ug.
TABLE 3-2 e-MINIMUM FREOUENCIFS FOR CIIECKS. CALIBRATIONS AND TESTING OF
- o ENGINEERED SAFFTY FEATURES. INSTRUMENTATION AND CONTROLS n
04
$d Channel Descrisdion Surveillance Function Frequency Surveillance Method 1.
Pressurizer Pressure lew a.
Check S
a.
CilANNEL CHECK b.
Tea Q"'P*
b.
CIIANNEL FUNCTIONALTEST l
u c.
Calibrate R
c.
CIfANNEL CALIBRATION l
CIIANNEL CALIBRATION l
i 2.
Pressurizer Low a.
Calibrate R
a.
Pressure Blocking Circuit CilANNEL FUNCTIONAL TEST (Sinmlation of l
3.
Safety injection a.
Test Q
a.
PP13 or CPilS 2/4 logic)
Actustion irgic b.
Test Rm b.
CIIANNEL FUNCTIONAL TEST l
I l
3-7 Arnendrnent No. 54,443,182 i
o l
L t
TABLE 3-2 (Continued)
MINIMUM FREOUENCIES FOR CllECKS. CALIBRATIONS AN11 TESTANG OF ENGINEERED SAFETY FEATURES. INSTRUMENTATION AND COmOLS Channel Description Surveillance Function Frequency Surveillance Method 18.
SIRW Tank Temperature a.
Check D'*
a.
Verify that tu.v..iure is within limits.
b.
Test R
b.
Measure tuir.,iure of SIRW tank with standard laboratory instm-rnents.
19.
Manual Recircuts' ion a.
Test R
a.
CHANNEL FUNCTIONAL TEST l
Actuation l
20.
Recirculation Actuation a.
Test Q
a.
CHANNEL FUNCTIONAL TEST l
b.
Test Rm b.
CIIANNEL FUNCTIONAL TEST l
21.
4.16 KV Enegency Bus a.
Check S
a.
Verify voltage readings are above alarm initiation on degraded voltage low Voltage (loss of level - supervisory lights "on".
[
Voltage and Degraded Voltage) Actuation legic b.
Test Q
b.
CilANNEL FUNCTIONAL TEST (Undervoltage g
relay) c.
Calibrate R
c.
CllANNEL CAllBRATION l
22.
Manual Emergency Off-site a.
Test R
a.
CIIANNEL FUNCTIONAL TEST l
Power Imw Trip Actuation 3 12 Arnendrnent No. d',!53,!6' 'n.182 2
_ _. _ _ _