ML20203F244
ML20203F244 | |
Person / Time | |
---|---|
Site: | Hope Creek ![]() |
Issue date: | 07/24/1986 |
From: | Corbin McNeil Public Service Enterprise Group |
To: | Adensam E Office of Nuclear Reactor Regulation |
Shared Package | |
ML20203F249 | List: |
References | |
NLR-N86079, NUDOCS 8607300234 | |
Download: ML20203F244 (3) | |
Similar Documents at Hope Creek | |
---|---|
Category:OPERATING LICENSES-APPLIATION TO AMEND-RENEW EXISTING
MONTHYEARML20217E0371999-09-30030 September 1999
[Table view]Application for Amend to License NPF-57,supporting Use of ABB-CE Fuel & Reload Analyses Beginning with Upcoming Cycle 10.Proprietary & non-proprietary Info Re Subject Amend,Encl. Proprietary Info Withheld,Per 10CFR2.790(a)(4) LR-N990357, Application for Amend to License NPF-57,to Change TS to Raise Condensate Storage Tank (CST) Low Level Setpoints & Corresponding Allowable Values Associated with Transfer of HPCI & RCIC Pump Suctions from CST to Suppression Pool1999-08-26026 August 1999 Application for Amend to License NPF-57,to Change TS to Raise Condensate Storage Tank (CST) Low Level Setpoints & Corresponding Allowable Values Associated with Transfer of HPCI & RCIC Pump Suctions from CST to Suppression Pool ML18107A3571999-06-0404 June 1999 Application for Amends to Licenses DPR-70,DPR-75 & NPF-57 Re Transfer of PSEG Ownership Interests & Licensed Operating Authorities to New,Affiliated Nuclear Generating Company, PSEG Nuclear Llc.Proprietary Encls Withheld ML20195B5461999-05-24024 May 1999 Application for Amend to License NPF-57,correcting Typos & Editorial Errors Contained in Ts.Corrections Are Considered to Be Administrative in Nature LR-N990137, Application for Amend to License NPF-57 to Revise TS to Include Oscillation Power Range Monitor (OPRM) Sys,In Preparation for Plans to Fully Enable OPRM Trip Function During Ninth Refueling Outage,Scheduled for Apr 22,20001999-05-17017 May 1999 Application for Amend to License NPF-57 to Revise TS to Include Oscillation Power Range Monitor (OPRM) Sys,In Preparation for Plans to Fully Enable OPRM Trip Function During Ninth Refueling Outage,Scheduled for Apr 22,2000 ML20206G0651999-03-29029 March 1999 Redistributed Application for Amend to License NPF-57, Incorporating Programmatic Controls in TS for Radioactive Effluents & for Environ Monitoring Conforming to Applicable Regulatory Requirements.Rev 18 to ODCM Also Encl ML20205E7931999-03-29029 March 1999 Application for Amend to License NPF-57,incorporating Programmatic Controls in TS for Radioactive Effluents & Environ Monitoring,Conforming to Applicable Regulatory Requirements ML20198T0131998-12-30030 December 1998 Application for Amend to License NPF-57,proposing Rev to Flood Protection TS LCO & Associated Action Statements ML20198N3901998-12-28028 December 1998 Application for Amend to License NPF-57,permitting Increase in Allowable Leak Rate for MSIVs & Deleting MSIV Sealing Sys LR-N980532, Application for Amend to License NPF-57,revising TS by Replacing Accelerated Testing Requirements of TS Table 4.8.1.2-1 with EDG Performance Monitoring & Delete TS 4.8.1.1.3 Requirement to Submit 30-day Special Rept1998-12-16016 December 1998 Application for Amend to License NPF-57,revising TS by Replacing Accelerated Testing Requirements of TS Table 4.8.1.2-1 with EDG Performance Monitoring & Delete TS 4.8.1.1.3 Requirement to Submit 30-day Special Rept ML20155D3441998-10-22022 October 1998 Application for Amend to License NPF-57,to Revise TS to Establish More Appropriate Minimum Battery Electrolyte Temperature Limits ML20154R5821998-10-19019 October 1998 Application for Amend to License NPF-57,eliminating Restrictions Imposed by TS 3.0.4 for Filtration, Recirculation & Ventilation Sys During Fuel Movement & Core Alteration Activities LR-N980363, Application for Amend to License NPF-57,permitting Use of non-class 1E Single Cell Battery Chargers,With Proper Electrical