l BYRON NUCLEAR POWER STATION UNIT 1 AND UNIT 2 MONTHLY PERFORMANCE REPORT C0letONWEALTH EDISON COMPANY NRC DOCKET NO. 050-454 NRC DOCKET NO. 050-455 LICENSE NO. NPF-37 LICENSE NO. NPF-66 (0625M/0062M-2) 8801190070 871231 PDR ADOCK 05000454

1. [ 2 4, j,'

n en w

I.

Monthly Report for Byron Unit 1 for the month of December 1987 A.

Sumary of_ Operating Experience for Unit 1 The unit began this reporting period in Mode 1 at 98% power. On 12/19/87, at 0745, power was reduced to 37% to add oil to the 1A reactor coolant pump. By 12/21/87 power was returned to 98%. The unit operated at power levels of up to 98% for the rest of the reporting period.

(062SM/0062M-3)

e

'B.

OPERATING DATA REPORT DOCKET NO.:

050-454 UNIT:

Byron On3 DATE:

01/10/88 COMPILED BY:

D. J. Spitzer TELEPHONE:

(815)234-5441 x2023 OPERATING STATUS 1.

Reporting Period: December 1987. Gross Hours: 744 2.

Currently Authorized Power Level (MWt): 3411 Design Electrical Rating: 1175 (MWe-gross)

Design Electrical Rating: 1120 (MWe-net)

Max Dependable Capacity (MWe-net): NOT DETERMINED 3.

Power Level to Which Restricted (If Any): 1097 (Mwe-net) 4.

Reasons for Restriction (If Any): Steam Generator Split Flow (23MW)

THIS MONTH YR TO DATE CUMULATIVE

  • 5.

Report Period Hrs.

744 8760 20089 6.

Rx Critical Hours' 744 6210 15312 7.

Rx Reserve Shutdown Hours 0

0 37.8 8.

Hours Generator on Line 744 6007 14961 9.

Unit Reserve Shutdown Hours 0

0 0

10. Gross Thermal Energy (MWH) 2307217 17050016.6 43595850.6
11. Gross Elec. Energy (MWH) 767956 5701545 14625777
12. Not Elec. Energy (MWH) 726878 5321399 13739477
13. Reactor Service Factor 100 70.9 76.2
14. Reactor Availability Factor 100 70.9 76.2
15. Unit Service Factor 100 68.6 74.5
16. Unit Availability Factor 100 68.6 74.5
17. Unit Capacity Factor (MDC net)

N/A N/A N/A

18. Unit Capacity Factor (DER net) 87.2 54.2 61.1
19. Unit Forced Outage Hrs.

0 135.1 912.1

20. Unit Forced Outage Rate 0

2.2 5.7

21. Shutdowns Scheduled Over Next 6 Months:
22. If Shutdown at End of Report Period, Estimated Date of Startup:
23. Units in Test Status (Prior to Commercial Operation): None I
  • Note - The cumulative numbers do not reflect power generated prior to commercial se rvice.

l (0625M/0062M-4) i

t W

- - ~ - - - - - - - - - - - - - - - - - - -,-

C.

AVERACE DAILY UNIT POWER' LEVEL 8

DOCKET NO.: 050-454-UNIT: Byron One DATE: 01/10/88 COMPILED BY:

D. J. Spitzer TELEPHONE:

(815)234-5441 x2023 MONTH: December,1987 DAY AVERAGE DAILY POWER LEVEL (MWe-Net) 1.

1056 MW 16, 977 MW 2.

1072 MW 17.-

1044 MW 3.

1069 MW 18.

1025 MW i

4.

1070 MW 19.

447 MW 5.

1064 W 20.

521 MW 6,

999 MW 21.

851 MW 7.

1058 W 22.

1047 MW 8.

1056 W 23.

1026 MW 9.

1014 W 24.

985 MW 10.

1061 W 25.

981 MW 11.

1054 W 26.

1053 MW 12.

1046 W 27.

1065 MW

't 13.

898 W 28, 1064 MM 14.

889 W 29.

976 MW 15.

835 MW 30.

1048 MW 31.

1021 MW INSTRUCTIONS On this form list the average daily unit power level in MWe-Net for each day in the reporting month. Compute to the nearest whole megawatt. These figures will ba used to plot a graph for each reporting month. Note that when maximum dependable capacity is ussd for the not electrical rating of the unit there may be occasions when the daily average power level exceeds the 100% line (or the restricted power level line.)

In such cases the average daily unit power output sheet should be footnoted to explain the apparent anomaly.

