s g,,
,, u J
/
~
So - 466 l
J. C. Glynn, Technical Assistant for Plant Systems, DSS TliRU: Cus C. Lainas, Chief. Containment Systems Branch, DSS CONTAINMENT SYSTEMS BRANCH C0t9fENTS POR TAR 3916 In accordance with Technical Assistance Request 3916, we have reviewed the appli-cant's proposed modifications to the design of the component cooling water system for the Washington Nuclear Plants, Units 1 and 4 as described in Attachment A.
Our only comment is that the applicant should verify that the influent and efflu-eat lines for the component cooling water system are each provided _ with two aut8-matic containment isolation valves, one inside containment and one outsido containment, since the system inside containment is not ANS Safety Class 2.
OF '
~
ww.:
y;,
wa a 'n p arl 11. Brooks E
Containment Systems Branch v
Division of Systems Safety cc:
G. Lainas J. Shapaker J. Kudrick FILE: WPPSS 1-4 i
i DISTRIBUTION:
CSB READING DOCKET FILE NRR READING i
8605290569 760702 PDR ADOCK 05000460 A
PDR 1
B',:
S
.,CSB S
DSS' o"'c = >
Elbirooks :mt.. J,Shapaker
_Qf'T m i n as eu.a.me,
7 e.re h,...j/2/76
}7/M76 7///76 Form AEC. stb (Rev. P 53) ABOE 0240 W u. en sevenament raintime orrices ters.see.ees I
s
. - - -, -.