Ms. Irene Johnson, Acting Manage' Nuc! car Regulatory Services Commonwealth Edison Company Executive Towers West 111 1400 Opus Place, Suite 500 Downers Grove, IL 60515

SUBJECT:

SUPPLEMENTAL SAFETY EVALUATION OF THE LASALLiE COUNTY STATION RESPONSE TO THE STATION BLACKOUT RULE (TAC NOS. M98864 AND M96865)

Dear Ms. Johnson:

By letter dated May 28,1997, Commonwealth Edison Company (Comed) requested a clarification to the LaSalle County Station Blackout (SBO) Safety Evaluation (SE) dated March 6,1992. Specifically, Comed requested clarification of Section 2.3.2 of the SBO SE related to the Class 1E battery capacity. The SE, in addition to stating that the battery capacity calculations L. sed an electrolyte temperature of 60 degrees Fahrenheit, a design margin of 1.0, and an aging factor of 1.25, also states that the battery calculation provides a minimum margin of 8.3 percent for all Class 1E batteries except the Division 3 batteries. Comed has determined that the published 1 minute rating for the batteries was overstated and the remaining battery margin is actually 3.7 percent after recovery. Comed determiried that an adjustment of the aging factor is necessary to maintain a 5 percent remaining margin. Comed has committed to revise the plant procedures and Updated Final Safety Analysis Report to be consistent with the change to the aging factor and 5 percent remaining battery margin prior to restart of either unit.

The staff has reviewed Comed's proposal and has determined, as discussed in the enclossd supplemental SE, that the proposed changes are consistent with the SBO rule and are acceptable.

Sincerely, Orig, signed by Donna M. Skay, Project Msnager Project Dimetorate lll 2 Division of Reactor Projects - lilllV Office of Nuclear Reactor Regulation 1

Docket Nos. 50-373,50-374 pO\\

.b

Enclosure:

Supplemental Safety Evatuation cc w/ encl: see next page

{

!DNN7 PUBUC PDilb2 r/f E. Adensam.EGA1 R. Capra C. Moore

'D. Skay OGC,015B18 A. Vogel, Riti

  • SE provided by memo did 10/17/97; no major revisions DOCUMENT NAME: G:\\CMNTJR\\!.ASALLE\\L',98864.SE Ta receive a copy of thle documerit,indleate try thehn: 'C', = Copy without enclosures "E" = Copy with enclosures "N* = No copy OfflCE PM:PDill-2 k.

RAJPDlW D

BC: EELB D:PDill-2 5

NAME DSKAY (Q W 6t@REW JCALVO

  • RCAPRA Peu DATE 12/rl/97 120/97 10/17/97 12/4 /97 OFFICIAL RECORD COPY l

9712120355 971204 m o n e m n.

'oid I.llll.lil ll.11.I!l.l1.1a a EMER &V

^=

goa

+

@*og l

4 UNITED STATES y

j

,j NUCLEAR REGULATORY COMMISSION-t WASHINGTON, D.C. 3065H001

%...../

December 4, 1997 Ms. Irsne Johnson, Acting Manager Nuclear Regulatory Services Commonwealth Edison Company Executive Towers West til 1400 Opus Place, Suite 500 Downers Grove,IL 60515

SUBJECT:

SUPPLEMENTAL SAFETY EVALUATION OF THE LASALLE COUNTY STATION RESPONSE TO THE STATION BLACK 3UT RULE (TAC NOS, M96864 AND M98865)

Dear Ms. Johnson:

By letter dated May 28,1997, Commonwealth Edison Company (Comed) requested a clarification to the LaSalle County Station Blackout (SBO) Safety Evaluation (SE) dated March 6,1992. Specifically, Comed requested clarincation of Section 2.3.2 of the SBO SE related to the Class 1E battery capacity. The SE, in addition to stating that the battery capacity

(,

calculations used an electrolyte temperature of 60 degrees Fahrenheit, a design margin of 1.0, and an aging factor of 1.25, also states that the battery calculation provides a minimum margin of 8.3 percent for all Class 1E batteries ext,ept the Division 3 batteries. Comed has determined that the published 1-minute rating for the batteries was overstated and the remaining t4 ; ty margin is actually 3.7 percent after recovery. Comed determined that an adjustn.ent of the aging factor is necessary to maintain a 5 percent remaining margin. Comed has committed to revise the plant procedures and Updated Final Safety Analysis Report to ba consistent with the change to the sging factor and 5 percent remaining battery margin prior to restart of either unit.

The staff has reviewed Comed's proposal and has determined, as tiiscussed in the enclos6d supplemental SE, that the proposeo changes are consist 6at with the SBO rule and are acceptable.

Sincerep a& J &

Donna M. Skay, Project M ager Project Directorate 111-2 Division of Reacto-Projects - lil/IV Office of Nuclear Reactor Regulation Docket Nos. 50-373, 50-374

Enclosure:

Supplemental Safety Evaluation

.0 w/ encl: see next page

l. Johnson LaSalle County Station Commonwealth Edison Company Unit Nos.1 and 2 cc:

Phillip P. Steptoe, Esquire Robert "ushing Sidley and Austin Chef, Public Utilities Division One First National Plaza lilinois Attomey General's Office Chicago,lilinois 60603 100 West Randolph Street Chicago, Illinois 60601 Assistant Attomey General 100 West Randolph Street Michael I. Miller, Esquire Suite 12 Sidley and Austin Chicago, Illinois 60601 One First National Plaza Chica00. lilinois 60603 U.S. Nuclear Regulatory Commission LaSalle Resident inspectors Office Document Control Desk-Licensing 2605 N. 21st Road Commonwealth Edison Company Marseilles, Illinois 61341 9756 1400 Opus Place, Suite 400 Downers Grove, Illinois 60515 Chairman LaSalle County Board of Supervisors Commonwealth Edison Company LaSalle County Courthouse Site Vice Pres.ident - LaSalle Ottawa, Illinois 6135; Rural Route 1 P.O. Box 220 Attomey General Merseilles, Illinois 61341 500 South Second Street Srwingfield,Illino;s 62701 Chairman lilinois Commerce Comn:Ission

t. eland Building 527 East Capitol Avenue Springfield,ll!inois 62706 lilinois Department of Nuclear Safety Office of Nuclear Facility Safety 1035 Outer Park Drive Springfield, Illinois 62704 Regional Administrator U.S. NRC, Rogion til 801 Warrenville Road Lisle, Illinois 60532-4351 Commonwealth Edison Company LaSalle Station Manager Rural Route 1 P.O. Box 220 Marseilles, Illinois 61341