- - _---

C. K. McCoy Southors bciser Vce President Operating Company. Inc.

Rgtle Propet 40 inverness Center Parkway PO Ba1795 Dinningharn, Alabama 35201 bi 705 932 71??

Iai 205 93? 0403 SOUTHERN COMPANY Energy ro Serve Your tr'orld'*

December 1,1997-LCV 1124 Docket No.: 50-424 U. S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, D. C. 20555 Ladies and Gentlemen:

VOGTLE ELECTRIC GENERATING PLANT REVISION 8 TO FIRST TEN YEAR INTERVAL INSERVICE INSPECTION PROGRAhi Southern Nuclear Operating Company (SNC), the licensee and operator of the Georgia Power Company (GPC)-owned Yogtle Electric Gencritting Plant (VEGP), :ubmits herein ten copics of Revision 8 to the inservice inspection (ISI) program for VEGP Unit 1 (VEGP 1) for its first ten year insenice inspection interval. The first ten year insenice inspection interval was for the period from May 31,1987 though MLy 30,1997, excluding the one year grace period allowed by 10 CFR 50.55a for completion of all required examinations. The enclosure provides Revision 8 to VEGP 1 ISI Program document ISI-P-006. The program in ell'ect for the first ten year inservice inspection laterval was written to the requirements orthe 1983 Edition of the American Society of Mechanical Engineers (ASME) Boiler and Pressur: Vessel Code,Section XI, with Addenda through Summer 1983 except where relief has been granted by the NRC. The enclosed document supersedes portions of the original ISI program previously submitted to the NRC.

All required examinations were completed during the interval except for certain examinations which were completed during our most recent maintenance / refueling outage which was completed on October 20,1997. No other examinations remain to be completed to fulfill the ASME Section XI requirements for the first ten year insenice inspection interval. The results of the remaining examinations necessary to complete the examination requirements for the first ten year inservice inspection interval will be J h. ] l I addressed in the Owner's Report for Insenice inspection for VEGP-1 Maintenance / Refueling Outage IR7 which will be submitted to the NRC under separate I

cover by January 20,1998.

971203017397g424 blllllbll ll t

PDR ADOCK 0 G

PDR

U; S. Nuclear Regulatr.ty Commission LCV ll24 Page Two l

The Revision 8 changes to the VEGP 1 ISI Program include the following:

]

Modification of existing Relief Requests RR 2, RR 3, RR-4, RR 5, and RR 30, Addition of new Relief Requests RR 63 and RR 64, and

{

Minor editorial changes.

1 Existing Relief Regs-sts RR-2 and RR-3 were prt viously approved by the NRC but approval was later revoked through rulemaking to 10 CFR 50.55a since they concerned ASME Section XI Category B A, item No. Bl.10 reactor pressure vessel (RPV) welds.

The subject relief reguests are being re-submitted to the NRC for review and approval because full Code examination coverage greater than ninety percent (90%) is not possible.

A fbil Code examination is considered to be one where examination coverage is greater than 90% as discussed in ASME Section XI Code Case N-460. That Code Case has been approved by the NRC for use as documented in NRC Regulatory Guide 1.147. Similarly, new Relief Request RR-63, which concerns ASME Section XI Category B A, Item No.

1.10 reactor pressure vessel welds, is submitted for NRC review and approval and involves examination coverage limitations whereby a full Code examination is not capable of being performed for the affected welds. Relief Requests RR-2, RR 3, and RR-63 constitute requested relief from both the requirements of the ASME Section XI Code aml 10 CFR 50.55a(g)(6)(ii)(A).

- Existing Relief Request RR-2 is revised to address examination limitations for weld' ll201 V6-001-WO6 which is an RPV lower shell to-bottom head weld. Examination coverage for this ASME Section XI Category B A, Item No. Bl.11 weld is limited to approximately 62% due to six core support lugs physically obstmeting a portion of the subject weld. As a result, the examination coverage achievable for the subject weld does not constitute a full-Code examination. No alternate examinations are practical.

