c.

I December 19,1997 MEMORANDUM TO: Information and Records Management Branch Office of Information Resources Management FROM:

Glenn B. Kelly, Senior Project Manager Project Directorate 3-3, DRPW, NRR SUBsECT:

INFORMATION TO BE PLACED ON THE DUANE ARNOLD ENERGY CENTER (DAEC) DOCKET (50-331)

The enclosed information documents c series of conference calls and a fax between the NRC staff and IE3 Utilities Inc. regarding DAEC responser to staff requests for information on Section 3.8 of the DAEC improved technical specific on submittal. Please place the enclosed information on the DAEC docket.

Enclosure:

as stated Docket Nos. 50-331 cc: See next page DISTRIBUTION-Docket File PUBLIC G. Grant, DRP, Rill EAdensam (EGA1)

PD3-3 RF R. Savio G. Kelly ACRS OGC E. Tomlinson R. Tjader DOCUMENT NAME: C:\\DUANEARNi97197 COP.WPD groceve e copy of this oncument Wiscato u the tox CsCom wto attachment /endosure E= Copy eth attachmanyonclosure N = No copy OFFICE PM PD33 E

NAME GKelly\\

DATE 12/19/97 I

I OFFICIAL RECORD COPY

\\

ECRH CR %il@@pV

, ' '4 g s.-,

t 9801060003 971219 I

II DR ADOCK 05000331 PDR

.. -. ~.

p**,ca:p

  • p-UNITED STATES i

j-

.j NUCLEAR REGULATORY COMMISSION.

)

2' WASHINGTON, D.C. 20046 4001 os.,.....f December 19,1997 MEMORANDUM TO: information and Records Management Branch Office of Information Resources Manageme t

/

/

.FROM:

Glenn B. Kelly, Senior ProjeM Manager

/ /

Project Directorate 3-3, DRPW, NRR A

SUBJECT:

INFORMATION TO BE FLACED ON THE DUANE ARNOLD ENERGY CENTER (DAEC) DOCKET (50-331)

The enclosed information documents a series of conference calls and a fax between the NRC -

~ staff cnd IES Utilities inc, regarding DAEC responses to staff requests for information on -

= Section 3.8 of the DAEC improvec technical specification submittal. Please place the enclosed r

information on the DAEC docket.-

E

Enclosure:

as stated Docket Nos. 50-331 cc: See rat page O

w

- M vkurwtnAD) a&rasann1)

U*Umb>

1 1

Minutes DAEC - NRC ITS Conferengn CMI Date: 10 December 1997 Time: 1315 CST Amendees:

-DAEC Ken Peveler (Lictasing)-

Jeff Mahannah(Systan Eng.)

= Tony Browning (Licensag) _

- JoelEastos(Procedures)

Ken Putnam (Licensing)

Rob Anaerson (Outage Mgmt.)-

NRC Clenn Kelly (DAEC-LPM)

Ed Tomlinson(TSCB)

Bob Tjader(TSCB)

Per the agree-to fonnat for these calls, the "new business" was discussed first and "old business" from prior

(

calls was handled last, time partnitting.

I, Resumed discussion ofITS Section 3.8 RAls:

i RAI#

Discussion / Resolution / Action Items CTS 3.8.4 - 7 Action item: DAEC to bring service and perfcetnance discharge load profiles to Dec.

17 meeting. Issue to resolve is whe*her or not a modlSed performance discharge test p

' envelopes" a savice discharge test.

l-CTS 3.8.61 No further actions needed, question closed.

CTS 3.8.6-2 Action item: DAEC to verify that UFSAR references IEEE 450,1987. Then NRC will consider question closed.

CTS 3.8.6-3 No further actions needed, question closed.

CTS 3.8.6-4 No further actions needed, question closed.

CTS 3.8.71 To be discussed at the Dec.- 17 meeting.

CTS 3.8.7 2 No further actions needed, question closed.

- CTS 3.8.7-3 No father actions net.ded, question closed.

CTS 3.8.7-4

- No further actions naeded, question closed.

