Forwards SER Granting Licensee 980513 Request for Approval to Temporarily Repair ASME Code Class 3 Piping at VC Summer Nuclear Station Pursuant to 10CFR50.55a(g)(6)(i)
ML20198F418
Person / Time
Site: Summer 
Issue date: 12/18/1998
From: Berkow H
NRC (Affiliation Not Assigned)
To: Gabe Taylor
SOUTH CAROLINA ELECTRIC & GAS CO.
Shared Package
ML20198F422 List:
References
GL-90-05, GL-90-5, TAC-MA2107, NUDOCS 9812280121
Download: ML20198F418 (3)


Text

_ _.

DecemberL18,1998

' Mr. Gary J. Taylor Vics President, Nucl:ar Op: rations South Carolina Electric & Gas Company i

l Virgil C. Summer Nuclear Station Post Office Box 88

Jenkinsville, South Carolina 29065

SUBJECT:

APPROVAL TO USE GENERIC LETTER 90-05 GUIDANCE TO TEMPORARILY REPAIR ASME CLASS 3 SERVICE WATER SYSTEM PIPING AT V. C.

SUMMER NUCLEAR STATION (TAC NO. MA2107)

Dear Mr. Taylor:

Your May 13,1998, letter submitted a relief request seeking NRC approval to temporarily repair American Society of Mechanical Engineers (ASME) Code Class 3 piping. The piping is 4-inch carbon steel, moderate-energy, service water (SW) system pipe.

We evaluated your request in accordance with Generic Letter (GL) 90-05 " Guidance for Performing Temporary Non-Code Repair of ASME C'>de Class 1,2, and 3 Piping." We determined that your structural integrity and operability assessments are acceptable, and your augmented inspections are satisfactory. We find that making an immediate Code repair is j

impractical, since the Class 3 Code repair would require isolating the SW system for longer than the 72-hour Technical Specification (TS) Limiting Condition for Operation (LCO) 3.7.4 action statement allowance. Exceeding the SW system 72-hour LCO action statement requires a plant shutdown. Therefore, in accordance with 10 CFR 50.55a(g)(6)(i), we find that the Code requirements _ are impractical, grant the requested relief, and impose the alternatives, until the next refueling outage (RFO 11) is complete. The relief granted is authorized by law and will not endanger life or property or the common defense and security and is otherwise in the public interest, giving due consideration to the burden upon the licensee if the requirements were imposed on the facility. You indicated that you will perform a Code replacement of the defective i

- piping during the next scheduled outaga exceeding 30 days, or during RFO 11, currently scheduled for the Spring of 1999. The enclosed Safety Evaluation contains our evaluation of

= your relief request.

Sincerely, Original signed by:

Herbert N. Berkow, Director Project Directorate 11-2 9812290121 981218 Division of Reactor Projects - l/II f

^* O

[

Office of Nuclear Reactor Regulation q

Docket No. ; 0-395

Enclosure:

Safety Evaluation ypr3ptqF*f?:'~"00%-

NMP $ ' O

+"

.cc w/ encl: See next page.

' Distribution:

I!

Docket File PD ll-2 RF MTschiltz GHill (2)

ACRS f

PUBLIC.

JZwolinski LPlis'co, Ril OGC GGeorgiev F!LENAME - G:\\ SUMMER \\SUMA2107.REL d

f l

OFFICE PM:PDll-2 LA:PDil 2 EGCB*

~OGC*

D:PDil-NAME MPadovan DunningM GBacchi MYoung HBerkow DATE 12/ /98 12//7/98 12/3/98 12/,10/98' W /1 98 COPY Yes/No hJo' MNo Yestl$

Yes 23UN8 OFFICIACMECORD COPV *See previous cBiicurrence V

~.

f>D CE00%o%

UNITED STATES pe 4

j j

NUCLEAR REGULATORY COMMISSION i

WASHINGTON, D.C. 2066Mm01

\\,,+..../

December 18, 1998 Mr. Gary J. Taylor Vice President, Nuclear Operations South Carolina Electric & Gas Company Virgil C. Summer Nuclear Station Post Office Box 88 Jenkinsville, South Carolina 29065

SUBJECT:

APPROVAL TO USE GENERIC LETTER 90-05 GUIDANCE TO TEMPORARILY REPAIR ASME CLASS 3 SERVICE WATER SYSTEM PIPING AT V. C.

