s g,,

,, u J

/

~

So - 466 l

J. C. Glynn, Technical Assistant for Plant Systems, DSS TliRU: Cus C. Lainas, Chief. Containment Systems Branch, DSS CONTAINMENT SYSTEMS BRANCH C0t9fENTS POR TAR 3916 In accordance with Technical Assistance Request 3916, we have reviewed the appli-cant's proposed modifications to the design of the component cooling water system for the Washington Nuclear Plants, Units 1 and 4 as described in Attachment A.

Our only comment is that the applicant should verify that the influent and efflu-eat lines for the component cooling water system are each provided _ with two aut8-matic containment isolation valves, one inside containment and one outsido containment, since the system inside containment is not ANS Safety Class 2.

OF '

~

ww.:

y;,

wa a 'n p arl 11. Brooks E

Containment Systems Branch v

Division of Systems Safety cc:

G. Lainas J. Shapaker J. Kudrick FILE: WPPSS 1-4 i

i DISTRIBUTION:

CSB READING DOCKET FILE NRR READING i

8605290569 760702 PDR ADOCK 05000460 A

PDR 1

B',:

S

.,CSB S

DSS' o"'c = >

Elbirooks :mt.. J,Shapaker

_Qf'T m i n as eu.a.me,

7 e.re h,...j/2/76

}7/M76 7///76 Form AEC. stb (Rev. P 53) ABOE 0240 W u. en sevenament raintime orrices ters.see.ees I

s

. - - -, -.