Amend 64 to License NPF-5,revising Table 3.8.2.6-1 to Reflect Installation of Two Addl Overcurrent Protective Devices
ML20196K250
Person / Time
Site: Hatch 
Issue date: 10/22/1986
From: Muller D
Office of Nuclear Reactor Regulation
To:
City of Dalton, GA, Georgia Power Co, Municipal Electric Authority of Georgia, Oglethorpe Power Corp
Shared Package
ML20196K254 List:
References
NPF-05-A-064, TAC 62027 NUDOCS 8803150238
Download: ML20196K250 (5)


Text

. j o atcoq#o A

UNITED STATES g

8 NUCLEAR REGULATORY COMMISSION g

ej WASHINGTON, D. C. 20555 k...l..,/

GEORGIA POWER COMPANY OGLETHORPE POWER CORPORATION HUNICIPAL ELECTRIC AUTHORITY OF GEORGIA CITY OF DALTON, GEORGIA DOCKET NO. 50-366 EDWIN I. HATCH NUCLEAR PLANT, UNIT NO. 2 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No.: 64 License No.: NPF-5 1.

The Nuclear Regulatory Comission (the Comission) has found that:

A.

The application for amendment by Georgia Power Company, et al. (the licensee), dated July 11, 1986, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Comission's rules and regulations set forth in 10 CFR Chapter I; B.

The facflity will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Comission; C.

There is reasonabic assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety c" the public, and (ii) that such activities will be conducted in compliance with the Comission's regulations; D.

The issuance of this amendment will not be inimical to the comon defense and security or to the health and safety of the public; and E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the Comission's regulations and all applicable requirements have been satisfied.

2.

Accordingly, the licer.se is amended by changes to the Technical l

Specifications as indicated in the attachment to this license amendment, and paragraph 2.C.(2) of Facility Operating License No. NPF-5 is hereby amended to read as follows:

!!kso$$$N$o66 p

PDR

(2). Technical Specifications The Technical Specifications contained in Appendices A and B, as revised through Amendment No. 64, are hereby incorporated in the license. The licensee shall operate the facility in accordance with the Technical Specifications.

3.

This license amendment is effective as of its date of issuance and shall be implemented within 60 days of issuance.

FOR THE NUCLEAR REGULAT0DY COMMI SION

.///

Daniel R. Muller, Director BWR Project Directorate #2 Division of BWR Licensing

Attachment:

Changes to the Technical Specifications Date of Issuance: October 22, 1986 I

. ~ -

7

ATTACHMENT TO LICENSE AMENDMENT NO. 64 FACILITY OPERATING LICENSE NO. NPF-5 DOCKET NO. 50-366 Replace the following page of the Appendix "A" Technical Specifications with the enclosed page. The revised page is identified by Amendment number and contains a vertical line indicating the area of change. The overleaf page is provided for convenience.

Remove Insert 3/4 8-21 3/4 8-21 F

ww.

t d

. -. - ~,, -..,

-~

TABLE 3.8.2.6-1 (Continued)

PRIMARY CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES DEVICE NUMBER SYSTEM / COMPONENT AND LOCATION

  • POWERED c.

Type 3:

1.

600 VAC, MCB, T.M.

RECIRC. PUMP MOTOR HEATER 2R24-5014, COMPT. 5E 2831-C001B 4

i3 BHT SB 2

bl 3.

600 VAC, MCB, T.M.

DRYWELL COOLING UNIT 2R24-5013, COMPT. 38 2T47-8010A 4.

600 VAC, MCB, T.M.

DRYWELL COOLING UNIT 2R24-5014, COMPT. 8A 2T47-B010B d.

Type 4:

1.

120 VAC, MCB, T.M.

CABLES BHEB05M01 AND ER25-5102, CKT. 10 BHE808M02 2.

129 VAC, MCB, T.M.

CKTS, BGE708M01 AND 2RE5-5101, CKT. 10 BGE708M02 e.

Type 5:

c 1.