Isolation,For Charging Connected Cells in Operable Class 1E Batteries1998-09-0808 September 1998 Application for Amend to License NPF-57,permitting Use of non-class 1E Single Cell Battery Chargers,With Proper Electrical Isolation,For Charging Connected Cells in Operable Class 1E Batteries ML20151S4301998-08-25025 August 1998 Application for Amend to License NPF-57,implementing Appropriately Conservative SLMCPR for Upcoming Cycle 9 Plant Core & Fuel Designs.Proprietary & non-proprietary Description of Revs to TS Encl.Proprietary Info Withheld ML20236F1121998-06-25025 June 1998 Application for Amend to License NPF-57,deleting Requirement to Perform in-situ Functional Testing of ADS Valves Once Every 18 Months as Part of Startup Testing Activities ML20249A8101998-06-12012 June 1998 Application for Amend to License NPF-57,providing Increased Operational Flexibility During Periods of Elevated River Water Temp & Maintaining Ultimate Heat Sink Operation within Design.Engineering Analyses Also Encl ML20247K7301998-05-13013 May 1998 Application for Amend to License NPF-57,revising TS Inservice Leak & Hydrostatic Testing Requirements.Review Is Requested by 981220,to Support Next Refueling Outage ML20217P9221998-04-28028 April 1998 Application for Amend to License NPF-57,revising TS 3/4.4.2 by Implementing More Appropriate SRV Setpoints.Proprietary GE TR NEDC-32511P, Safety Review for Hope Creek SRV Tolerance Analysis, Encl.Proprietary Info Withheld LR-N970670, Application for Amend to License NPF-57,requesting Rev to App B of TS 4.2.2, Terrestrial Ecology Monitoring, by Rewording Section to Include Completion of Salt Drift Monitoring Program Which Was Completed in Mar 19891997-12-19019 December 1997 Application for Amend to License NPF-57,requesting Rev to App B of TS 4.2.2, Terrestrial Ecology Monitoring, by Rewording Section to Include Completion of Salt Drift Monitoring Program Which Was Completed in Mar 1989 LR-N970622, Application for Amend to License NPF-57,revising TS 3/4.11.1, Liquid Effluents - Concentration, by Adding Requirement to Perform Weekly Sampling & Monthly & Quarterly Composite Analyses of Ssws When Racs Is Contaminated1997-09-29029 September 1997 Application for Amend to License NPF-57,revising TS 3/4.11.1, Liquid Effluents - Concentration, by Adding Requirement to Perform Weekly Sampling & Monthly & Quarterly Composite Analyses of Ssws When Racs Is Contaminated LR-N970618, Application for Amend to License NPF-57,adding Surveillance Requirement in Section 3/4.5.1 to Perform Monthly Valve Position Verification for Each of Four Residual Heat Removal cross-tie Valves1997-09-24024 September 1997 Application for Amend to License NPF-57,adding Surveillance Requirement in Section 3/4.5.1 to Perform Monthly Valve Position Verification for Each of Four Residual Heat Removal cross-tie Valves ML20211M2571997-08-26026 August 1997 Sanitized Supplement to 970331 & 970716 Applications for Amend to License NPF-57,revising Ts.Addl Info & Revised TS Bases Pages Associated W/Amend 101 ML20217Q6641997-08-26026 August 1997 Application for Amend to License NPF-57,requesting Rev to TS to Clarify Plant Basis for Compliance W/Frvs TS Requirements ML20210P3341997-08-20020 August 1997 Application for Amend to License NPF-57,deleting References to Plants Suppression Pool Water Volume from TS & Supporting Planned Mods to ECCS Suction Strainers in Upcoming Refueling Outage,Per NRC Bulletin 96-003 ML20211M2451997-07-16016 July 1997 Sanitized Version of Supplement to 970331 Application for Amend to License NPF-57,revising TS & Providing Revised SLMCPR Values for Upcoming Operating Cycle (Cycle 8) ML20149G4271997-07-16016 July 1997 Supplements Application for Amend to License NPF-57, Submitted 970331.Supplement Provides Revised SLMCPR Values for Upcoming Operating Cycle (Cycle 8).TSs & Proprietary Info Re SLMCPR Changes,Encl.Proprietary Info,Withheld LR-N970217, Application for Amend