(0625M/0062M-5)

cosecoccoococoococcooooo R; port P2riod December, 1987 UNIT SHUTDOWNS / REDUCTIONS 0

BYRON O

~

(UNIT 1)

                                            • o**o No.

Date Type Hours Reason Method LER Number System Famnarnent Cause & Corrective Action to Prevent Recurrence 9.

12/18/87 N/A A

5 Ramped down to add oil to RCP.

ocoe..........

Summary oooe...........

TYPE Reason Method System & Component F-Forced A-Equip Failure F-Admin 1-Manual Exhibit F & H S-Sched B-Maint or Test G-Oper Error 2-Manual Scram Instructions for C-Refueling H-Other 3-Auto Scram Preparation of D-Regulatory Restriction 4-Continued Data Entry Sheet E-Operator Training 5-Reduced Load Licensee Event Report

& License Examination 9-Other (LER) File (NUREG-OlCl)

(0625M/0062M-6) 1

~1

E.

UNIQUE REPORTING REQUIREMENTS (UNIT 1) for th7 month of Dicember 1987 1.

Safety / Relief valve operations for Unit One.

VALVES NO & TYPE PLANT DESCRIPTION DATE ACTUATED ACTUATION CONDITION OF EVENT None 2.

Licensee generated charges to ODCM.

(Y/N)

No 3.

Indications of failed fuel.

(Y/N)

Yes.

1131 = 2.0 E-3 pcuries/ gram T

L I

I I

I i

b (0625M/0062M-7)

[

'F.

LICENSEE EVENT REPORTS (UNIT 1)

The following is a tabular summary of all Licensee Event Reports for Byron Nuclear Power Station, Unit One, submitted during the reporting period, December 1 through December 31, 1987. This information is provided pursuant to the reportable occurrence reporting requirements as set forth in 10CFR 50.73.

Occurrence Licensee Event Report Number Date Title of Occurrence None a

I i

4

)

F b

t r

1 i

2 1

l l

t i

l l

l t

'l l

l I

i l

(0625M/0062M-8) i l

j l.

l l

,,, -... -..,., ~.,,,, -., -. -.. -,

. n

u II. Monthly Report for Byron Unit 2 for the month of December 1987 l

A.

Surrunary of Operating Experience for Unit 2 The unit began this reporting period in Mode 5 (Cold Shutdown).

Mode 4 (Hot Shutdown) was entered at 1305 on 12/15/87. On 12/19/87 at 1658 Mode 3 (Hot Standby) was entered. The reactor was taken critical at 1354 on 12/21/87. The unit was synchronized to the grid at 0233 on 12/22/87. The unit operated at power levels of up to 88%

until 12/30/87 when a power reduction to 28% was begun because of steam generator chemistry concerns. The unit operated at approximately 28% for the rest of the reporting period.

, /'

/

(0625M/0062M-9)

'D.

OPERATING DATA REPORT DOCKET NO.:

050-455 UNIT: Byrcn Two DATE:

01/10/88 COMPILED BY:

D. J. Spitzer TELEPHONE:

(815)234-5441 x2023 OPERATING STATUS 1.

Reporting Period: December 1987. Gross Hours:

744 2.

Currently Authorized Power Level (MWt): 3411 Design Electrical Rating: 1175 (MWe-gross)

Design Electrical Rating: 1120 (MWe-net)

Max Dependable Capacity (MWe-net): NOT DETERMINED 3.

Power Level to Which Restricted (If Any):

1055 (MWe-net) 4.

Reasons for Restriction (If Any): Steam Generator Split Flow. (65 MW)

THIS MONTH YR TO DATE CUMULATIVE

  • 5.

Report Period Hrs.

744 3193 3193 6.

Rx Critical Hours 250.1 2329.2 2329.2 7.

Rx Reserve Shutdown Bours 0

0 0

8.

Hours Generator on Line 237.4 2280.4 2280.4 9.

Unit Reserve Shutdown Hours 0

0 0

10. Gross Thermal Energy (MWH) 347977 6472163.4 6472103.4
11. Gross Elec. Energy (MWH) 108548 2104311 2104311
12. Net Elec. Energy (MWH) 91060 1970901 1970901
13. Reactor Service Factor 33.6 72.9 72.9
14. Reactor Availability Factor 33.6 72.9 72.9
15. Unit Service Factor 31.9 71.4 71.4
16. Unit Availability Factor 31.9 71.4 71.4
17. Unit Capacity Factor (MDC net)

N/A N/A N/A

18. Unit Capacity Factor (DER net) 10.9 55.1 55.1
19. Unit Forced Outage Hrs.

0 288 288

20. Unit Forced Outage Rate 0

11.2 11.2

21. Shotdowns Scheduled Over Next 6 Months:
22. If Shutdown at End of Report Period, Estimated D2te of Startup:
23. Units in Test Status (Prior to Commercial Operation): None
  • Note - The cumulative numbers do not reflect power generated prior to commercial service.

