B ALTIMORE OASAND ELECTRIC CHARLES CENTER P. O. BOX 1475
- BALTIMORE, MARYLAND 21203 JosteH A.TitmNAN vice passioni.,
NucktAn Entper December 1.1988 l
U. S. Nuclear Regulatory Commission Washington, DC 20555 3
NTTENTION:
Document Control Desk SUHJECT:
Calvert Cliffs Nuclear Power Plant Unit Nos.1 & 2; Docket Nos. 50-317 & 50-318 NRC Bulletin No. 88-01: Defects in Westinehou:e Circult Breakers 4
i
REFERENCES:
(a) Letter to NRC Document Control Desk from hir. J. A. Tiernan (DG&E),
dated July 13, 1988, same subject (b) Letter to hir J. A. Tiernen (BGAE) from hir. S. A. hicNeil (NRC),
l dated September 29, 1988, Request for Additional Information BGAE Response to NRC Bulletin 88-01 Gentlemen:
Reference (a) was our response to NRC Bulletin 88-01. Reference (b) requested a
]
schedule for, and description of, corrective actions for breaker inspection failures reported in Reference (a).
Thirty-nine breakers on Unit 2 and zero on Unit I were shown in Reference (a) as needing corrective action. Nine of these Unit 2 breakers have had their pole shafts replaced. Thirty more breakers will have their pole shafts replaced during their next normal presentive maintenance, or by the end of the next Unit 2 refueling outage at the latest. The end of that outage is estimated to be hiny 30, 1989.
i When these 30 pole shafts are reptsced, appropriate welds will be checked against the criteria of Sections 6.1.1 and 7.1 of Westinghouse Technical Bulletin NSID-TB-87-II as amended by NRC Bulletin 88-01, plus the alignment check o." Section 7.2 will be performed, i
l 8912090196 881201 PDR ADOCK 05000317 j
Q FDC g
___________j
c
,Docum:nt Control Desk December 1,1988 Page 2 Should you have any further questions regarding this matter, we will be pleased to discuss them with you.
Very truly yours, www JAT/DLS/dtm cc:
D. A. Drune, Esquire J.
E.
Silberg, Esquire R. A.Capra, NRC S. A. McNeil, NRC W. T. Russell, NRC D. C. Trimble/V. L. Pritchett, NRC T. Magette, DNR