Existing Relief Request RR 3 is resised to address examination limitations for welds 11201-V6-001 W18,11201-V6-001 W19, and 11201 V6-001-W20, which are RPV lower shelllongitudinal welds. Examination coverage for each of these three ASME

'v B A item No B 12 we s was m te to approx mate yl 75 %

1, ld li i d i

Section XI f'"

percent coverage s to core support lugs physically obstructing a portion of the subject welds. As a result, the achievable examination coverages for the subject welds do not constitute full Code examinations. No alternate examinations are practical.

Existing Relief Requests RR-4, which was previously reviewed and approved by the NRC, is withdrawn. This relief request involved ASME Section XI Category B-A, Item Bl.20 welds; specifically, RPV meridional welds 11201-V6-001-W21,11201-V6-001-W22, n

W m

4 e-n e

,.y

,rr wp g

ps-a m-~

m-

U. S. Nuclear Regulatory Commission LCV 1124 Page Three 11201-V6-001-W23, and i1201-V6-001 W24. During inservice inspection activities, each of these welds had exaraination coverage greater than 90% thereby constituting a full Code examination. As a result, the subject relief request is withdrawn.

Existing Relief Request RR 5, which was previously reviewed and approved by the NRC, is revised to address examination limitations for RPV bottom head circumferential weld 11201-V6 001-WO7. This is an ash 1E Section XI Category B A, Jtem No. Bl.21 weld.

Examination coverage for this weld is limited to approximately 29% and therefore does not constitute a full Code examination. This RPV bo' tom head circumferential weld is physically obstructed due to in-core Hux instrumentation tubes. No alternate examination is practical.

Existing Relief Request RR-30, which was previously reviewed and approved by the NRC, has been revised to add Boron injection Tank (BIT) weld il204-V6-001-W05 to of the relief request. Examination coverage limitations were experienced on the bottom side of this AShtE Section XI Category C-C, Item No. C3.10 weld while performing the surface examination. Specifically, the examination was limited to approximately 64% coverage due to the bracket and support con 0guration. As a result, a full-Code examination was unable to be performed due to the limitations experienced. A supplemental visual examination was performed to augment the required surface examination. In addition, a reference to Rc!!cf Request RR-62 was added for welds associated with the Regenerative Heat Exchanger, Excess Letdown IIcat Exchanger, Letdown Heat Exchanger, Letdown Reheat IIcat Exchanger, and the Discharge Pulsation Dampener as identified in Attachment I to Relief Request RR 30. Relief Request RR 62 was previously reviewed and approved by the NRC in its letter dated hiarch 8,1996 to GPC, Attachment I to Relief Request RR-30 was also revised to correct the AShiE Item Number for Discharge Pulsation Dampener weld number 11208-Y4-002-W01 from C1.10 to Cl.20.

New Relief Request RR-63 requests relief from the examination coverage requirements for RPV welds 11201-V6-001-W12,11201 V6-001-W13, and 11201 V6-001-W14 which are RPV upper shelliongitudinal welds. These welds are also AShtE Section XI Category B-A, item No. Bl.12. In each case, examination coverage was limited to less than 90%

due to physical obstructions created by RPV nozzles. Examination coverage was limited to approximately 75%,80%, and 85% for welds ll201-V6-001-W12, ll201-V6-001-W13, snd 11201,V6-001-W14, respectively. As a result, a full-Code examination could not be performed due to the physical obstructions involved. No alternate examinations are practical.

