Text
{{#Wiki_filter:_. j JUN 2 61991 Docket: 50-285 License: DPR-40 Omaha Public Power District ATTN: W. G. Gates, Division Manager Nuclear Operations 444 South 16th Street Mall Mail Stop 8E/EP4 Omaha, NE 68102-2247 Gentlemen: This letter forwards the results of the Generic Fundamentals Examination Section (GFES) of the written operator licensing examination that was administered on June 5, 1991, to nominated employees of your facility. We are forwarding the following items: o the examination, including answer key, c the results for your nominated employees, and copies of the individual answer sheets completed by your nominated o employees We request that your training department forward the individual answer sheets and results to the appropriate indivicuals. It should be notec that the examination was administered in two forrs, which were icentical except for the sequence of ouestions. We would 1 4 e to call to your attention the exemplary performance on this examir.ation by three of your nominated empicyees. In accordance with the CorTaission's Regulations,10 CFR Part 2.790, a copy cf this letter and the examiration and answer key will be placed in the NRC's Public Document Room (PDR). The incividual results and answer sheets are exempt from public disclosure cnd therefore will not te placed in the PDR. Questions concerning this examination should be directed to Mr. Paul Doyle at (301)492-1058. Sincerely, O t.cina1 0 e r M F V: Thenus P. Grian (j Samuel J. Collins, Directcr Divisicn of Reactor Projects Encicsures: As stated cc: next page k \\ rp 9107030138 910626 PDR ADOCK 0500 S V
bec to DMB (IE42) bec distribution by RIV: R. D. Martin MIS System J. L. Pellet E. M. Himes NRR Project Panager (MS: 13-D-18) DRP SC RIV file L. Miller, TTC DRS (J. Pellet rds file) P
i Omaha Public Power District -2 JUN 2 61991 cc: Omaha Public Power District ATTN: J. K. Gasper, Manager - Training P.O. Box 399 Fort Calhoun, NE 68023 l l l l l l l DRS:CLS: lay-ORS:0LS:SC DRSk'; Dir DRP;DivDir r EMHimespf CLPellet / LJCallan /cy-SJCollirs 9 / 6/d4/91 6/24/9k 6/Ji/S1 6{$/91 l
-( 4
- e UNITED STATES NUCLEAR REGULATORY COMMISSION PRESSURIZED WATER REACTOR GENERIC FUNDAMENTALS EXAMINATION JUNE 1991 - FORM A Please Print:
Name: Facility: ID Number: Start Time: Stop Time: 1 INSTRUCTIONS TO CANDIDATE Use the answer sheet provided. Each question has equal point f value. A score of at least 80% is required to pass this portion of the written licensing examination. All examination papers will be collected 2.5 hours a"ter the examination starts. SECTION QUESTIONS % OF TOTAL SCORE COMPONENTS 1 - 44 REACTOR THEORY 45 - 72 THERMODYNAMICS 73 '00 TOTALS 100 All work done on this examination is my own. I have neither given nor received aid. Candidate's Signature
ANSWER KEY FOR JUNE 1941 PWR GFE (Rev. 5/24) FORM FORM FORM A B A B A B 1. 57. A 35. 91. B 69. 25. B 2. 58. D 36. 92. D 70. 26. A 3. 59. B 37. 93. D 71. 27. C 4. 60. B 38. 94. D 72. 28. C 5. 61. B 39. 95. A 73. 29. B 6. 62. C 40. 96. B 74. 30. C 7. 63. A 41. 97. A 75. 31. C 8. 64. B 42. 98. C 76. 32. D 9. 65. 'A 43. 99. A 77. 33. C 10. 66. D 44. 100. D 78. 34. B 11. 67. D 45. 1. C 79. 35. C 12. 68. C 46. 2. B 80. 36. C 13. 69. B 47, 3. B 81. 37. A 14. 70. C 48. 4. C 82. 38. C 15. 71. D 49. 5. A 83. 39. D 16. 72. A 50. 6. B 84. 40. D 17. 73. A 51. 7. C 85. 41. B 18. 74. D 52. 8. D 86. 42. D 19. 75. A 53. 9. D 87. 43. D 20. 76. A 54. 10. D 88. 44. A 21. 77. C 55. 11. B 89. 45. C 22. 78. A 56. 12. C 90. 46. C 23. 79. D 57. 13. A 91. 47. C 24. 80. B 58. 14. B 92. 48. A 25. 81. D 59. 15. B 93. 49. A 26. 82. C 60. 16. C 94. 50. C 27. 83. B 61. 17. A 95. 51. D 28. 84. D 62. 18. D 96. 52. B 29. 85. D 63. 19. A 97. 53. B 30. 86. C 64. 20. B 98. 54. D 31. 87. C 65. 21. D 99. 55. D 32. 88. A 66. 22. B 100. 56. A 33. 89. C 67. 23. B 34. 90. C 68. 24. D
e S. l UNITED STATES NUCLEAR REGULATORY COMMISSION PRESSURIZED WATER REACTOR GENERIC FUNDAMENTALS 1;XAMINATION JUNE 1991 - FORM A Please Print: Name: Facility: ID Number: Start Time: Stop Time: INSTRUCTIONS TO CANDIDATE Use the answer sheet provided. Each question has equal point value A score of at least 80% is required to pass this portion of the written licensing examination. All examination papers will be collected 2.5 hours after the examination starts. SECTION QUESTIONS % OF TOTAL SCORE COMPONENTS 1 - 44 REACTOR THEORY 45 - 72 THERMODYNAMICS 73 100 TOTALS 100 All work done on this examination is my own. I have neither given nor received aid. Candidate s Signature
l
- l RULES AND Gl'IDELINES l'OR Tile GENERIC FUNDAMENTALS EXAMINATION During the administration of this examination the following rules apply:
(1) Print your name in the blank provided on the cover sheet of the examination. (2) Fill in the name of your facility. (3) Fill in the ID-N'imber you were given at legistration. (4) Fill in your start and stop times at the appropriate time. (5) Three handouts are provided for your use during the examina-tion, an Equations and Conversions sheet, instructionc for filling out the answer sheet, and Steam Tabic booklets. t (6) Use only the answer sheet provided. Credit will only be given for ansWcrs properly marked on this sheet. Follow the instructions for filling out the answer sheet. (7) Scrap paper will be provided for calculations. (8) Any questions about an item on the examination should be directed to the examiner only. (9) Cheating on the examination will result in the automatic forfeiture of this examination. Cheating could also result in severe penalties. (10) Restroom trips are limited. Only ONE examince may leave the room at a time. In order to avoid the appearance or possibility of cheating, avoid all contact with anyone outside of the examination room. (11) After you have completed the examinatima, sign the statement on the cover sheet indicating that the work is your own and you have not received or been given any assistance in completing the examination. (12) Turn in your examination materials, answer sheet on top, followed by the exam booklet, then examination aids - stear. table booklets, handouts and scrap paper used during the examination. (13) After turning in your examination materials, leave the examination area, as defined by the examiner. If after leaving you are found in the examination area while the examination is in progress, your examination may be forfeited. l i l