to License NPF-7,revising Sections of TSs to Delete Reference to Rod Sequence Control Sys & Reduce Rod Worth Minimizer Low Power Setpoint from 20% to 10%1997-06-19019 June 1997 Application for Amend to License NPF-7,revising Sections of TSs to Delete Reference to Rod Sequence Control Sys & Reduce Rod Worth Minimizer Low Power Setpoint from 20% to 10% ML20141G8221997-05-19019 May 1997 Application for Amend to License NPF-57,revising Ultimate Heat Sink Temp & River Water Level Limits Which Resolve TS Related Issues Documented in Hope Creek Corrective Action Program ML20140F0261997-04-30030 April 1997 Application for Transfer of Control Re Operating License NPF-57 for Hcngs.Joint Proxy Statement/Prospectus Describing Details of Util Agreement & Plant of Merger W/Delmarva Power & Light Co,Encl LR-N970183, Application for Amend to License NPF-57,requesting Mod to Listed TSs to Adopt Option B of 10CFR50,App J1997-04-0101 April 1997 Application for Amend to License NPF-57,requesting Mod to Listed TSs to Adopt Option B of 10CFR50,App J ML20137M1061997-03-31031 March 1997 Application for Amend to License NPF-57,revising TS to Improve Consistency Between TS & Plant Configuration, Operation & Testing & Complete Required CA to Resolve TS Discrepancies Identified in CA Program ML20137M5811997-03-31031 March 1997 Application for Amend to License NPF-57,representing Changes to TS 2.1.2,action a.1.c for LCO 3.4.1.1 & Bases for TS 2.1. Info Re Safety Limit Min Critical Power Ratio Changes Encl. Info Withheld ML20135E8041997-03-0303 March 1997 Application for Amend to License NPF-57,changing TS 3/4.3.1, Reactor Protection Sys Instrumentation, 3/4.3.2, Isolation Actuation Instrumentation & 3/4.3.3, Emergency Core Cooling Sys Actuation Instrumentation ML20134M0771997-02-11011 February 1997 Application for Amend to License NPF-57,requesting Rev to 3/4.8 Re Electrical Power Systems for Improvements to EDG ML20134B5441997-01-24024 January 1997 Application for Amend to License NPF-57,changing TS 3.1.5, Control Rod Scram Accumulators ML20134F4231996-10-25025 October 1996 Application for Amend to License NPF-57,requesting Rev to 3.1.3.5 Re Control Rod Scram Accumulators ML20117K1231996-08-30030 August 1996 Application for Amend to License NPF-57,changing FSAR Decoupling SSE from LOCA ML18102A2541996-07-12012 July 1996 Suppls to Application for Amend to Licenses DPR-70,DPR-75 & NPF-57 Re Qualifications of Operations Manager ML20100R0841996-03-0606 March 1996 Application for Amend to License NPF-57,revising Diesel Fuel Oil Storage & Transfer Requirements ML18101B2501996-02-26026 February 1996 Application for Amends to Licenses DPR-70,DPR-75 & NPF-57, Revising TS Section 6.0 Re Administrative Controls of Plant ML20097C5671996-02-0505 February 1996 Application for Amend to License NPF-57,revising SR 4.6.2.2.b & 4.6.2.3.b to Include Flow Through RHR Heat Exchanger Bypass Line in SPC & Suppression Pool Spray Flow Path Used During RHR Pump Testing ML18101B1751996-01-11011 January 1996 Application for Amends to Licenses DPR-70,DPR-75 & NPF-57, Revising TS Section 6.0 Re Administrative Controls & Replacing Specific Mgt Titles W/Generic Mgt Functional Positions ML20099L6571995-12-28028 December 1995 Application for Amend to License NPF-57,revising TS Definition 1.4 Re Channel Calibr to Ensure Required Testing Methodology Aligns W/Std Industry Methodology for Instrument Channels Having T/C or RTD as Sensor ML20098D0011995-10-0707 October 1995 Application for Amend to License NPF-57,revising SR 4.8.1.1.2 Re Testing of EDGs to Be Consistent W/Applicable Licensing Documents Used for Development of EDG Surveillance ML20086T6991995-07-27027 July 1995 Application for Amend to License NPF-57,revising Ts,By Incorporating Updated Pressure Vs Temperature Operating Limit Curves Contained in TS Figure 3.4.6.1-1 ML20083B9591995-05-0404 May 1995 Application for Amend to App a of License NPF-57,increasing Annual Operational Limit for Drywell & Suppression Chamber Purge Sys from 120 H to 500 H ML20082T3351995-04-18018 April 1995 Application for Amend to License NPF-57,revising TS Table 4.3.7.1-1, Radiation Monitoring Instrumentation SRs by Extending Channel Functional Test Interval from Monthly to Quarterly for Each Instrument ML20082C1171995-03-30030 March 1995 Application for Amend to License NPF-57 for Hope Creek Generating Station.Amend Would Eliminate Selected Response Time Testing Requirements from TS & Associated Bases Changes ML20078C8351995-01-20020 January 1995 Application for Amend to License NPF-57,to Remove Specification from TSs & Relocates Bases to Plant UFSAR & Surveillance Requirements to Applicable Surveillance Procedures ML20078C8141995-01-20020 January 1995 Application for Amend to License NPF-57,to Revise Surveillance Requirement 4.1.3.1.2.b Re CR Immovable as Result of Excessive Friction or Mechanical Interference 1999-09-30 Category:TEXT-LICENSE APPLICATIONS & PERMITS MONTHYEARML20217E0371999-09-30030 September 1999
[Table view]Application for Amend to License NPF-57,supporting Use of ABB-CE Fuel & Reload Analyses Beginning with Upcoming Cycle 10.Proprietary & non-proprietary Info Re Subject Amend,Encl. Proprietary Info Withheld,Per 10CFR2.790(a)(4) ML20211N5471999-09-0808 September 1999 Amend 121 to License NPF-57 Revising TSs by Locating Procedural Details of RETS to Offsite Dose Calculation Manual LR-N990357, Application for Amend to License NPF-57,to Change TS to Raise Condensate Storage Tank (CST) Low Level Setpoints & Corresponding Allowable Values Associated with Transfer of HPCI & RCIC Pump Suctions from CST to Suppression Pool1999-08-26026 August 1999 Application for Amend to License NPF-57,to Change TS to Raise Condensate Storage Tank (CST) Low Level Setpoints & Corresponding Allowable Values Associated with Transfer of HPCI & RCIC Pump Suctions from CST to Suppression Pool ML18107A3571999-06-0404 June 1999 Application for Amends to Licenses DPR-70,DPR-75 & NPF-57 Re Transfer of PSEG Ownership Interests & Licensed Operating Authorities to New,Affiliated Nuclear Generating Company, PSEG Nuclear Llc.Proprietary Encls Withheld ML20195B5461999-05-24024 May 1999 Application for Amend to License NPF-57,correcting Typos & Editorial Errors Contained in Ts.Corrections Are Considered to Be Administrative in Nature LR-N990137, Application for Amend to License NPF-57 to Revise TS to Include Oscillation Power Range Monitor (OPRM) Sys,In Preparation for Plans to Fully Enable OPRM Trip Function During Ninth Refueling Outage,Scheduled for Apr 22,20001999-05-17017 May 1999 Application for Amend to License NPF-57 to Revise TS to Include Oscillation Power Range Monitor (OPRM) Sys,In Preparation for Plans to Fully Enable OPRM Trip Function During Ninth Refueling Outage,Scheduled for Apr 22,2000 ML20205E7931999-03-29029 March 1999 Application for Amend to License NPF-57,incorporating Programmatic Controls in TS for Radioactive Effluents & Environ Monitoring,Conforming to Applicable Regulatory Requirements ML20206G0651999-03-29029 March 1999 Redistributed Application for Amend to License NPF-57, Incorporating Programmatic Controls in TS for Radioactive Effluents & for Environ Monitoring Conforming to Applicable Regulatory Requirements.Rev 18 to ODCM Also Encl ML20198T0131998-12-30030 December 1998 Application for Amend to License NPF-57,proposing Rev to Flood Protection TS LCO & Associated Action Statements ML20198N3901998-12-28028 December 1998 Application for Amend to License NPF-57,permitting Increase in Allowable Leak Rate for MSIVs & Deleting MSIV Sealing Sys LR-N980532, Application for Amend to License NPF-57,revising TS by Replacing Accelerated Testing Requirements of TS Table 4.8.1.2-1 with EDG Performance Monitoring & Delete TS 4.8.1.1.3 Requirement to Submit 30-day Special Rept1998-12-16016 December 1998 Application for Amend to License