ML20203F239

From kanterella
Jump to navigation Jump to search
Discusses Four Remote Oil Pots,One for Each Rcp.Fire Detection on Both of Elevations Side of Containment
ML20203F239
Person / Time
Site: Davis Besse Cleveland Electric icon.png
Issue date: 12/09/1997
From:
CENTERIOR ENERGY
To:
NRC
References
NUDOCS 9712170316
Download: ML20203F239 (1)


Text

0EC-09.97 11:00 FPOMit3JCLEfR LICENSItC 419-249-2302 TO: RESIDENT PAGE:02 There are four remote oil fill pots, one for each Reactor Coolant Pump (RCP). Each fill 33_ r _ pdt is located on the 603' elevation of the containment building.

The fill pots for RCP 1 1 and RCP l-2 are located on the west side of containment, above a concrete floor at the 603' elevation. Oil from a leak or spill at this location would migrate to a floor drain which empties into the containment normal sump. There is no redundant safe shutdown equipment in the imnwdiate vicinity at these locations.

The fill pots for RCP 2 1 and RCP 2-2 are located on the east side of containment at the 603' elevation, above grating. Oil from a leak or spill in the vicinity of these two fill pots would fall through the grating to the concrete floor at the 585* elevation below, and then migrate to a floor drain which empties into the contamment normal sump. Redundant safe shutdown components in the vicinity are adequately separated or are protected by a radiant energy shield. There is fire detection on both of these elevations in this side of containment.

la the event a fite were to occur, it would be limited to one half gallon of oil. Due to the lack of oil addition system presst:rization, the large size of the containment, the fact that during the oil addition process there will be personnel in the immediate vicinity instructed to report to the control room any evidence of smoke, and the limited fire size caused by one half gallon of oil, there is reasonable assurance that damage would not occur to safe shutdown equipment.

The lower oil reservoir of each RCP is vented to the containment atmosphere.

k/=fSD-TW.

Fe,,,: % :,. gsw A h ' <hla,a.

T;: N&c Kau:

<zinin h

h001/

D d

1?C019 9712170316 971209 PDR ADOCK 05000346 F

pag.

e

-