l 4 CENERIC FUNDAMETALS EXAMINATION SECTION EQUATIONS AND C0fA'ERSIONS llANDOUT Sl!EET K'!ATIONS me aT Cycle Efficiency Net o rk ( ou t ) Q p Energy (in) 0
- n ah SCR S/(1. K,ff)
Q UA AT cry (1. K,f )y CR2 (1 ' Keff)2 SUR - 26.06/r M 1/(1 K,ff) CR /CR 1 0 26.06 (A,ff c) (1.Kdf}0 (3 - p) (1 K,ff)y SUR(t) P P 10 SDM (1 - Kef.,)/Ke f., o P, e(t/r) P Pwr V m f (1 /p) + [(S - p)/Ag] r 1 /(p - p) p r (K,ff 1)/K,ff 1 1 x 10'5 seconds AK,ff/Y, ff A,gg - 0.1 seconds'1 s 1 2 --2)
- 9IZ e(P, - P ) + y (7 i) 0
~V -Z g e i e CONVERSIONS 10 1 Curie 3.7 x 10 dps 1 kg 2.21 lbm 3 6 I hp 2.54 x 10 BTU /hr 1 Mw 3.41 x 10 BTU /hr 1 BTU 778 ft lbf 'F 9/5 'C + 32
- C 5/9 (*F - 32)
I
O ATf.OSPHERE f,/, / / / / / Ae + TANK DIFFERENTIAL PRESSURE LEVEL INDICATORS l 1 l FIGURE 1
e FIL COfit ECTIO J c-{ ~ PRESSURE L 461-DETECTOR DETECTOR IJO.1 NO 2 FIL CotJi ECTIO J gi ?S " if " e u p DETECTOR DETECTOR NO. 3 NO. 4 TANK DIFFERENTIAL PRESSURE LEVEL DETECTORS FIGURE 2
1 f i i i l l l 1 1 I l l I I l i I I l I I I l l l l l I I I l I l I l l I I I I i l i I w I i l l l l l O I l l l I I l l l I 'j l l l l l g i I I l u I I l l cn l I l l l h l w - PARTICLE I l l l l I l l l 1 I I l l l $ - PARTICLE o l l l l 03 l I I I I e l 3 l l l I I l l l l l 1 l ll l 111 l IV l V l VI APPLIED VOLTAGE TO THE y GAS FILLED DETECTOR GAS-FILLED DETECTOR CHARACTERISTIC CURVE FIGURE 3
l/P cot 1VERTER FROM FROM P R O T E C TI O rl S/G +- LOGIC LEVEL cot 1 TROL-__ VALVE POSITIOt1ER l y p S l W --I l- ..........................7 5 ~ ATMOSPHERE < FC n AIR SUPPLY FROM [ TO v STEAM FEED g AIR SUPPLY PUMPS FEED GEllERATOR cot 1 TROL AIR
- n'""*"*
COf4 TROL VALVE LOGIC SIGilAL ---- PNEUM ATIC CONTROL SYSTEM - PWR FIGURE 4
h TEf.1PERATURE LUBE TRAtlSr.11TTER OIL TEF.1PERATURE COilTROLLER i l i I I I I COOLirJG C O O LillG / HEAT EXCHAt1GER WATER WATER N TEr.1PERATURE cot 1 TROL VALVE A LUBE OIL l LUBE OIL TEMPERATURE COf HitOL SYST Er.1 FIGURE 5
4 4 TEM 0EAATurt I LUE'E TR AN5f.ilTT E R OIL TEMPER ATUnE \\ CONTROLLER ~~' ~ ~ ~ ~ ~ / l I l l i T i COOL!NG _ N HEAT EXCHANGER WATER yN ( COOLtr4G TEMPERATURE WATER CONTnol V ALVE h LUBE TUMP Cil LUBE OIL TEMPERATURE COf1 TROL SYSTEM , POINT A l POINT E t 9 CURVE 1 I / POINT B FRESSURE .y I CURVE: I l I POINT D L' POINT C _U FLOW I l CEf4TRIFUGAl PUMP OPERATitJG CURVE t t l FiaVRE 6 l ,, _ _ _ _.. _ - _ = _
ik COOLING WATER r LUBE OIL a l l LUBE OIL HEAT EXCHANGER FIGURE 7
+ 125 VDC ___ #1 cot 4 TACT CLOSED BY > ltJITIATitJG 33 COtJDITIOtl
- 2 cot 4 TACT
- 3 COf4 TACT p___
1 e i i 1 1 8 1 I I f 1 1 L._________ K3 RELAY (ENERGlZE TO OPEN VALVE. 4 DEENERGlZE TO CLOSE VALVE.) -125 VDC TYPICAL VALVE CONTROL CIRCUIT FIGURE 8
I CLAD e;J m w. l I FUEL PELLET l w,s m e lj i l l n w ,s T I I COOLANT COOLANT l FLOW u_i s FLOW i J i FUEL ROD AND COOLANT FLOW CHANNEL l l FIGURE 9
l. I i l USNRC GENERIC FUNDAMENTALS EXAMINATION PWR - FORM A I QUESTION: 1 i i The difference between the setpoint pressure at which a safety valve opens and the pressure at which it closes is called: i l A. blowdown. B. accumulation. l } C. setpoint tolerance, i D. setpoint deviation. l l QUESTION: 2 t In comparison to a globe valve, a gate valve has a L pressure drop when fully open and is the choice for l throttling. A. higher; better l l B. lower; better lL C. higher; poorer D. lower; poorer QUESTION: 3 When manually positioning a motor-operated valve, why must care be taken to avoid using excessive valve seating /backseating force? A. Limit switch settings may change. B. The valve may not operate on demand. C. The motor may.not re-engage. D. Torque switch settings may change. 1
USNRC GE!!ERIC FUI1 DAME!!TALS EXAMI!JATION PWR - FORM A QUESTION: 4 A stop check valve is a modified check valve that: A. cannot be shut remotely. B. can be used to prevent flow in both directions. C. can be opened manually to allow flow in both directions. D. contains both a gate valve disk and a check valve disk. QUESTION: 5 Density compensation is used in flow instruments to change to A. mass flow rate; volumetric flow rate B. Volumetric flow rate; mass flow rate C. mass flow rate; differential pressure D. differential pressure; volumetric flow rate QUESTION: 6 Which one of the following will cause indicated volumetric flow rate to be LOWER than actual volumetric flow rate using a differential pressure flow detector and a calibrated orifice? x A. Debris becomes lodged in the orifice. B. A leak develops in the low pressure sensing line. C. The orifice erodes over time. D. System pressure decreases. 2
USliRC GE!1ERIC FUf1 DAME!JTALS EXAMIllATIO!J PWR - FORM A QUESTIO!J: 7 The flow rate of a fluid passing through a venturi can be determined by measuring the: A. differential pressure of the fluid as it passes through the venturi. D. linear displacement of a metering plug installed in the throat of the venturi. C. change in the velocity of the fluid as it passes through the venturi. D. rotation of a paddle wheel type device installed in the throat of the venturi. QUESTIOll: 8 Refer to the drawing of two tank differential pressure level indicators (see figure 1). Two differential pressure (D/P) levol indicators are installed on a large water storage tank. Indicator I was calibrated at 100 degrees F water teraperature and indicator 2 was calibrated at 200 degrees F water temperature. Assuming both are on scale, which indicator will indicate the higher level? A. Indicator 1 at all water temperatures B. Indicator 2 at all water temperatures C. Indicator 1 below 150 degrees F, indicator 2 above 150 degrees F D. Indicator 2 below 150 degrees F, indicator 1 above 150 degrees F 3
USNRC GENERIC FUllDAMENTALS EXAMINATION PUR - FORM A QUESTION: 9 Refer to the drawing of four tank differential pressure level detectors (see figure 2). The tanks are identical with equal water levels and both are pressurized to 20 psig. All detectors were calibrated at the current water temperature and 70 degrees F external (ambient) temperature. Which detectors will provide the MOST INACCURATE level indication following an increase in external (ambient) temperature from 70 degrees F to 100 degrees F? (Assume water temperature and external pressure do not change.) A. 1 and 3 B. 2 and 4 C. 1 and 4 D. 2 and 3 QUESTION: 10 If the pressure sensed by a bourdon tube increases, the curvature of the detector will because of the greatest force being applied to the curve of the detector. A.- increase; inner B. -decrease; inner C. increase; outer D. decrease; outer 4 1 i 1 l l l
USNRC GENERIC FUN DAMEfJTALS EXAM 1!JATION 1 %'R - FORM A QUESTION: 11 A bellows pressure transmitter with its low-pressure side vented to containment atmosphere is being used to ceasure Reactor Coolant System (RCS) pressure. A decrease in the associated pressure indication could be caused by either a containment pressure or a RCS pressure A. decrease; decrease B. increase; increase C. decrease; increase D. increase; decrease QUESTION: 12 A resistance temperature detector (RTD) operates on the principle that the change in metal resistance is proportional to the change in A. inversely; metal temperature B. inversely; metal temperature squared C. directly; metal temperature D. directly; metal temperature squared 5
I USNRC GENERIC FUNDAME!1TALS EXAMINATION PWR - FORM A QUESTION: 13 The plant has experienced a loss of coolant accident with degraded safety injection flow. The reactor coolant pumps have been manually tripped and the resulting phase separation has caused partial core uncovery (approximately 20 percent). Which one of the following describes excore source /startup range neutron level indication as core uncovery increases from 20 percent to 100 percent of the core? (Assume neutron detectors are located adjacent to the bottom portion of the core.) A. Increases continuously B. Increases, then decreases l j C. Decreases continuously D. Decreases, then increases l QUESTION: 14 Refer to the drawing of a gas-filled detector characteristic curve (see figure 3). Which of the following statements describes how a gas-filled radiation detector, operating in the " proportional" reglen, functions? A. Essentially all of the ions caused by incident radiation are collected. Ions collected from secondary lonizations are independent of applied voltage. B. Essentially none of the ions caused by incident radiation ere collected. Ions collected from secondary ionizations vary directly with applied voltage. C. Essentially all of the ions caused by incident radiation are collected. Ions collected from secondary ionizations vary directly with applied voltage. D. Essentially none of the ions caused by incident are collected. Ions collected from secondary ionizations are independent of applied voltage. i l 6
l US!4RC GE!1ERIC FU!JDAME!JTALS EXAMI!2AT1011 PWR - FORM A QUESTIOll: 15 The difference between the setpoint and the measured parameter in an automatic flow controller is called: A. gain. B. bias. C. feedback. D. error. QUESTIOll: 16 Refer to the drawing of a pneumatic control system (see figure 4). Given that an increasing control signal from the Steam Generator Level Control System causes the I/P converter to modulate open, if the control signal is manually increased, how will the pneumatic control system affect steam generator level? A. Level will increase because the valve positioner will open more. B. Level will decrease because the valve positioner will open more. C. Level will increase because the valve positioner will close more. D. Level will decrease because the valve positioner will close more. 7
USNRC GENERIC FUNDAMLlJTALS EXAMI!J ATIO!J PWR - PORM A QUESTION: 17 Refer to the drawing of a lube oil temperature control system (see figure 5). If the temperature transmitter fails HIGH (high temperature output signal), the temperature controller will the temperature control valve, causing the actual heat exchanger lube oil outlet temperature to A. open; decrease B. open; increase C. close; decrease D. close; increare QUESTION: 18 What may be damaged if an operator attempts to manually disengage the motor on a motor-operated valve while the motor is operating? A. Limit switches B. Valve seat C. Torque switches D. Clutch l 8 l l C
US!JRC GE!Ji: HIC 1 U!! DAME!JTA1.S 1.:X AM I !J A'l I U!1 MlH - l'ORM A QUESTIO!J : 19 Which one of the following describes the response of a direct acting proportional-integral controller, operating in automatic, to an increase in the controlled parameter above the controller setpoint? A. The controller will develop an output signal that continues to increase until the controlled parameter equals the controller setpoint, at which time the output signal becomes constant. B. The controller will develop an output signal that wil1 remain directly proportional to the difforence between the controlled parameter and the controller setpoint. C. The controller will develop an output signal that continues to increase unti.1 the controlled parameter equals the controller setpoint, at which time the output signal becomes zero. D. The controller will develop an output signal that will remain directly proportional to the rate of change of the controlled parameter. QUESTIO!1: 20 Which of the following changes in pump operating parameters wil1 DIRECTLY lead to pump cavitation in a centrifugal pump that is operating at rated conditions in an open system? A. Steadily increasing pump inlet temperature B. Steadily decreasing pump speed C. Steadily increasing pump suction pressure D. Steadily decreasing pump recirculation flow 9
USNRC GENERIC FUNDAMENTALS EXAMI!JATION PWR - FORM A QUESTION: 21 When a centrifugal pump is operating at shutoff head, it is pumping at capacity and discharge head. A. maximum; minimum B. maximum; maximum C. minimum; maximum D. minimum; minimum QUESTION: 22 A centrifugal pump is circulating water at 100 degrees F in a cooling water system. After several hours the water temperature has increased to 150 degrees F. Assuming system flow rate (gpm) is constant, pump motor amps will have because A. decreased; water density has decreased B. increased; water density has decreased C. decreased; pump shaft speed has increased D. increased; pump shaft speed has increased 10
_ = - l USNRC GENERIC FUNDAMENTALS EXAMINATION PWR - FORM A QUESTION: 23 Refer to the drawing of a lube oil temperature control system and the associated centrifugal pump operating curve (see figure 6). If the pump is operating at point B on the operating curve, how will the operating point change if the temperature control valve modulates further open? A. Operating point B will be located on curve 1 closer to point D. B. Operating point B will be located on curve 2 closer to point A. C. Operating point B will be located on curve 1 closer to point E.- D. Operating point B will be located on curve 2 closer to point C. i QUESTION: 24 Which one of the following specifies the proper pump discharge l valve position and the basis for that position when starting a large centrifugal pump? l A. Discharge valve fully open to ensure proper axial alignment j of pump impeller. I B. Discharge valve throttled to reduce motor power requirements C. Discharge valve fully open to ensure adequate pump recirculation flow D. Discharge valve throttled to lessen the possibility of air binding the pump l l l l \\ 11 i
_ - - _ - _ ~. _. _ -.... USNRC GENERIC FUNDAMENTALS EXAMINATION PWR - FORM A QUESTION: 25 If the speed of a positive displacement pump is increased, the available net positive suction head (NPSH) will and the probability of cavitation will A. increase; increase D. decrease; decrease C. increase; decrease D. decrease; increase QUESTION: 26 Why are positive displacement and centrifugal pumps typically NOT operated in parallel? A. At high system flow rates the positive displacement pump may not receive adequate net positive suction head. B. At low discharge pressures the-positive displacement pump r may overheat from a lack of recirculation flow. C. At-high discharge pressures the positive displacement pump may prevent flow through the centrifugal pump. D. Cyclic stresses may be placed on each pump due to uneven or oscillating pump flow rates. l l l l 12 .-. ~.
4 I US11RC GEllERIC FUf1DAMEf1TALS EXAMI!1ATIO!J PWR - FORM A QUESTIO11: 27 An operator can differentiate a locked reactor coolant pump (RCP) rotor from a sheared RCP rotor 30 seconds after the event by observing: (Assume no operator action.) A. loop flow indications. B. RCP ammeter indications. C. loop differential temperature indications. D. reactor trip status. QUESTIO!J: 28-If the generator bearings on a motor-generator begin to fall from overheating, then: A. generator current will increase. B. generator windings will overheat. C. motor current will decrease. D. motor windings will overheat. l 13
USNRC GENERIC FUNDAMENTALS EXAMINATION PWR - FORM A QUESTION: 29 A main generator is operating on the grid with the following indications: - 100 MWe - 0 MVAR - 2,900 amps - 20,000 volts If main generator excitation is reduced, amps will and MWe will A. decrease; decrease B. increase; decrease C. decrease; remain the same D. increase; remain the same QUESTION: 30 A motor-driven centrifugal pump is operating at a low flow condition in an open system. The throttled discharge valve is then fully opened to increase system flow rate. Which one of the following will increase? A. Pump discharge pressure B. Available net positive suction head C. Motor amps D. Pump speed 14
USNRC GENERIC FUNDAMENTALS FXAMINATION PWR - FORM A QUESTION: 31 The starting current in an AC induction motor is significantly higher than the full-load running current because: A. starting torque is lower than running torque. B. starting torque is higher than running torque. C. rotor current during start is too low to generate sufficient counter electromotive-force (CEMF) in the stator. D. rotor current during start is too high to generate sufficient counter electromotive force (CEMF) in the stator. QUESTION: .32 . Refer to the drawing of a lube oil heat exchanger (see figure 7). Decreasing the oil flow rate through the heat exchanger will cause the oil outlet temperature to and the cooling water outlet temperature to (Assume cooling water flow rate remains the same.) A. decrease;-decrease B. increase; decrease C. decrease; increase D. increase; increase 15
USNRC GENERIC FUNDAMENTALS EXAMINATION PWR - FORM A QUESTION: 33 Tube fouling in a heat exchanger causes heat transfer rate to decrease by: A. reducing fluid velocity on the shell side of the excharger and reducing heat transfer area. B. increasing flow rate through the tube ride of the exchanger and increasing heat transfer area. C. reducing the overall heat transfer coefficient and reducing tube side flow. D. increasing the overall heat transfer coefficient and increasing shell side flow. QUESTION: 34 During normal plant operation at power, a crack in the shel? of the main condenser, that results in a decreased condenser vacuum, will cause cooling water outlet temperature to and hotwell temperature to A. increase; decrease B. decrease; decrease C. increase; increase D. decrease; increase 16 -.~ -.. -,. = - _ _. -. - -. -. -..
I USNRC GENERIC FUNDAMENTALS EXAMINATION PWR - FORM A QUESTION: 35 How does dcmineralizer dif ferential pressure indicate the condition of the demineralizer resin bed? j A. Low differential pressure indicates flow blockage in the domineralizer. B. Eigh differential pressure indicates flow blockage in the domineral izer C. Low differential pressure indicates that the domineralizer realn bed in exhausted. D. High diff6rentia] pressure indicates that the domineralizer resin bed is exhausted. l QUESTION: 36 Prior to a scheduled plant shutdown, the Reactor Coolant System 1 was chemically shocked to induce a crud burst. What effect will this have on the letdown purification domineralizers? A. Decreased operating time before the resin is exhausted l B. Increased flow-rate through the demineralizers C. Decreased domineralizer outlet conductivity D. Increased pressure drop across the demineralizers i 17 . ~.
l l i USNRC GENERIC FUND 7JENTALS EXAMINATION PWR - FORM is QUESTION: 37 The temperature of the water passing through a domineralizer must be controlled because EXCESSIVELY HOT water will: A. increase the ion exchange rate for hydronium ions, thereby changing effluent pH. B. degrade the corrosion inhibitor applied to the inner wa' n' the demineralizer. C. result in excessive demineralizer retention element thermal expansion, thereby releasing resin. D. reduce the affinity of the demineralizer resin for ion exchange. QUESTION: 38 Which of the following results from a loss of circuit breaker control power to a circuit breaker supplying a motor? A. Motor ammeter indication would be zero regardless of actual breaker position. B. Breaker position would remotely indicate closed regardless of actual position. C. Breaker would trip open due to the actuation of its protective trip device. D. Close spring charging motor would not charge the spring following local tripping of the breaker. A 18
i' USNRC GENERIC FUNDAMENTALS EXAMINATION PWR - FORM A QUESTION: 39 How is circuit breaker operation affected when the circuit breaker control power transfer switch is placed in the LOCAL position? A. Control power will be available to provide protective trips and the circuit breakar can be closed by pushing the close pushbutton on or inside the circuit breaker enclosure. B. Control power will be removed from the close circuits but control power will still be available for automatic circuit breaker trips. C. Control power will be removed from both the open and close circuits and breaker operation is restricted to local ranual operation only. D. Control power will be removed from both the open and close circuits and the circuit breaker can be closed by pushing the close pushbutton on or inside the circuit breaker enclosure. QUESTION: 40 Refer to the drawing of a typical valve control circuit (see figure 8). The purpose of the K3 relay is to: A. hold the valve open after one or both of the initiating conditions have cleared, even if the reset pushbutton (S1) is depressed. B. hold the valve open even if one or both of the initiating conditions have cleared. C. close the valve as soon as either initiating condition has cleared. D, close the valve as soon as both initiating conditions have cleared. i l 19
USNRC GENERIC FUND 101ENT/sLS EXAMINATION PWR - FORM A QUESTION: 41 During paralleling operations of the main generator to the grid, closing the generator output breaker with the frequency of the generator at 60.1 hertz and the grid frequency at 60.0 hertz Will: A. cause the generator to immediately increase load. B. trip open the generator breaker on reverse power. C. cause the generator voltage to increase. D. cause the generator current to decrease. QUESTION: 42 When a typical 4160 volt breaker is racked to the TEST position control power is the breaker and the breaker is the load. A. removed from; isolated from B. removed from; connected to i C. available to; isolated from D. available to; connected to QUESTION: 43 The function of high voltage electrical disconnects is to provide electrical isolation of equipment during conditions. A. manual; no-load B. manual; overload C. automatic; no-load 't D. automatic; overload t 20 4 l
USNRC GENERIC PUNDAMENTALS EXAMINATION PWR - PORM A QUESTION: 44 The following remote indications are observed for a 480 VAC load supply breaker. (The breaker is normally open.) Red indicating light is on. Green indicating light is off. Load voltage indicates 0 volts. Line voltage indicates 480 volts. What is the condition of the breaker? A. Open and racked in B. Closed and racked in C. Open and racked to " test" position D. Closed and racked to " test" position l l l l l i i 21 1 1
USNRC GENERIC FUNDAMENTALS EXAMINATION PWR - FORM A QUESTION: 45 As compared to a prompt neutron, a delayed neutron is more likely to: A. cause fast fission in the reactor fuel. B. be resonantly absorbed in the reactor fuel. C. cause thermal fission in the reactor fuel. D. be detected by excore nuclear instrumentation. QUESTION: 46 Select the equation that defines K-excess (excess reactivity). A. K + 1 gf B. K 1 g, C. Kgf(1-SDM) D. 1/(1-Kg,) l 22 l l
_m USNRC GENERIC FUNDAMENTALS EXAMINATION PWR - FORM A QUESTION: 47 At the time of a reactor trip from 100 percent power, shutdown margin was determined to be -5.883% delta-K/K. Over the next 72 hours the Reactor Coolant System was cooled down and boron concentration was increased. The reactivities affected by the change in plant conditions are as follows: Reactivity Chance (+ or -) Xenon 2.675% delta-K/K Moderator temperature 0.5% delta-K/K Boron 1.04% delta-K/K What is the shutdown margin 72 hours after the trip? (Assume end of core life.) A. -1.668% delta-K/K B. -3.748% delta-K/K C. -7.018% delta-K/K D. -9.098% delta-K/K QUESTION: 48 -8 Reactor power increases from 10 amps to 5 x 10'7 amps in 2 minutes. What is the average startup rate? A. 0.95 dpm l B. 0.90 dpm I l C. 0.85 dpm l. l D. 0.82 dpm I i I l 23
ll' US!IRC GENERIC FUN DAMEllTA LS EXAMINATION IMR - 10RM A QUESTION: 49 over core life, plutonium isotopes are produced with delayed neutron fractions that are than uranium delayed neutron fractions, thereby causing reactor power transients to be near the end of core life. A. smaller; faster B. smaller; slower C. larger; faster D. larger; slower QUESTION: 50 Which one of the following isotopen is the MOST significant contributor to resonance capture of fission neutrons in the reactor core? A. U-233 B. U-238 C. Pu-239 D. Pu-240 QUESTION: 51 Which one of the following will cause the Doppler power coefficient to become MORE negative? A. Increased clad creep B. Increased pellet swell C. Lower power level D. Lower coolant boron concentration 24 l
USNRC GE!1ERIC FUNDAMEllTALS EXAMIllATION PWR - FORM A QUESTION: 52 Which one of the following reactivity coefficients is the LARGEST contributor to the total power coefficient at the beginning of core life? A. Moderator temperature coefficient B. Void coefficient C. Pressure coefficient D. Doppler coefficient i QUESTION: 53 The amount of boric acid required to increase the reactor coolant boron concentration by 10 ppm at beginning of core life conditions (1200 ppm) is approximately the amount of boric acid required to increase boron concentration by 10 ppm at end of core life conditions (100 ppm). A.. twelve times D. eight times I C. four times D. the same as l QUESTION: 54 Integral control rod _(CEA) worth is the chango in per change in rod (CEA) position. A. reactor power; total-B. reactivity; unit C. reactor power; unit D. reactivity; total 25 e,,- -, ~,.
l USNRC GENERIC FUNDAMENTALS EXAMINATION PWR - FORM A QUESTION: 55 Which one of the following parameters typically has the GREATEST effect on the shape of a differential rod worth curve? A. Core radial flux distribution B. Core axial flux distribution C. Core xenon distribution D. Burnable poison distribution QUESTION: SS The purposes of using control rod (CEA) bank cverlap are to: A. ensure the rod (CEA) insertion limits are not exceeded and to maintain individual and group rod (CEA) position within allowable tolerances. B. provide a more uniform dif ferential rod (CEA) worth and to ensure the rod (CEA) insertion limits are not exceeded. C. provide a more uniform axial flux distribution and to provide a more uniform differential rod (CEA) worth. D. maintain individual and group rod (CEA) position indicators within allowable tolerances and to provide a more uniform axial flux distribution. 26
-.. - -.. ~ USNRC GENERIC FUNDAMENTALS EXAMINATION PWR - FORM A QUESTION: 57 The reactor is operating at 80 percent power during a load decrease to 60 percent when a control rod (CEA) becomes stuck during insertion of the rest of its group. If group control rod insertion continues, which of the following will be adversely affected? A. Power distribution and shutdown margin B. Shutdown margin and power defect C. Power defect and critical heat flux D. Critical heat flux and power distribution QUESTION: 58 Xenon-135 is considered a major fission product poison because it has a large: i A. fission cross section. B. absorption cross section. C. elastic scatter cross section. D. inelastic scatter cross section. 27
- -~r'+
e et 4 -w w-w w w w w wriwev-v< wr w-'b ec'-w-'71-
1 i USNRC GENERIC FUNDAhENTALS ~EXisM1N ATION PWR - FORM A QUESTION: 59 A reactor has been operating at a steady-state power level for 15 hours following a rapid power reduction from 100 to 50 percent using boration for reactivity control. Which one of the following describes the current core xenon concentration? A. Increasing B. Decreasing C. At equilibrium D. Oscillating QUESTION: 60 A reactor has been operating at 100 percent power for one week when power is ramped in 4 hours to 50 percent. Which statement describes the new equilibrium xenon concentration? A. One-half the 100 percent value B. Less than one-half the 100 percent value C. More than one-half the 100 percent value D. Equal to the 100 percent value QUESTION: 61 Xenon oscillations that tend to DAMPEN themselves toward equilibrium over time are oscillations. A. converging B. diverging C. diffusing D. transitioning 28
USNRC GENERIC FUNDAMENTALS EXAMINATIOt1 PWR - FCRM A QUESTION: 62 Following a 7 day shutdown, a reactor startup is performed and the plant is taken to 40 percent power over a 6 hour period. After sthbilizing at 40 percent power, what type of reactivity will the operator need to add to compensate for xenon changes I over the next 24 hours? A. Negative only B. Negativa, then positive C. Positive, then negative D. Positive only QUESTION: 63 Following a reactor trip, negative reactivity from xenon initially increases due to: A. Xenon production from the decay of iodine-135. B. Xenon production from the spontaneous fission of uranium. C. the reduction of xenon removal by decay. D. the reduction of xenon removal by recombination. QUESTION: 64 During a six-month period of continuous full power reactor operation, the reactor coolant boron concentration must be decreased steadily to compensate for: A. buildup of fission product poisons and decreasing control rod (CEA) worth. B. fuel depletion and buildup of fission product poisons. C. decreasing control rod (CEA) worth and burnable poison burnout. I j D. burnable poison burnout and fuel depletion. 29 l
USNRC GEliERIC FU!IDAMEliTA LS E X A M I ll A T I O t1 PWR - FORM A I QUEST 10!!: 65 While withdrawing control rods (CEAs) during an approach to criticality, the stable count rate doubles. If the same amount of reactivity that caused the first doubling is added again, stable count rate will and the reactor will be A. double; subcritical B. more than double; subcritical C. double; critical D. more than double; critical QUESTIO!!: 66 During a reactor startup, control rods (CEAs) are withdrawn such that K,,, increases from 0.98 to 0.99. If the count rate before the rod withdrawal was 500 cps, which one of the following will be the final count rate? A. 750 cps B. 1000 cps C. 1500 cps D. 2000 cps 30
l l [ l USNRC GENERIC FUNDAMENTALS EXAMINATION PWR - FORM A i j QUESTION: 67 l L An estimated critical rod position (ECP) has been calculated for { a reactor startup that is to be performed 6 hours after a trip from a 60 day full power run. Which one of the following events l' or conditions will result in the actual critical rod position being LOWER than the ECP? l A. The startup is delayed for approximately 2 hours. B. The steam generator pressures are decreased by 100 psi just prior to criticality. i C. A new boron sample shows a current borcn concentracion 20 ppm higher than that used in the ECP calculation. l l D. Steam generator feedwater addition rate is reduced by 5 i i percent just prior to criticality. l l I l QUESTION: 68 The reactor is critical at 10,000 cps when a steam generator l atmospheric relief valve fails open. Assume end of core life l conditions, no reactor trip, and no operator actions are taken. 1 When the reactor stabilizes, Tave will be than the initial Tave and reactor power will be the point of l adding heat. A. greater; at B. greater; above C. less; at i D. less; above 1. l \\ I l l 33 l
USNRC GENERIC FUNDAMENTALS EXAMINATION PWR - FORM A -QUESTION: 69 During a xenon-free reactor startup, critical data were inadvertently taken one decade above the required intermediate range (IR) level. The critical data were taken again at the proper IR level with the same reactor coolant temperatures and boron concentration. the critical rod (CEA) position taken at the proper IR level is t'ne critical rod position taken one decade above the proper IR level. d A. less than B. the same as C. greater than D. unrelated to QUESTION: 70 After taking critical data during a reactor startup, the operator establishes a stable 1 dpm startup rate to increase power to the point of adding heat (POAH). How much negative reactivity feedback must be added at the POAH to stop the power increase? Assume: J, = 0.00579 ,3 1 1.0 x 10 = 0.1 sec, sec A.,, = A. 0.16% delta-k/k B. 0.19% delta-k/k C. 0.23% delta-k/k D. 0.29% delta-k/k 32 l l
1 l f USNRC GENERIC FUNDALENTALS EXAMINATION PWR - FORM A QUESTION: 71 The use of boron as a burnable poison in a reactor core: A. inc.~ eases the amount of fuel required to produce the same amount of heat. B. allows the plant to operate longer on a smaller amount of fuel. C. allows more fuel to be loaded and prolongs core life. D. absorbs neutrons that would otherwise be lost from the core. QUESTION: 72 The reactor is exactly critical below the point of adding heat when a single control rod (CEA) is fully inserted into the core. Assuming no operator or automatic action, reactor power will slowly decrease to: A. zero. B. the value associated with the source neutron strength. C. a value above the source neutron strength. D. a slightly lower value, then slowly increase to the initial value. 33
i ) USNRC GENERIC FUNDAMENTALS EXAMINATION PWR - FORM A QUESTION: 73 A pressure gauge on a condenser reads 27 inches of mercury (Hg) vacuum. What is the absolute pressure corresponding to this vacuum? (Assume an atmospheric pressure of 15 psia.) A.- 1.0 psia B. 1.5 psia C. 13.5 psia D. 14.0 psia QUESTION: 74 A liquid is saturated with 0 percent quality. Assuming pressure remains constant, the addition of a small amount of heat will: _A. raise the liquid temperature above the boiling point. B. result in a subcooled liquid. C. result in vaporization of the liquid. D. result in a superheated liquid. QUESTION: 75 Which one of the following steam generator (S/G) pressures will come closest to producing a 50 degree F reactor coolant system (RCS) subcooling margin with RCS pressure at 1000 psia? (Assume a negligible delta-T across the S/G tubes.) A. 550 psia D. 600 psia l C. 650 psia D. 700 psia 34 i l l
US!1RC GE!!ERIC FU!1 DAME!4TALS EXAM 11; ATI Oli PWR - FORM A QUESTIOll: 76 Which one of the following explains why condensate subcooling is necessary in the steam turbine / condenser phase of a plant cycle? A. To maximize overall secondary efficiency B. To provide a better condenser vacuum C. To minimize turbine blade and condenser tube erosion by entrained moisture D. To provide net positive suction head for the condensate pumps QUESTION: 77 You are involved in a routine plant shutdown with a steam bubble in the pressurizer. Pressurizer pressure is 415 psig and pressurizer pressure and level are slowly decreasing. You suspect a pressurizcr power operated relief valve (PORV) is partially open but the position indicating lights are not working. Which one of the following is the expected PORV tailpipe temperature if the PORV is open? (Assume downstream pressure is atmospheric.) A. 652 degrees F B. 450 degrees F C. 330 degrees F D. 212 degrees F 35
~_- l l i USNRC GENERIC FUNDAMENTALS EXAMINATION PWR - PORM A QUESTION: 78 ) To achieve maximum plant efficiency, feedwater should enter the steam generator (S/G) and the temperature 1 difference between the S/G and the condenser should be as as possible. A. close to saturation; small B. close to saturation; great C. as subcooled as practical; small D. as subcooled as practical; great QUESTION: '79 A sudden stop of fluid flow in a piping system, due to rapid l closure of an isolation valve, will most likely result in: A. check valve slamming. B. pump runout. C. water hammer. I D. pressurized thermal shock. QUESTION: 80 A'55 gpm leak has developed in a cooling water system that is operating at 100 psig. Which one of the following is the expected leak rate when system pressure has decreased to 50 poig? i A. 27.5 gpm B. 31.8 gpm C. 38.9 gpm D. 43.4 gpm l 36
l l USNRC GENERIC FUNDAMENTALS EXAMINATION PWR - FORM A QUESTION: 81 Cavitation of a centrifugal pump in an open system is indicated by discharge pressurc and flow rate. A. low; low B. high; high C. low; high D. high; low QUESTION: 82 In an operating cooling water system with a constant water velocity, if water temperature decreases, indicated volumetric flow rate (gpm) will: A. remain the same, because the density of the water has not changed. B. increase, because the density of the water has increased. C. remain the same, because the water velocity has not changed. D. increase, because the viscosity of the watet has increased. QUESTION: 83 To decrease the flow rate through an operating positive displacement pump, an operator should: A. throttle the pump discharge valve partially closed. B. throttle the pump suction valve partially closed. C. decrease the pump NPSH. D. decrease the pump speed. 37