NPF-57,revising TS by Replacing Accelerated Testing Requirements of TS Table 4.8.1.2-1 with EDG Performance Monitoring & Delete TS 4.8.1.1.3 Requirement to Submit 30-day Special Rept ML20155D3441998-10-22022 October 1998 Application for Amend to License NPF-57,to Revise TS to Establish More Appropriate Minimum Battery Electrolyte Temperature Limits ML20154R5821998-10-19019 October 1998 Application for Amend to License NPF-57,eliminating Restrictions Imposed by TS 3.0.4 for Filtration, Recirculation & Ventilation Sys During Fuel Movement & Core Alteration Activities LR-N980363, Application for Amend to License NPF-57,permitting Use of non-class 1E Single Cell Battery Chargers,With Proper Electrical Isolation,For Charging Connected Cells in Operable Class 1E Batteries1998-09-0808 September 1998 Application for Amend to License NPF-57,permitting Use of non-class 1E Single Cell Battery Chargers,With Proper Electrical Isolation,For Charging Connected Cells in Operable Class 1E Batteries ML20151S4301998-08-25025 August 1998 Application for Amend to License NPF-57,implementing Appropriately Conservative SLMCPR for Upcoming Cycle 9 Plant Core & Fuel Designs.Proprietary & non-proprietary Description of Revs to TS Encl.Proprietary Info Withheld ML20236F1121998-06-25025 June 1998 Application for Amend to License NPF-57,deleting Requirement to Perform in-situ Functional Testing of ADS Valves Once Every 18 Months as Part of Startup Testing Activities ML20249A8101998-06-12012 June 1998 Application for Amend to License NPF-57,providing Increased Operational Flexibility During Periods of Elevated River Water Temp & Maintaining Ultimate Heat Sink Operation within Design.Engineering Analyses Also Encl ML20247K7301998-05-13013 May 1998 Application for Amend to License NPF-57,revising TS Inservice Leak & Hydrostatic Testing Requirements.Review Is Requested by 981220,to Support Next Refueling Outage ML20217P9221998-04-28028 April 1998 Application for Amend to License NPF-57,revising TS 3/4.4.2 by Implementing More Appropriate SRV Setpoints.Proprietary GE TR NEDC-32511P, Safety Review for Hope Creek SRV Tolerance Analysis, Encl.Proprietary Info Withheld LR-N970670, Application for Amend to License NPF-57,requesting Rev to App B of TS 4.2.2, Terrestrial Ecology Monitoring, by Rewording Section to Include Completion of Salt Drift Monitoring Program Which Was Completed in Mar 19891997-12-19019 December 1997 Application for Amend to License NPF-57,requesting Rev to App B of TS 4.2.2, Terrestrial Ecology Monitoring, by Rewording Section to Include Completion of Salt Drift Monitoring Program Which Was Completed in Mar 1989 ML20199C1411997-11-0606 November 1997 Amend 108 to License NPF-57,changes TS 3/4.11.1, Liquid Effluent-Concentration. Change Adds Requirement to Perform Weekly Sampling & Monthly & Quarterly Composite Analyses of Station Service Water Sys LR-N970622, Application for Amend to License NPF-57,revising TS 3/4.11.1, Liquid Effluents - Concentration, by Adding Requirement to Perform Weekly Sampling & Monthly & Quarterly Composite Analyses of Ssws When Racs Is Contaminated1997-09-29029 September 1997 Application for Amend to License NPF-57,revising TS 3/4.11.1, Liquid Effluents - Concentration, by Adding Requirement to Perform Weekly Sampling & Monthly & Quarterly Composite Analyses of Ssws When Racs Is Contaminated LR-N970618, Application for Amend to License NPF-57,adding Surveillance Requirement in Section 3/4.5.1 to Perform Monthly Valve Position Verification for Each of Four Residual Heat Removal cross-tie Valves1997-09-24024 September 1997 Application for Amend to License NPF-57,adding Surveillance Requirement in Section 3/4.5.1 to Perform Monthly Valve Position Verification for Each of Four Residual Heat Removal cross-tie Valves ML20217Q6641997-08-26026 August 1997 Application for Amend to License NPF-57,requesting Rev to TS to Clarify Plant Basis for Compliance W/Frvs TS Requirements ML20211M2571997-08-26026 August 1997 Sanitized Supplement to 970331 & 970716 Applications for Amend to License NPF-57,revising Ts.Addl Info & Revised TS Bases Pages Associated W/Amend 101 ML20210P3341997-08-20020 August 1997 Application for Amend to License NPF-57,deleting References to Plants Suppression Pool Water Volume from TS & Supporting Planned Mods to ECCS Suction Strainers in Upcoming Refueling Outage,Per NRC Bulletin 96-003 ML20149G4271997-07-16016 July 1997 Supplements Application for Amend to License NPF-57, Submitted 970331.Supplement Provides Revised SLMCPR Values for Upcoming Operating Cycle (Cycle 8).TSs & Proprietary Info Re SLMCPR Changes,Encl.Proprietary Info,Withheld ML20211M2451997-07-16016 July 1997 Sanitized Version of Supplement to 970331 Application for Amend to License NPF-57,revising TS & Providing Revised SLMCPR Values for Upcoming Operating Cycle (Cycle 8) LR-N970217, Application for Amend to License NPF-7,revising Sections of TSs to Delete Reference to Rod Sequence Control Sys & Reduce Rod Worth Minimizer Low Power Setpoint from 20% to 10%1997-06-19019 June 1997 Application for Amend to License NPF-7,revising Sections of TSs to Delete Reference to Rod Sequence Control Sys & Reduce Rod Worth Minimizer Low Power Setpoint from 20% to 10% ML20141G8221997-05-19019 May 1997 Application for Amend to License NPF-57,revising Ultimate Heat Sink Temp & River Water Level Limits Which Resolve TS Related Issues Documented in Hope Creek Corrective Action Program ML20140F0261997-04-30030 April 1997 Application for Transfer of Control Re Operating License NPF-57 for Hcngs.Joint Proxy Statement/Prospectus Describing Details of Util Agreement & Plant of Merger W/Delmarva Power & Light Co,Encl LR-N970183, Application for Amend to License NPF-57,requesting Mod to Listed TSs to Adopt Option B of 10CFR50,App J1997-04-0101 April 1997 Application for Amend to License NPF-57,requesting Mod to Listed TSs to Adopt Option B of 10CFR50,App J ML20137M1061997-03-31031 March 1997 Application for Amend to License NPF-57,revising TS to Improve Consistency Between TS & Plant Configuration, Operation & Testing & Complete Required CA to Resolve TS Discrepancies Identified in CA Program ML20137M5811997-03-31031 March 1997 Application for Amend to License NPF-57,representing Changes to TS 2.1.2,action a.1.c for LCO 3.4.1.1 & Bases for TS 2.1. Info Re Safety Limit Min Critical Power Ratio Changes Encl. Info Withheld ML20135E8041997-03-0303 March 1997 Application for Amend to License NPF-57,changing TS 3/4.3.1, Reactor Protection Sys Instrumentation, 3/4.3.2, Isolation Actuation Instrumentation & 3/4.3.3, Emergency Core Cooling Sys Actuation Instrumentation ML20134M0771997-02-11011 February 1997 Application for Amend to License NPF-57,requesting Rev to 3/4.8 Re Electrical Power Systems for Improvements to EDG ML20134B5441997-01-24024 January 1997 Application for Amend to License NPF-57,changing TS 3.1.5, Control Rod Scram Accumulators ML20134F4231996-10-25025 October 1996 Application for Amend to License NPF-57,requesting Rev to 3.1.3.5 Re Control Rod Scram Accumulators ML20117K1231996-08-30030 August 1996 Application for Amend to License NPF-57,changing FSAR Decoupling SSE from LOCA ML18102A2541996-07-12012 July 1996 Suppls to Application for Amend to Licenses DPR-70,DPR-75 & NPF-57 Re Qualifications of Operations Manager ML20100R0841996-03-0606 March 1996 Application for Amend to License NPF-57,revising Diesel Fuel Oil Storage & Transfer Requirements ML18101B2501996-02-26026 February 1996 Application for Amends to Licenses DPR-70,DPR-75 & NPF-57, Revising TS Section 6.0 Re Administrative Controls of Plant ML20097C5671996-02-0505 February 1996 Application for Amend to License NPF-57,revising SR 4.6.2.2.b & 4.6.2.3.b to Include Flow Through RHR Heat Exchanger Bypass Line in SPC & Suppression Pool Spray Flow Path Used During RHR Pump Testing ML18101B1751996-01-11011 