(0625M/0062M-10)

'C.

AVERAGE DAILY UNIT POWER LEVEL DOCKET NO.:

050-455 UNIT:

Byron Two DATE:

01/10/88 COMPILED BY:

D. J. Spit::er TELEPHONE:

(8151234-5441 x2023 i

MONTH: December, 1987 DAY AVERAGE DAILY POWER LEVEL (MWe-Net) 1.

O MW 16.

O MW 2.

O MW 17.

O MW 3.

O MW 18.

O MW 4.

O MW 19.

O MW 5.

O MW 20.

O MW 6.

O MW 21.

O MW 7.

O MW 22.

206 MW 0 MW 23.

277 MW 9.

O MW 24, 230 MW F

10.

O MW 25, 343 MW 11.

O MW 26, 340 MW 12.

O MW 27.

570 MW 13.

O MW

?d.

667 MW 14.

O MW 29, 901 MW i

15.

O MW 30.

317 MW t

31, 248 MW f

INSTRUCTIONS i

On this form list the average daily unit power level in MWe-Net for each day in the reporting month. Compute to the nearest whole megawatt. These figures will be used to plot a graph for each reporting month. Note that when maximum dependable capacity is used for the not electrical rating of the unit there may be occasions when the daily average power level exceeds the 100% line (or the restricted power level line.) In such cases the average daily unit power output sheet should be footnoted to explain the apparent anomaly.

(0625M/0062M-11)

~

ce*accoscucococccooococco Report Period December,1987 UNIT SHUTDOMES/REDUCTICBIS 0

BYRON o

(UNIT 2) ocococococcococcocococcoco No.

Date Type Hours Reason Method LER Number System Component Cause & Corrective Action to Prevent Recurrence 7.

12/22/87 S 506.5 H

4 Unit 2 Surveillance Outage Ends.

8.

12/30/87 F 48 H

5 Steam Generator Cation Conductivity ecocee***eeeeee Sunsnary coce***.......

TYPE Reason Method System & Component F-Forced A-Equip Failure F-Admin 1-Manual Exhibit F & H S-Sched B-Maint or Test G-Oper Error 2-Manual Scram Instructions for C-Refueling H-Other 3-Auto Scram Preparation of D-Regulatory Restriction 4-Continued Data Entry Sheet E-Operator Training 5-Reduced Load Licensee Event Report l

& License Examination 9-Other (LER) File (.WREG-0161)

(0625M/0062M-12)

'.E. UNIQUE REPORTING REQUIRDENTS (UNIT 2) fer the month cf Decimber 1987 1.

Safety / Relief valve operations for Unit Two.

VALVES NO & TYPE PIANT DESCRIPTION DATE ACTUATED ACTUATION CONDITION OF EVENT None 2.

Licensee generated changes to ODCM.

(Y/N)

No 3.

Indications of failed fuel.

(Y/N)

Yes.

I131 = 2.0E-2 pcuries/ gram (0625M/0062M-13)

0

_F. LICENSEE EVENT REPORTS (UNIT 2)

The following is a tabular summary of all Licensee Event Reports for Byron Nuclear Power Station, Unit Two, submitted during the reporting period, December 1 through December 31, 1987. This information is provided pursuant

_l to the reportable occurrence reporting requirements as set forth in 10CFR l

50.73.

Occurrence Licensee Event Repcrt Number Date Title of Occurrence 87-020-00 12/02/87 Unanticipated Water Discharge Into the RCS From the Safety Injection Accumulators Due to a Procedural Inadequacy P

t P

(0625M/0062M-14)

, ~ r, January 10, 1988 LTR:

BYRON 88-0011 File:

2.7.200 Director, Office of Management Information and Program Control United States Nuclear Regulatory Comnisalon Washington, D.C.

20555 ATTN:

Document Control Desk Gentlemen:

Enclosed for your information is the Monthly Performance Report covering Byrc.t Nuclear Power Station for the period December 1 through December 31, 1987.

Very truly yours, R. E. Querio Station Manager Byron Nuclear Power Station REQ /IA75/bb cc: