_ _ _ _ _ _ _ - _ _ _ _ _ - _ _ _ _ _ _ _ - - _ _ - -. - - _ - _ - _ -

Ctation Support Department

.Q 10CeR50, Appendix E PECO NUCLEAR reco cee,o< comneex 965 Chesterbrook Boulevard A Unit of PECO Energy Wayne, PA 19087-5691 November 19,1998 Docket Nos. 50-277 50-278 License Nos. DPR-44 DPR-56 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555

SUBJECT:

Peach Bottom Atomic Power Station, Units 2 and 3 Emergency Response Data System Data Point Library Changes

Dear Sir:

The purpose of this letter is to update some of the transmitted data points provided in the Data Point Library for the Emergency Response Data System (ERDS) for Peach Bottom Atomic Power Station (PBAPS), Units 2 and 3. ERf.9 is a direct, near real-time, electronic data link between PBAPS and the NRC's Operations Center which provides for the automated transmission of a limited data set of selected parameters.

10CFR50, Appendix E, Section VI.3.a requires that any changes in computer hardware or software that affect the transmitted data points identified in the ERDS Data Point Library must be submitted to the NRC within 30 days after the changes are completed. NUREG-1394, Revision 1, " Emergency Response Data System (ERDS) Implementation," provides the appropriate guidance for submitting ERDS data point library information.

Accordingly, the enclosed ERDS data point information for PBAPS is being submitted within 30 days after the changes have Deen completed as required by 10CFR50, Appendix E. The data point information is a format consistent with the guidance specified in NUREG-1394. In addition, [/

the changes have been annotated with a reference indicating whether the point is an addition,

./

replacement, or change to the data point library.

/[

if you have any questions or require additional information, please do not hesitate to contact us.

Very truly yours, fce d

Garrett D. Edwards Director-Licensing Enclosure cc:

H. J. Miller, Administrator, Region 1, USNRC (2 copies of enclosure)

A. C. McMurtray, Senior Resident inspector PBAPS (w/ enclosure) 9812010135 981119 I' PDR ADOCK 05000277; Y

PDR a l

s 9*

Novsmber 19 - 1998

'l

-Page 2 i

i bec:

N. J. Sproul, Public Service Electric & Gas w/o enclosure R. l. McLean, State of Maryland j

A. F. Kirby, Ill, Delmarva Power & t.ight Company R. R. Janati, Commonwealth of Pennsylvania G. R. Rainey - 63C ;

J. J. Hagan - 62C-3 i

J. Doering - PB, SMB4-9 M. E. Wamer - PBAPS. A4-1S R. Z. Kinard - COATSVI w/ enclosure J. A. Slaymaker PBAPS, SC1-1

~J. G. Hufnagel - 62A-1 G. J. Lengyel-PB, A4 SS i

Commitment Coordinator-62A-1

)-

Correspondence Control Desk L

DAC l

\\

i i

i 1

i l

]

r l

l 1

l t

1-k I

i 4

PEACH BOTTOM ATOMIC POWER STATION DATA POINT LIBRARY REFERENCE FILE UNIT 2 WIDE RANGE NEUTRON MONITORING MOD Date 10/23/98 Reactor Unit PE2 Data Feeder N/A NRC ERDS Parameter NI Source RNG Point ID C529 (Replaces SPDS0222)

Plant Spec Point Description AVG WRNM PERCENT POWER Generic /Cond Description Nuclearinstruments, Source Range Analog / Digital A

Engr Units / Dig States

% power Engr Units Conversion N/A Minimum instr Range 10*

Manmum Instr Range 100 Zero Point Reference N/A Reference Point Notes N/A PROC or SENS P

Number of Sensors 4

i How Processed HealthyAwrage j

Sensor Locations N/A I

Alarm / Trip Set Points None NI Detector Power Supply Cut-off Power Level N/A NI Detector Power Supply Tum-on Power Level N/A Instrument Failure Mode Low Temperature Compensation for DP N/A Transmitters Lewi Reference Leg N/A Unique System Description Average of the WRNM channels C, D, E, F. Any value not considered reasonable is omitted from the average.