ML20203A640

From kanterella
Jump to navigation Jump to search
Forwards Insp Repts 50-454/98-06 & 50-455/98-06 on 980120-23 & 26.Noncited Violation Re Workers Failure to Follow Directions on Posting Was Identified.Event on 980111,involving Worker Who Crossed Boundary Identified
ML20203A640
Person / Time
Site: Byron  
Issue date: 02/17/1998
From: Grobe J
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
To: Kingsley O
COMMONWEALTH EDISON CO.
Shared Package
ML20203A644 List:
References
50-454-98-06, 50-454-98-6, 50-455-98-06, 50-455-98-6, NUDOCS 9802240085
Download: ML20203A640 (3)


See also: IR 05000454/1998006

Text

_ _ _ _ _

___---_

- _ _

Oc.3

.

February 17, 1998

.

Mr. Oliver D. Kingsley

President, Nuclear Generation G oup

Commonwealth Edison Company

ATTN: Regulatory Services

Executive Towers West lli

1400 Cpus Place, Suite 500

Downers Grove,IL 60515

SUBJECT:

NRC ROUTINE RADIATION PROTECTION INSPECTION REPORTS

50-454/98006(DRS); 50-455/98006(DRS)

1

,

Dear Mr. Kingsley:

On Janusry 26 1998, the NRC completed an inspection at your Byron Generating Station Units

1 and 2. The enclosed report presents the results of tnat inspection.

The inspection was an examination of activities conducted under your license as they relate to

radiation safety and to compliance with the Commission's rules and regulations and with the

conditions of your license. Within these areas, the inspection consisted of selective

examinations of procedures and representative records, interviews wlth personnel, and

observation of activities in progress. Specifically, the inspection focused on your survey

program, unconditional and conditional release programs, and overall radiologicsl conditions of

the plant.

Overall, the survey program, and unconditional and conditionalIelease programs were

generally well implemented. We are concerned, however, with the event involving the worker

who crossed a radiography boundary on January 11,1998. Although the individual received no

additional exposure from crossing the boundary, radiography work has the potential for very

high exposures if proper precautions and procedures are not followed. The workers failure to

follow the directions on the posting is a concern and resulted in a non-cited violation. We also

identified isolated problems with the completeness of survey documentation and the review of

that documentation, including an instance when a survey reccrd was approved prior to final

completion. Discussions with Radiation Protection management indicated that this did not meet

stat lon expectations. A non-cited violation was identified for incomplete surv 1 documentation.

Additionally, we identified a weakness in the way high radiation areas within Antainment were

posted during the steam generator replacement project. Although the majority of the areas in

containment did not have radiation fields high enough to meet the definition of a high radiation

area as defined by 10 CFR Part 20, all access points into containment were posted as a high

radiation area. The purpose of radiological postings is to alert workers to the presence of

radiation fields and help them to keep their doses ALARA. Posting til of containment es a high

radiation area and not the individual discrete areas within containment may not provide workers

with sufficient radiological information to minimize exposure from radiation.

t

in accordance with 10 CFR 2.790 of the NRC'S " Rules of Prcetice," a copy of this letter and the

enclosure will be placed in the NRC Public Document Room (PDR).

l

\\

.

dY

,.mmn,

"

9802240085 980217

PDR

AD3CK 05000454

,

- -

-

l

1

,

. _ _ _ _ _ _ . _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ - _ _ _ _ _ _ _ _ - _ _ _ _ _ _ _ .

,

O. D. Kingsley

2

-

February 17, 1998

We will gladly discuss any questions you have concerning this inspection.

Sincerely,

Original Signed by Harold 0. Christensen (for)'

John A. Grobe, Director

Division of Reactor Safety

Docket Nos.00-454; 50-455

License Nos. NPF-37; NPF-66

Enclosure:

Inspection Reports. 50-454/98006(DRS); 50-455/98006(DR3)

cc w/ encl:

M. Wallace, Chief of Staff

D. Helwig, Senior Vice President

G. Stanley, PWR Vice President

J. Perry, BWR Vice President

D. Farrar, Regulatory

Seivices Manager

I. Johnson, Licensing Director

DCD - Licensing

K. Graesser, Site Vice President

K. Kofron, Station Manager

D. Brindle, Regulatory Assurance

Superviscr

Richard Hubbard

Nathan Schloss, Economist

Office of the Attorney General

State Liaison Officer

State Liaison Officer, Wisconsin

Chairman, Illinois Commerce

Commission

,

DOCUMENT NAME: G:DRS\\BYR98006(DRS)

v.ew..em.,iwm m wie. m e cm m .n e w.c.cm e.n - w w.ec. mew

OFFICE

Rill:DRS

C. Rlll:DRS

c. Rill:DRP

C

Rill:DRS

,

NAME

DNissen:jp AJ Q

GShear PAL 4, MJordanFl./et

JGrobe hn

DATE

02/(,,/98

"'

02/t.t/98 "

02hl/98

'

02/f//98 ~

' ' '

OFFICIAL RECORD COPY

_-_ A

.

_ . . . _ _ . _ . . _ _ . _ . _ . . _ _ . . . _ . _ _ . _ . . . _ _ _ . . . . . . _ - . . _ _ _ _ . _ . _ . _ _ _ . _ . _ _ . . _ _ _ _ _ _ . _ _ . _ .

-

.

O. D. Kingsmy

3

February 17, 1998

-

-

Djaldhu1100

Docket Rie w/ encl

Rlli PRR w/enci

Rlll Enf. Coordinator w/enci

PUBLIC lE-01 w/ encl

SRI, Byron w/enci

TSS w/enci

LPM, NRR w/enci

J. L. Caldwell, Rlli w/ encl

R. A. Capra, NRR w/ enc!

DRP w/enci

A. B. Beach, Rill w/en.-i

DOCDESK w/ encl

DRS w/ encl

IEO w/ encl

i

,