4 n 3.8.7-5 No further actions needed, qusstion closed.

.UREO 3.8.l 1 No firtber actions needed, question closed.

NUAEG 3.8.1-2 To be resolved concurrently with CTS 3.s.1 2.

NUREG 3.8.1-3 Action Ites: NRC staff to discuss the use of' Notes'.

NUREG 3.8.1 No further actions needed, question closed.

NUREG 3.8.l 5 NRC staff undersands "rsted" to mean nameplate rating (i.e.: one value), not a range.

Acties Itcas: DAEC to review the use of the term " rated" and evaluate providing a range instead.

NUREG 3.8.16 DAEC agreed to change loadans criteria to values corresponding to 90 to 100% of rated. Its NRC staff understands tha' DAEC's accident loading is approximately sisvarc-revresponse/121ot7. doc

l 1

l 92% of rated and stated that Is acceptable. NRC staff stated that the intent of the SR is I

to ensure the diesel is loaded enough to stress it enough for equipment def4ciencies to become apparent without overloading the diesel The design of the :)*m ensures that ets DG is sized appropriately to handle tht accident loads. The periodic surveillance test does not have to be performed spec!fically at accidem loading to ensure it is functioning properly.

NUREO 3.8.17 No further actions needed, question closed.

NUREO 3.8.18 Action Item: DAEC to provide information on testing of day tank alarms.

NUREO 3.8.19 To be resolved concurrentl with NUREG 3.8.16.

3 NUREG 3.8.1 10 No further actions needed, question closed.

NUREO 3.8.1 11 No further actions needed, question closed.

NUREG 3.8.1 12 To be resolved concurrently with NUREG 3.8.1 5.

NUREG 3.8.1 13 Action Item: DAEC to provide information at the Dec.17 meeting on how one start of the DGs can satisfy each of the SRs concurrently without the additonal wear of muhiple DG starts.

NUREG 3.8.1 14 To be resolved concurrently with NUREG 3.8.1 13.

NUREO 3.8.1 15 To be resobed concurrently with NUREO 3.8.1-13.

NUUiG 3.8.1 16 To be resolved concunently with NUREG 3.8.1 5.

NUREO 3.8.4 7 To i>e resolved concurrently with CTS 3.8.4 7.

NUREG 3.8.61 To be discussed at the Doc.17 meeting.

Action Item: NRC to refer to techn! cal branch.

Action Item: DAEC to provide information on why OK to have one cell inoperable.

NUREG 3.8.6 3 To be resolved concurrently with NUREG 3.8.6-1.

NUREG 3.8.6-4 Action item: DAEC to provide some kind of time limit In which cell level must return to normal.

NUREG 3.8.7 1 NRC concernA that DAEC may need to enter LCO 3.0.3 (f the DC bus itself becomes inoperable. Action Item: DAEC to evaluate adding the DC buses themselves to Table of distribution panels.

NUREG 3.8.7 3 To be resolved concurrently with NUREO 3.8.71.

NUREG 3.8.7-4

- To be resolved concurrently with NUREG 3.8.71.

11. Followp Items from 12/3/97 call: Due to Ed's sick leave. the material faxed to the St Hafter the last cali (12/3/97) had not yet been reviewed. These issues will be discussed in the next planned call on 12/12/97.

taip/ arc t:14csponse/121097. doc l

g Minutes DAEC - NRC ITS Conference Call Date: 12 December 1997 Time: 12:30 CST Attendees:

DAEC-Tim Al'm (Operations)

Ken Peveler (Manager, Regulatory Pertormance)

Jeff Mahannah (System Eng.)

Tony Browning (Licensing)

Ken Putnam (Licensing)

NRC - Ed Tomlinson (TSCB)

1. "New Business" Section 3.8 Questions Reviewed:

NUREG 3.8.2.1: To be discussed at the 17 December meeting.

NUREG 3.8.2.2: To be discussed at the 17 December meeting.

NUREG 3.8.3.1:No further actions needed, question closed.

NUREG 3.8.3.2: DAEC will review the independence of the Air Recievers and verify that the bases for Condition E is consistent with the LCO. FOLLOW -UP item for D AEC NUREG 3.8.3.3: DAEC will review the independence of the Air Recievers and verify tha* the bases for Condition E is consistent with the LCO. FOU OW -UP item for DAEC NUREG 3.8.3.4: No further actions needed, question closed NUREG 3.8.4.1: DOC P18 - DAEC will remove the phrase "(as the limiting single failure)". Once this is done, no further actions needed, question closed.

NUREG 3.8.4.2: NRC to check with Glenn as to if this has been sent to the Tech Branch or not.

FOLLOW UP item for NRC NUREG 3.8.4.3: No further actions needed, question closed NUREG 3.8.4.4:No further actions needed, question closed NUREG 3.8.4.5: No further actions needed, question closed NUREG 3.8.4.6: DAEC will review the worCng of the SR and the need to reinstate the NUREG note.

FOLLOW UP item for DAEC.

NUREG 3.8.5.1: No further actions needed, question closed NUREG 3.8.6.2:No further actions needed, question closed NUREG 3.8.7.2: No further actions needed, question closed NUREG 3.8.7.5: No further actions needed, question closed NUREG 3.8.7.6: No further actions needed, question closed NUREG 3.8.7.7: To be discussed at the 17 December meeting after addit;onal NRC review. FOLLOW-UP item for NRC NUREG 3.8.8.1: To be discussed at the 17 Dember meeting after additional NRC review. FOLLOW-UP item for NRC NUREG 3.8.8.2: No further actions needed, question closed ll. *Old Business": Review of follow-up items from the 12/3/97 call:

CTS 3.8.1.2: NRC was concerned about how the Completion Time for LCO 3.8.1 Required Action A.2 was translated from the CTS into the ITS format. Specifically, the translation of the CTS " Cold Condition" to the ITS Modes 3 and 4. The DAEC will review this to see if a change is needed or provide Meussion on why it is not.NRC questioned why the NOTE loca:ed in LCO 3.8.1 just prior to Required Ar a A.2 was 1

8UMPSth/

LUDJU t>tEnJUtnnAR>

ULinMx9Uuutti>

e I

not located in the LCO section. NRC will discuss this prior to the riext meeting. DAEC will find other examples of w here this is used in the ITS.

Response.1TRC will discuss the use of the 3.0.4 notes at the 12/17 meeting The DAEC requested a call for Monday (12/15) to begin discussion on the Section 3.6 Questions. In particular, to highlight the priority issues for farther discussion at the upcoming meeting of 12.18/97. "Ihe bT.C will confirm Monday moming if a call will occur.

F4 y uce

> >,lmp y, um p,a %y,,_

N %~ L'a q

~~~'

DAEG 24VDd Ba7Ar;p /ssoe.

[EAZ 3 84-/, 3.8. 9-3,38.7-t) 5/saen de n-ing7 weedog cuiy% ossg, rye /icoe f ddeifiy (a isAcscinng Ak ers.u um inpied-~&

i was re Arred'd too Mixri ersa BrawAdid Mr-

/kalmrs thshwhas ori de esae ere as &&as.-

7'Ae asues b oo/.aex y

. apaer.sooraes,4ve Z,w,7 /w?o%/de ace,04aeeridra q a en sa.u Azre 6 he a rs A tisee.s/wA/de a6d4d'./wn &.tAs smwesiew aid,iMs<res)paad'ss e apsesle hun,wg aaJn.

  • f f N Sd 62f? db S/&

h 8dde,0 k Md6 f Ye ff y af

/c re/oaek rife avm de/Agr tego/resei/s prio? 4 ksuave

& Inamonam'r{ //ai//Le.eh/aoW

- ir'.sla/ aayo6me. fA Dam J a w ss+

be oMaines'prio2. d asonee zuas s f Dou aidlave 4 Aside a;/

esad4 a sEva sa/Ag,4yh-eds/m y G/

hsesse os/.d He isne resosas

-