTOR CRITICAL 720.0 6489.0 177982.2
- 13. REACTOR RESERVE SHUTDOWN HOURS 0.0 0.00 1518.1 t
- 14. HOURS GENERATOR ON-LINE 720.0 6438.6 176483.1
- 15. UNIT RESERVE SHUTDOWN HOURS 0.0 0.00 0.00
- 10. GROSS THERMAL ENERGY GENERATED (MWH) 1185019 10317857 281239966
- 17. GROSS ELECTRICAL ENERGY GENERATED (MWH) 400930 3447510 92082800
- 18. NET ELECTRICAL ENERGY GENERATED (MWH) 380893 3745703 87056477
- 19. UNIT SERVICE FACTOR 100 80.3 87.7
- 20. UNIT AVAILABILITY FACTOR 100 80.3 87.7
- 21. UNIT CAPACITY FACTOR ( MDC NET) 103.3 79.1 80.2 1
- 22. UNIT CAPACITY FACTOR ( DER NET) 99.8 76.4 81,7
- 23. UNIT FORCED OUTAGE RATE O
8.7 2.6
- 24. FORCED OUTAGE HOURS 0.0 617.2 4731.1
- 25. SHUTDOWNS SCHEDULED OVER NEXT SIX MONTHS (TYPE, DATE. AND DURATION OF EACH):
N/A r
- 26. IF CURRENTLY SHUTDOWN. ESTIMATED STAPTUP DATE:
N/A i
[
L w.
n.
,_.-...,.-..n.w,.
NRC MONTHLY REPORT PRINTED 13/1597 PageB e
DOCKET NO. 50 300 UNIT PRAIRIE tF%ND NO. 2 DATE 12/15'97 COMPLETED BY DALE DUGSTAD TELEPHONE 612 3881121-4376 -
l UNILSHUIDOWMS.AND.EQWER REDMCIl0MB i
MONIBLNOVEMBER.199I DATE UNIT TYPE HOURS REASON METHOD LER NUMBER SYSTEM COMPONENT i
11/30/97 2
None.
O NOTES:
b r
l IYPE REA8DN MEIHQQ SMILILCODE F-FORCED A-EQUIPMENT FAILURE 1 MANUAL -
DRAFT lEEE STD S-SCHEDULED D. MAINTENANCE OR TEST i MANUAL TRIP C REFUELING 3-AUTO TRIP
' D REGULATORY RESTRICTION 4 CONTINUED E-OPERATOR TRAINING AND
$ REDUCED LOAD COMEQNEMI_ CODE LICENSE EXAMINATION 9-OTHER lEEE STD 803A 1983 -
F ADMINISTRATIVE G-OPERATIONAL ERROR HOTHER l
..