ML20195F233

From kanterella
Jump to navigation Jump to search
Corrected Pages 3/4 5-7 & 3/4 5-9 for Amends 83 & 55 to Licenses DPR-70 & DPR-75,respectively.Correction Involved Min Refueling Water Storage Tank Vol
ML20195F233
Person / Time
Site: Salem  
(DPR-70-A-083-01, DPR-70-A-83-1, DPR-75-A-055, DPR-75-A-55)
Issue date: 06/15/1988
From:
NRC
To:
Shared Package
ML20195F235 List:
References
NUDOCS 8806240251
Download: ML20195F233 (2)


Text

-

EMERGENCY CORE COOLING SYSTEMS REFUELING WATER STORAGE TANK LIMITING CONDITION FOR OPERATION 3.5.5 The refueling water storage tank (RWST) shall be OPERA 8tf with:

a.

A contained volume of between 364,500 and 400,000 of borated water.

l b.

A boron concentration of between 2,300 and 2,500 ppm, and c.

A minimum water temerature of 35'F.

APP LICAB I LITY: MO CES 1, 2, 3 and 4 ACTION:

With the refueling water storage ta.nk inoperable, restore the tank to OPERABLE status within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> or be in at least HOT STAN(BY within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUT 00WN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

SURVEILLANCE REQUIREMENTS 4.5.5 The RWST shall be demonstrated OPERABLE:

a.

At least once per 7 days by:

1.

Verifying the water level in the tank, and 2.

Verifying the boron concentration of the water.

b.

At least once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> by verifying the RWST temerature when the outside air tegerature is < 35'F.

l SALEM - UNIT 1 3/4 5-7 Amendment No. 83 8806240251 800615 PDR AEOCK 05000272 P

PDR j

. ~

3 l

EMERGENCY CORE COOLING SYSTEMS REFLE LING WATER STORAGE TANK LIMITING CONDITION FOR OPERATION 3.5.5 The refueling water storage tank (RWST) shall be OPERABLE with:

a.

A contained volume of between 364,500 and 400,000 of borated water.

(

b.

A boron concentration of between 2,300 at i 2,500 ppm, and l

c.

A minimum water temperature of 35'F.

APP LICAB I LITY: MOES 1, 2, 3 and 4.

ACTION:

l With the refueling water storage tank inoperable, restore the tank to OPERABLE i

status within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> or be in at least HOT STANCBY within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTCOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

SURVEILLANCE REQUIREMENTS 4. 5.:5 The RWST shall be demonstrated OPERABLE:

a.

At least once per 7 days by:

1.

Verifying the water level in the tank, and 2.

Verifying the boron concentration of the water.

b.

At least once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> by verifying the RWST tegerature when the outside air tegerature is < 35'F.

S A LIM - UNIT 2 3/4 5-9 Amendment No. 55