January 1996 Application for Amends to Licenses DPR-70,DPR-75 & NPF-57, Revising TS Section 6.0 Re Administrative Controls & Replacing Specific Mgt Titles W/Generic Mgt Functional Positions ML20099L6571995-12-28028 December 1995 Application for Amend to License NPF-57,revising TS Definition 1.4 Re Channel Calibr to Ensure Required Testing Methodology Aligns W/Std Industry Methodology for Instrument Channels Having T/C or RTD as Sensor ML20098D0011995-10-0707 October 1995 Application for Amend to License NPF-57,revising SR 4.8.1.1.2 Re Testing of EDGs to Be Consistent W/Applicable Licensing Documents Used for Development of EDG Surveillance ML20086T6991995-07-27027 July 1995 Application for Amend to License NPF-57,revising Ts,By Incorporating Updated Pressure Vs Temperature Operating Limit Curves Contained in TS Figure 3.4.6.1-1 ML20083B9591995-05-0404 May 1995 Application for Amend to App a of License NPF-57,increasing Annual Operational Limit for Drywell & Suppression Chamber Purge Sys from 120 H to 500 H ML20082T3351995-04-18018 April 1995 Application for Amend to License NPF-57,revising TS Table 4.3.7.1-1, Radiation Monitoring Instrumentation SRs by Extending Channel Functional Test Interval from Monthly to Quarterly for Each Instrument ML20082C1171995-03-30030 March 1995 Application for Amend to License NPF-57 for Hope Creek Generating Station.Amend Would Eliminate Selected Response Time Testing Requirements from TS & Associated Bases Changes 1999-09-08 |
Text
s Pubhc Service Electric and Gas Company Ctrbin A. McNeill, Jr. Pubhc Service Electric and Gas Company P.O. Box 236, Hancocks Bridge, NJ 08038 609 339-4800 Vice President -
Nuclear July 24, 1986 NLR-N86079 Director of Nuclear Reactor Regulation United States Nuclear Regulatory Commission 7920 Norfolk Avenue Bethesda, Maryland 20814
, Attention: Ms. Elinor Adensam, Director
. Project Directorate #3 Division of BWR Licensing
Dear Ms. Adensam:
HOPE CREEK GENERATING STATION TECHNICAL SPECIFICATION CHANGES FOR INCORPORATION IN THE FULL-POWER OPERATING LICENSE HOPE CREEK GENERATING STATION DOCKET NO. 50-354 Public Service Electric and Gas Company (PSE&G): is currently operating Hope Creek Generating Station (HCGS) in accordance with the Technical Specifications contained in Appendix A of Operating License NPP-50, dated April 11, 1986. As a result of operating experience gained since the issuance of the low power operating
-license, PSE&G is requesting that the HCGS Technical Specifications be revised, as shown in the Attachments, when the full-power operating license is issued. Since HCGS currently meets the requirements of the existing Technical Specifications, no amendment to the present low-power operating. license is sought. It can be concluded from the justification and explanation for the changes indicated in the Attachments that these revisions do not involve a significant hazards consideration. This change supplements previous changes forwarded in a letter dated June 13, 1986.
Should you have any questions, do not hesitate to contact us.
Sincerely, m
Attachments 8607300234 860724 1$
D PDR ADOCK 05000354 k P PDR i
Director of Nuclear 2 Reactor Regulation 7/24/86 C Mr. D. H. Wagner USNRC Licensing Project Manager Mr. R.W. Borchardt USNRC Senior Resident Inspector
ATTACHMENT I TECHNICAL SPECIFICATION 4. 8.1.1. 2. f l .b AC SOURCES - OPERATING Surveillance Requirement 4.8.1.1.2.f.l.b specifies a Saybolt Second Universal (SSU) viscosity of less than or equal to 45 SSU for diesel generator new fuel oil or a fuel oil sample from the storage tanks. The attached change would revise the upper limit from 45 SSU to 40.1 SSU.
Although this change will have no discernible effect on the performance or operation of the Emergency Diesel Generators, this Technical Specification revision is necessary to maintain strict compliance with the requirements of ASTM Standard D975.77 for No. 2 grade diesel fuel oil, t