Special Rept:On 860523,Tech Spec 3.7.5.2 Violated.Caused by Failure to Return Charcoal Filter Deluge Sys to Svc within 14-day Period.Fire Watch Established.Sys Should Be Returned to Svc by 860718
ML20199G479
Person / Time
Site: LaSalle  
Issue date: 06/20/1986
From: Deiderich G
COMMONWEALTH EDISON CO.
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
NUDOCS 8606250251
Download: ML20199G479 (1)


Text

Q#3 N

Commonwealth ECson SP-M n

o

) RurilRouta #1, Box 220 LaSills County Nucitar Station y

h m >

V Marseilles, Illinois 61341 Telephone 815/357-6761 June 20, 1986 gigingo11l$

i

. te '

" ' h

.c x;c James G. Keppler q\\

M,

}g Regional Administrator 2g Region III U.S. Nuclear Regulatory Commission fl 799 Roosevelt Road Glen Ellyn, Illinois 60137

Dear Sir:

This special report is submitted in accordance with LaSalle Unit 1 Operating License NPF-11, Appendix A, and LaSalle Unit 2 Operating License NPF-18, Appendix A, Technical Specifications 3 7.5.2.

On May 23, 1986, the A Control Room Ventilation (VC) Air Supply Charcoal Filter Deluge System exceeded the fourteen (1h) day period allowed by Technical Specification 3.7.5.2 prior to requiring a special report. On May 9, 1986, the A VC Charcoal Filter Deluge System was mechanically isolated from fire protection water to prevent inadvertent vetting of the charcoal filter while a Technical Staf f investigation of the suspected VC charcoal filter solenoid deluge valve failures was being conducted. The investigation was not completed within the fourteen (14) days allowed by Technical Specification 3.7.5.2.

Prior to removing the A VC Charcoal Filter Deluge System from service an hourly fire watch patrol was established in accordance with Action a of Technical Specification 3.7 5.2.

In the event of an actual fire in the A VC Charcoal Filter, the deluge system could be actuated by opening the manual deluge stop valve prior to the normal manual initiation of the deluge system.

The A VC Charcoal Filter Deluge System is expected to be returned to service by July 18, 1986, following completion of the Technical Staff investigation.

A D.

./nG. J. Diederich Station Manager LaSalle County Station GJD/DJR/kg gOf xc:

U.S. NRC Document Control Desk INPO - Records Center File /NRC 0

jyH EO

(

B606250251 860620 PDR ADOCK 05000373 g

PDR