600 VIC, MCB, M.0.

DRYWELL EQUIP. DR. SUMP 2R24-5014, COMPT. 2A DISCH. MOV 2G11-F018 2.

600 VAC, MCB, M.O.

ORYWELL EQUIP. DRAIN SUMP 2R24-5014, COMPT. 6C RECIRC. MOV 2G11-F015 3,

600 VAC, MCB, M.O.

RCIC STEAMLINE INBOARD T

2R24-50128, COMPT. 4A ISO. MOV. 2E51-F007 4.

600 VAC, MC0, M.0.

RHR HEAD SPRAY ISOLATION 2R24-5011, COMPT. 9A MOV. 2E11-F022

['.hh 5.

600 VAC, MCB, M.O.

HPCI STEAM LINE INBOARD 2R24-3011A, CCMPT. 4A It0LATION MOV. 2E41-F002 l

6.

600 VAC, MCB, M.0.

RWCU INBOARD ISOLATION l

2R24-5011, COMPT. 14C MOV. 2G31-F001 7.

600 VAC, MCB. M.O.

MIN STEAM LINE DRAIN J

i 2R24-3011, COMPT. ISB HOV. 2B21-F016

.,;4 HATCH - UNIT 2 3/4 8-21 Amendment No. 46,60, 64 o..

o.. a

~

TAELE 3.8.2.6-1 (continued)

% 'l PRIMME CCNTAI2M2Tr PENEFRP&ICN CONIXJCTOR CVEFCUPJETr PPCTICTIVE DEVICES DEVICE tmBER SYSIDi/CCt@CNENT AMD I4 CATION

  • POEFFD c.

Type 6:

1.

600 VAC, FCB, M.O.

IDCP 'A' PWP SLCTICN 2R24-5018A, CCWr. 2A E 2B31-IO23A 2.

600 VAC, FCB, M.O.

IICP 'A' PTP DISCH.

2P24-S018A, CCWr. 2B M 2B31-IO31A 3.

600 VAC, FCB, M.O.

14CP 'B' PGP SLUTICN f

2R24-501BB, CCter. 3A KV 2B31-IO23B 4.

600 WC, FCB, M.O.

IfrP 'B' P2P DI!CH.

2F24-5018B, CCtfr. 3B.

EV 2B31-7031B 5.

600 VAC, FCB, M.O.

DRSELL IDUIP. ERAIN 2R24-5014, CCtPr.1B PUMP B 2Gil-CD06B 6.

600 VAC, 1CB, M.O.

DRWILL II.COR EPAIN SWP 2R24-5014, CCSPT. 7D PO P 'B' 2G11-C0013 7.

600 VAC, FCB, M.O.

DRW7EI.L IILOR EPAIN Stif 2R24-3013, CQPr. 4A P&P 1A 2G11-C001A j

~

8.

600 VAC, }CB, M.O.

DIT77I1 FDUIP. DIRIN St.t?

2R24-2013, CQPr. 4B P2P A 2G11-COO 6A 9.

600 VAC, FCB, M.O.

DRMIL COCLING UTI 2R24-S012, CDPr.18B 2T47-2007B1

10. 600 VAC, FCB, M.O.

DRMLL CCCLI2U UNIT 2R24-!D12, COPr.19A 2r47-C001B 11, 600 VAC, FCB, M.O.

IEP SEUIDON COCLI25 2R24-SOll, CCNPT 6C ISO. 60/ 2E11-FOO9

12. 600 VAC, PCB, M.O.

DRMIL CCCLDU HIIT 2R24-SOll, CCWr.18A 2T47-3007A

13. 6d0VAC,}CB,M.C.

DRMIL COCLDU ITTUFi!

2R24-SO11, CCwr.18C AIR FAN 2T47-C001A.

  • M.C.B. - mided case circuit breaker M.O. - zagnetic cnly i

T.M. - ther:nal mgnetic IUc a - 21IT 2 3/4 8-22 Amendment No. 4, 60 e

.