Registry of Radioactive Sealed Sources & Devices,Safety Evaluation of Device for Model SI Series. Certificate:NR-355-D-106-E
ML20199E501
Person / Time
Site:
(NR-355-D-106-E, SSD-97-35)
Issue date: 01/07/1998
From: Steven Baggett, John Lubinski
NRC
To:
Shared Package
ML20199E492 List:
References
SSD, NUDOCS 9802020171
Download: ML20199E501 (3)


Text

,.

4 REGISTRY OF RADIOACTIVE SEALED SOURCES AND DEVICES SAFETY EVALUATION OF DEVICE i-NO.: NR-355-D-106-3 DATE: January 7, 1998 PAGE: 1 OF 3 1

[

-DEVICE TYPE:

Smoke Detector MODEL:

SI Series 4

MANUFACTURER / DISTRIBUTOR:

Hochiki America Corporation 5412 Industrial Drive

-Huntington Beach, CA-92649 l

SEALED SOURCE MODEL DESIGNATION:

NRD Model h-001

}

Amersham Model AMM1001 i

.I9OTOPE:

MAXIMUM ACTIVITY:

j_

Am-241 0.5 pCi (18.5 kBq) 1 LEAK TEST FREOUENCY:

Not-required 1

a 3

PRINCIPAL USE:

(P) Ion Generator, Smoke Detectors i

4 CUSTOM DEVICE:

YES, X

NO I

i' 9802020171 98010e PDR RC SSD pop 4PN

/>

1 REGISTRY OF RADIOACTIVE SEALED SOURCES AND DEVICES

+

t'

-SAFETY EVALUATION OF DEVICE' NO.: NR-355-D-106-E_

DATE: January 7, 1998 PAGE: 2 OF 3

. DEVICE TYPEt -Smoke: Detector i

DESCRIPTION 1 The SI series. smoke-detectors [(models SIH-24F, SIH-24FAP,-and' SIJ-24) are industrial-type detectors connected to and operated j-from a central fire control unit.

They are normally mounted on the ceiling or below-the floor.. These1 detectors are-designed such that;the radioactive material isinot readily accessible to; i

installers or users.

The ion chambers'for the detectors are the same.

The only major physical differences are the design of_the

. outer cover and in the method of attachment of the outer cover; 2

the SIJ-24 detector requires a-special tool to remove the outer cover, whereas the others do'not.

There are a few' minor internal physical differences.

The sensitivity lof the detectors to detect smoke also varies-.

t The method of assembly for the ion chamber is as follows:

j (1) The foil is captured onto the_ inner electrode with_a-retaining disc which'is staked in place by a hydraulically e

contrelled welding machine; (2) The inner electrode-is placed into the insulation plate and the intermediate electrode is then snapped over the inner electrode andlinto the insulation plate.

i One leg of the intermediate electrode snaps into the insulation 4-plate-and the other leg _ protrudes through_the insulation plate and is soldered; and (3) The outer electrode is then placed over.

-this assembly.. The outer electrode has:two-tabs,-180* apart, that are placed through-openings in both the insulation; plate and--

t the printed control board.

These tabs are t. hen' soldered.

Once this is. complete, the source is inaccessible without someone i

removing the printed circuit board from'the detector and l-de-soldering the two legs of the outer electrode.

I d

4 I-U i

4

)

i-1 4

J-REGISTRY OF RADIOACTIVE SEALED SOURCES AND DEVICES SAFETY-EVALUATION OF DEVICE' NO.: NR-355-D-106-E' DATE: January 7, 1998 EAGEA'3 OF 3 DEVICE TYPE:

Smoke Detector DESCRIPTION: (Cont'dI Hochiki distributes these devices under different trade-names, consequently, the; detectors may have different product codes listed on the point' of sale labeling (see table bei wi).

Hochiki Simplex Radionics-SIH-24F 2098-9576 or D281 2098-9550 **

SIH-24FAP NA NA SIJ-24 NA NA Model 2098-9550 is identical mechanically and in sensitivity to detect smoke to Model 2098-9576 with the exception of the epoxy encapsulated printed circuit board used in Model 2098-9550.

D REFERENCES 1 The following-supporting documents for the smoke detector models-SI Series are hereby incorporated by reference and are made a part of this registry document, Hochiki America Corporation's application dated May 2,

1997, o

facsimiles dated June 18, 1997, December 1,

1997, December 4, 1997, and January 6, 1998, and letter dated August 4,-1997,.with enclosures thereto.

ISSUING AGENCY:

U.S. Nuclear Regulatory Commission

,)

Date:

Januarv 7.

1998 Reviewer:

/?

/

Jonn'W. Lubinski Date:

January 7.

1998 Concurrence:

IN,#

Steven L. Baggett