USNRC GENERIC FUNDAMENTALS EXAMINATION PWR - FORM A QUESTION: 84 Refer to the drawing of a fuel rod and coolant flow channel at beginning of core life (see figure 9). Given the following initial core parameters: Reactor power 100 percent = Teootant 500 degrees F = T = 3000 degrees F fuet centerune What would the fuel centerline temperature be if, over core life, the total fuel-to-coolant thermal conductivity were doubled? (Assume reactor power is constant.) A. 1000 degrees F B. 1250 degrees F C. 1500 degrees F D. 1750 degrees F QUESTION: 85 The reactor is operating at 80 percent power with a core delta-T of 48 degrees F when a station blackout occurs. Natural circulation is established and core delta-T stabilizes at 40 degrees F. If mass flow rate is 3.0 percent, what is the current decay heat level? A. 1.0 percent B. 2.0 percent C. 3.0 percent t D. 4.0 percent 38
USNRC GENERIC FUNDAMENTALS EXAMINATION PWR - FORM A QUESTION: 86 Subcooled nucleate boiling is occurring along a heated surface. The heat flux is then increased slightly. What will be the effect on the delta-T between the surface and the fluid? (Assume subcooled nucleate boiling is still occurring.) A. Large increase in delta-T because of steam blanketing B. Large increase in delta-T causing radiative heat transfer to become significant C. Small increase in delta-T because of steam blanketing D. Small increase in delta-T as vapor bubbles form and collapse-QUESTION: 87 Which parameter change will reduce the departure from nucleate boiling ratio (DNBR)? A. Decrease in reactor power B. Increase in pressurizer pressure C. Increase in reactor coolant flow D. Increase in reactor coolant temperature QUESTION: 88 How does critical heat flux vary from the bottom to the top of the reactor core during normal full power operation? A. Decreases continuously B. Decreases then increases C. Increases continuously [ D. Increases then decreases l l [ 39 l l' l l
USNRC GEtiERIC FUNDAMENTALS EXAMI!!ATION PWR - FORM A QUESTION: 89 A small increase in delta-T (at the fuel clad-to-coolant interface) causes increased steam blanketing and a reduction in heat flux. This describes which type of boiling? A. Subcooled boiling B. Nucleate boiling C. Partial film boiling D. Total film boiling QUESTION: 90 The heat transfer coefficient of the core will be directly increased if: (Assume bulk coolant subcooling.) A. the coolant temperature is decreased. B. the coolant flow rate is decreased. C. nucleate boiling occurs in the coolant. D, the coolant flow is laminar instead of turbulent. QUESTION: 91 Which one of the following parameters provides the BEST indication of adequate core nooling following a small loss-of-coolant accident? A. Emergency cooling injection flow rate B. Pressurizer level C. Subcooling margin D. Pressurizer pressure 40
.=_ USNRC GENERIC FUNDAMENTALS EXAMINisTION PWR - FORM A QUESTION: 92 During a plant cooldown and depressurization with forced circulation, Reactor Coolant System (RCS) loop flow and reactor coolant pump (RCP) current indications become erratic. This is most likely caused by: A. RCP cavitation. B. RCP runout. C. RCS loop water hammer. D. RCS hot leg saturation. QUESTION: 93 With the Reactor Coolant System subcooled and all reactor coolant pumps stopped, the stable natural circulation flow rate will NOT be affected by an increase in the: A. reactor coolant pressure. B. time after reactor trip. C. steam generator level. D. steam generator pressure. l l l l-i 41 l I ii,_. - ~-- ~ ~ ~ - ~- ' ~ ~ ~ ' " ~ ' "
'B 4 USNRC GENERIC FUNDAMENTALS EXAMINATION PWR - FORM A QUESTION: 94 The 2200 degrees F maximum peak cladding temperature limit is imposed because: A. it is approximately 500 degrees F below the fuel cladding melting temperature. B. any clad temperature higher than this correlates to a fuel centerline temperature at the fuel melting point. C. the oxidation rate of the zircalloy cladding increases sharply above 2200 degrees F. D. the thermal conductivity of zircalloy decreases at temperatures above 2200 degrees F causing an unacceptably sharp rise in the fuel centerline temperature. QUESTION: 95 l l The pellet-to-clad gap in fuel rod construction is designed to: A. decrease fuel pellet slump. B. attenuate fission gammas. C. increase heat transfer. D. reduce internal clad strain. QUESTION: 96 Pressure stress on the reactor vessel wall is: A. compressive across the entire wall. B. tensile across the entire wall. C. tensile at the inner wall, compressive at the outer wall. D. compressive at the inner wall, tensile at the outer wall. 42
USt1RC GUllERIC FUIIDAMI:!!T/sLb EX AM1 t! ATI Of1 PWR - FORM A QUESTION: 97 The reference temperature for nil-ductility transition ( RT. ) is sg the temperature above which: A. a large compressive stress can result in brittle fracture. B. a metal exhibits more ductile tendencies. C. the probability of brittle fracture increases. D. no appreciable deformation occurs prior to failure. QUESTION: 98 The probability of reactor vessel brittle fracture is DECREASED by minimizing: A. oxygen content in the reactor coolant. B. the time taken to cool down the Reactor Coolant System. C. operation at high temperatures. D. the amount of copper in the reactor vessel. QUES 7, N: 99 Which one of the following types of radiation significantly reduces the ductility of the metal of a reactor pressure vessel? A. Beta B. Thermal neutrons C. Gamma D. Fast neutrons 43
ro 5 o USNRC GEtIERIC FUt! DAME!1TALS EXAMI!1 ATIO!J PWR - FORM A QUESTION: 100 Pressurized thermal shock would most likely be a concern during an uncontrolled: A. cooldown followed by a rapid repressurization. B. depressurization followed by a rapid repressurization. C. cooldown followed by a rapid depressurization. D. depressurization followed by a rapid cooldown. 44}}