4 SUMMER NUCLEAR STATION (TAC NO. MA2107)

Dear Mr. Taylor:

Your May 13,1998, letter submitted a relief request seeking NRC approval to temporarily repair American Society of Mechanical Engineers (ASME) Code Class 3 piping. The piping is 4-inch carbon steel, moderate-energy, service water (SW) system pipe.

We evaluated your request in accordance with Generic Letter (GL) 90-05 " Guidance for Performing Temporary Non-Code Repair of ASME Code Cl ass 1,2, and 3 Piping." We determined that your structural integrity and operability assessments are acceptable, and your augmented inspections are satisfactory. We find that making an immediate Code repair is impractical, since the Class 3 Code repai.r would require isolating the SW system for longer than the 72-hour Technical Specification (TS) Limiting Condition for Operation (LCO) 3.7.4 action statement allowance. Exceeding the SW system 72-hour LCO action statement requires a plant shutdown. Therefore, in accordance with 10 CFR 50.55a(g)(6)(i), we find that the Code requirements are impractical, grant the requested relief, and impose the alternatives, until the next refueling outage (RFO 11) is complete. The relief granted is authorized by law and will not endanger life or property or the common defense and security and is otherwise in the public interest, giving due consideration to the burden upon the licensee if the requirements were imposed on the facility. You indicated that you will perform a Code replacement of the defective l

piping dunng the next scheduled outage exceeding 30 days, or during RFO 11, currently l

scheduled for the Spring of 1999. The enclosed Safety Evaluation contains our evaluation of your relief request.

Sincerely, dEEMD l

Herbert N. Berkow. Director Project Directorate 11-2 Division of Reactor Projects - I/11 Office of Nuclear Reactor Regulation Docket No. 50-395

Enclosure:

Safety Evaluation cc w/ encl: See next page 4

Mr. Gary J. Tay'or VIRGIL C. SUMMER NUCLEAR STATION South Carolina Electric & Gas Company cc:

Mr. R. J. White J. B. Knotts, Jr., Esquire Nuclear Coordinator Winston & Strawn Law Firm S.C. Public Service Authority

.1400 L Street, N.W.

c/o Virgil C. Summer Nuclear Station Washington, D.C. 20005-3502

.. Post Office Box 88, Mail Code 802 Jenkinsville, South Carolina 20065 Resident inspector / Summer NPS c/o U.S. Nuclear Regulatory Commission Route 1, Box 64 Jenkinsville, South Carolina 29065 Regional Administrator, Region ll U.S. Nuclear Regulatory Commission Atlanta Federal Center 61 Forsyth Street, SW, Suite 23T85 -

Atlanta, Georgia 30303 Chairman, Fairfield County Council-Drawer 60 Winnsboro, South Carolina 29180 Mr. Virgil R. Autry, Director l

. Division of Radioactive Waste Management Bureau of Land & Waste Management Department of Health & Environmental Control 2600 Bull S"cet Columbia, South Carolina 29201

- Mr. Robert M. Fowlkes, Manager Operations

. South Carolina Electric & Gas Company Virgil C. Summer Nuclear Station, Mail Code 303 Post Office Box 88

'Jenkinsville, South Carolina 29065 Ms. April R. Rice, Manager Nuclear Licensing & Operating Experience South Carolina Electric & Gas Company Virgil C. Summer Nuclear Station, Mail Code 830

. Post Office Box 88 Jenkinsville, South Carolina 29065

.W

--r,-

g

-aw-

-- -i w-mgw y.-zg y