U. S. Nuclear Regulatory Commission LCV ll24 Page Four New Relief Request RR-64 has been added resulting from a concern identified by the Authorized Nuclear Insenice Inspector (ANil) who found that any repairs of piping and components 1 inch nominal pipe size (NPS) and smaller may not have been properly documented, e.g., use of_ Owner's Reports for Repairs and Replacements (ASME Form NIS-2), due to a misunderrtanding of the ASME Section XI Code requirements. This concern was previously identified to the NRC in GPC letter LCV-0932 dated January 8, 1997. Our review indicated that both VEGP units appear to have been in non-compliance since the beginning of commercial operation for any repairs of piping and components l-inch NPS and smaller. It is our position that no compensating increase in the level of safety would be achieved for either VEGP unit were compliance with the Code requirements invoked retroactively for the first ten yeer insenice inspection inten'al for any repairs wnich may have been performed to piping and ec.nponents 1-inch NPS and smaller Relief will also be requested for VEGP Unit 2 (VEGP-2) and will be submitted under separate cover as part of Revision 8 t: VnGP-2 ISI Program document ISI P-014.

Subsequent to the identification of this potential non compliance, plant personnel responsible for repair activities have been instructed that repairs, irrespective of the size of piping and components involved, are to be properly documented (including use of ASME Form NIS-2), the repair / replacement procedure was revised, and a training course was held.

The remaining changes in Revision 8 to the VEGP-1 ISI Program for the First Ten-Year ISI Interval are editorial in naturt. Specifically, these include, but are not limited to, changing references, where appropr.ste, from Georgia Power Company to Southern Nuclear Operating Company due to the transfer of the plant operating licenses earlier in 1997. Incorporation of the editorial changes do not change the intent and scope of the ISI Program for VEGP-1 for the First Ten-Year ISI Interval.

Please refer to the enclosed ISI program revision for details on the changes described above. A summary of the changes resulting from Revision 8 to the VEGP-1 ISI Program is provided in the enclosure and precedes the affected document pages.

The NRC is requested to review and grant approval of the enclosed ISI program revision in temrdarce with the requirements of 10 CFR 50.55a as detailed in the affected relief reqwsts. The subject changes do not affect public health and safety.

We wish to clarify a statement made previously to the NRC in GPC letter LCV-0817 dated July 30,1996. That letter submitted the Owner's Report for Insenice Inspection l

for VEGP-1 Maintenance / Refueling Outage 1R6. The transmittalletter incorrectly noted i

that the remaining valve bolting visual examinations for Safety injection (SI) System

U. S. Nuclear Regulatory Commission LC %1124 Page Five valves 11204U6128 and 11204U6129 were being reported as not having been inspected pursuant to a request from the NRC in its letter dated November 26,1991 to GPC, the former licensee and operator of VEGP and sister company to SNC. The subject GPC letter should have stated that the intcma/ surfaces of these Si valves, rather than the valve bolting, had not been visually examined during the interval. The NRC letter of November 26,1991 required that GPC identify to the NRC any pumps or valves for which an internal examination had not been performed during the inservice inspection interval. This was required by the NRC in lieu of msndatory disassembly of a pump or valve for the sole purpose of performing a vi.;ual examination on its internal surfaces. Based on our compliance with the surface examination requirement cited in the subject NRC letter, no relief request is being submitted, nor considered by SNC to be required, for Si valves 11204U6128 and 11204U6129.

Should there be any questions in this regard, please contact this oflice at your earliest convenience.

Sincerely, C. K. McCo CKM/JAE/jac

Enclosure:

Revision 8 to VEGP-1 First Ten Year Interval ISI Program document ISI P-006 xc: SarthemEus. lear operating Companv Mr. J. B. Beasley, Jr. (w/o enclosure)

Mr. W. L. Burmeister (w/o enclosure)

Mr. M. Sheibani(w/ enclosure)

NORMS (w/ enclosure)

P. S. N2 clear Regulatory Commission Mr. L. A. Reyes, Regional Administrator (w/ enclosure)

Mr. D. Jade, Senior Project Manager, NRR (w/ enclosure)

NRC Senior Resident inspector, Vogtle (w/ enclosure)

,