December 22, 1998 Mr. Lew W. Myers l

Vice President - Nuclear, Perry I

Centerior Service Company P.O. Box 97, A200 Perry, OH 44081 l

SUBJECT:

GENERIC LETTER 92-08 CLOSEOUT REPORT - THERMO-LAG RELATED AMPACITY DERATING ISSUES - PERRY NUCLEAR POWER PLANT, UNIT NO.1 (TAC NO. MA3326)

Dear Mr. Myers:

By letters dated April 16,1993 (PY-CEl/NRR-1638L), February 11,1994 (PY-CEl/NRR-1750L),

December 15,1994 (PY-CEl/NRR-1886L), March 22,1995 (PY-CEl/NRR-1926L), June 28, 1995 (PY-CEl/NRR-1966L), October 2,1996 (PY-CEl/NRR-2091L), and January 12,1998 (PY-CEl/NRR-2250L), The Cleveland Electric illuminating Company responded to Generic Letter 92-08, "Thermo-Lag 330-1 Fire Barriers," dated December 17,1992, in regard to Thermo-Lag 330-1 fire barriers installed at the Perry Nuclear Power Plant, Unit No.1 (PNPP). In addition, your letters dated November 20,1995 (PY-CEl/NRR-2003L), June 28,1996 (PY-CEl/NRR-2067L),

and October 28,1996 (PY-CEl/NRR-210SL), addressed Thermo-Lag ampacity derating issues.

The staff has completed its review of your analytical approach for ampacity derating determinations. We conclude that there are no significant safety hazards associated with the application of your ampacity derating methodology for PNPP. The results of our review are documented in the attached Safety Evaluation.

Sincerely, Original signed by:

Douglas V. Pickett, Senior Project Manager Project Directorate 111-2 Division of Reactor Projects lil/lV Office of Nuclear Reactor Regulation Docket No. 50-440 Distribution:

Enclosure:

As stated PUBLIC PDill-2 R/F GGrant, R3 cc: See next page EAdensam BBoger JCalvo y

DOCUMENT NAME:

G:\\PD3-3\\ PERRY \\MA3326 To rsesive a copy of this document, indicate in the box: 'C" = Copy without enclosures *E" = Copy with enclosures "N" = No copy PM PDild-2 C

LA:PDIII-2 f BC:EELB D:PDIII-2 O

0FFICE i

NAME DPid#tt EBarnhillffh-JCalvo*

SRichards $M V DATE 12/2.198 12/o?% 98 12/15/98 12/1 /98 12/ /98 Y

  • See Calvo to Bellamy memo dated 12/15/98 0FFICIAL RECORD COPY bo$$$4o

_.,_ c ---

pg b '--' d

^ g._,, u

.h

-.4

  • J

-_.- ~_.

I J

3 Vice President - Nuclear, Perry Centerior Service Company l

P.O. Box 97, A200 Perry, OH 44081

SUBJECT:

GENERIC LETTER 92-08 CLOSEOUT REPORT - THERMO-LAG RELATED AMPACITY DERATING ISSUES - PERRY NUCLEAR POWER PLANT, UNIT NO.1 (TAC NO. MA3326)

Dear Mr. Myers:

I I

l I

By letters dated April 16,1993 (PY-CEl/NRR-1638L), February 11,1994 (PY-CEl/NRR-1750L),

December 15,1994 (PY-CEl/NRR-1886L), March 22,1995 (PY-CEl/NRR-1926L), June 28, 1995 (PY-CEl/NRR-1966L), October 2,1996 (PY-CEl/NRR-2091L), and January 12,1998 (PY-CEl/NRR-2250L), The Cleveland Electric illuminating Company responded to Generic Letter 92-08, 'Thermo-Lag 330-1 Fire Barriers," dated December 17,1992, in regard to Thermo-Lag 330-1 fire barriers installed at the Perry Nuclear Power Plant, Unit No.1 (PNPP). In addition, your letters dated November 20,1995 (PY-CEl/NRR-2003L), June 28,1996 (PY-CEl/NRR-2067L),

and October 28,1996 (PY-CEl/NRR-2105L), addressed Thermo-Lag ampacity derating issues.

l The staff has completed its n eiew of your analytical approach for ampacity derating determinations. We conclude that there are no significant safety hazards associated with the application of your ampacity derating methodology for PNPP. The results of our review are documented in the attached Safety Evaluation.

