4 PlNK COPY

~

OCT 2 5 m3 Affiliated Environmental Service, Inc.

ATTN: Jack Dauch President 219 Fremont Avenue Sandusky, OH 44870 Gentlemen:

We have reviewed you' application dated September 27, 1985 requesting a new r

license to perform leak testing service. We find that we need additional information concerning your program.

The NRC has prepared the " Guide For the Preparation of Applications For License For the use of Radioactive Materials in Leak-Testing Services" to assist applicants in providing necessary information. Refer to the enclosed guide and provide the following additional information:

1.

Provide a more detailed description of the element and mass number of the radionuclides involved in performing the leak test service.

Refer to the guide, Item 5 on page 5 for examples of suggested responses.

2.

Describe the kinds of sealed sources or sources in devices to be leak tested.

For example, specify the radioisotope and the amount in curies.

Refer to Item 6 on page 6 of the guide for specific examples of the description needed.

3.

Regarding the training provided to any persons involved in leak checks, please provide the information requested in the guide in Item 8 on page 9.

Briefly, this includes providing an outline of the radiological health topics covered, name and training of instructors and describing records of training.

4.

Provide a more complete description of your laboratory facilities located at 219 Fremont Avenue, Sandusky, Ohio.

Include a description of the items addressed in Item 9 on page 10 of the guide, i

5.

It appears form your application that personnel will. wear TLD whole body and finger badges as well as pocket dosimeters during collection of the leak test sample. Therefore, please specify that the organization furnishing the TLD service will be a commercial service company and state the exchange frequency for the TLD's.

i 6.

In addition to the above, describe the use and calibration of the pocket dosimeters. We recommend that the dosimeters be recharged to zero prior to each days use and be calibrated at intervals not to exceed one year.

8604160285 860310 REG 3 LIC30 PDR

Affiliated Environit. ental Service, Inc. 2 OCT 2 51963 7.

Describe the calibratten of your survey meters including frequency and method. Refer to Item 10.2.1 on page 11 of the guide.

8.

Describe the calibration of ycur wipe sample counting equipment. Refer to Item 10.2.2 on page 13 of the guide.

9.

Modify your radiological safety program to include the following:

a.

Any specific instructions provided by the source and device manufacturers on recommended methods and areas to be wiped.

b.

Instructions on what to do in case of emergencies.

Include tle items addressed the the guide in Item 10.3 on page 14.

l Submit the modified program.

10. Describe the types of records you will maintain on leak test samples.

f These records should include the items addressed in Item 10.5 on page 15 i

of the guide.

1 If you have any questions or require clarification on any of the information I

stated above, you may contact us at (312) 790-5625.

We will continue our review of your application upon receipt of this information.

Please reply in duplicate, within 30 days, and refer to Control Number 79851.

Sincerely, Original Signed By Evelyn R. Matson Materials Licensing Section

Enclosure:

Guide on Leak-Testing Services RIII Matson/cm 10/23/85 L

-