Sincerely, Original signed by:

Douglas V. Pickett, Senior Project Manager Project Directorate ill-2 Division of Reactor Projects ill/IV Office of Nuclear Reactor Regulation Docket No. 50-440 Distribution:

Enclosure:

As stated PUBLIC PDill-2 R/F GGrant, R3 cc: See next page EAdensam BBoger JCalvo DOCUMENT NAME:

G:\\PD3-3\\ PERRY \\MA3326 Ts rec 2a a copy of this document. Indicate in the box: "C" = Copy without enclosures *E* = Copy with enclosures *N" = No copy PM PDI.14-2 C

LA:PDIII-2 f BC:EELB f,-

D:PDIII-2 cs 0FFICE I

NAME DPidett EBarnhill &

JCalvo*

SRichards #

DATE 12/2298 12/a?A/98 12/15/98 12/2V/98 12/ /98

  • Sae Calvo to Bellamy memo dated 12/15/98 0FFICIAL RECORD COPY

Y Ct!

t UNITED STATES 7

l j

NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20066 4001

+4 * * * *

  • 4 l

0 December 22, 1998 Mr. Lew W. Myers Vice President - Nuclear, Perry Centerior Service Company P.O. Box 97, A200 Perry, OH 44081

SUBJECT:

GENERIC LETTER 92-08 CLOSEOUT REPORT - THERMO-LAG RELATED AMPACITY DERATING ISSUES - PERRY NUCLEAR POWER PLANT, UNIT NO.1 (TAC NO. MA3326) l

Dear Mr. Myers:

By letters dated April 16,1993 (PY-CEl/NRR-1638L), February 11,1994 (PY-CEl/NRR-1750L),

December 15,1994 (PY-CEl/NRR-1886L), March 22,1995 (PY-CEl/NRR-1926L), June 28, 1995 (PY-CEl/NRR-1966L), October 2,1996 (PY-CEl/NRR-2091L), and January 12,1998 (PY-CEl/NRR-2250L), The Cleveland Electric illuminating Company responded to Generic Letter 92-08, "Thermo-Lag 330-1 Fire Barriers," dated December 17,1992, in regard to Thermo-Lag 330-1 fire barriers installed at the Perry Nuclear Power Plant, Unit No.1 (PNPP). In addition, your letters dated November 20,1995 (PY-CEl/NRR-2003L), June 28,1996 (PY-CEl/NRR-2067L),

and October 28,1996 (PY-CEl/NRR-2105L), addressed Thermo-Lag ampacity derating issues.

The staff has completed its review of your analytical approach for ampacity derating determinations. We conclude that there are no significant safety hazards associated with the application of your ampacity derating methodology for PNPP. The results of our review are documented in the attached Safety Evaluation.

Sincerely,

% ~- u k V PW o

Douglas V. Pickett, Senior Project Manager Project Directorate ill-2 Division of Reactor Projects lil/IV Office of Nuclear Reactor Regulation Docket No. 50-440

Enclosure:

As stated cc: See next page I

_ _ _ _ - ~ _ ~ _ _ _ _

[.

1 7

L. Myers Perry Nuclear Power Plant, Units 1 and 2 -

Centerior Service Company.

James R. Williams l

Mary E. O'Reilly Chief of Staff FirstEnergy - A290 Ohio Emergency Managemsr,t Agency i

10 Center Road 2855 West Dublin Granville Road i

Perry, OH 44081 Columbus, OH 43235-7150 i

i Resident inspector's Office Mayor, Village of Perry i

U.S. Nuclear Regulatory Commission P.O. Box 100 P.O. Box 331 Perry, OH 44081-0100 j

Perry, OH 44081-0331 Radiological Health Program i

Regional Administrator, Region lli Ohio Department of Health U.S. Nuclear Regulatory Commission P.O. Box 118 i

801 Warrenville Road Columbus, OH 43266-0118 2

Lisle, IL 60532-4531 Ohio Environmental Protection Sue Hiatt Agency j

OCRE Interim Representative DERR-Compliance Unit 8275 Munson ATTN: Mr. Zack A. Clayton Mentor, OH 44060 P.O. Box 1049 Columbus, OH 43266-0149 j

Henry L. Hegrat Regulatory Affairs Manager Chairman j

Cleveland Electric illuminating Co.

Perry Township Board of Trustees l

Perry Nuclear Power Plant 3750 Center Road, Box 65 P.O. Box 97, A210 Perry, OH 44081 Perry, OH 44081 State of Ohio i

FirstEnergy Corporation Public Utilities Commission j

Michael Beiting East Broad Street Associate General Counsel Columbus, OH 43266-0573 j