Final ASP Analysis - Millstone 2 (LER 336-77-020)
ML20168A576
Person / Time
Site: Millstone 
Issue date: 06/16/2020
From: Christopher Hunter
NRC/RES/DRA/PRB
To:
Littlejohn J (301) 415-0428
References
LER 1977-020-00
Download: ML20168A576 (4)


Text

PRECURSOR DESCRIPTION AND DATA NSIC Accession Number:

132979 Date:

August 10, 1977

Title:

Both Diesel Generator Fuel Supply Valves Found Shu~t at Millstone 2 The failure sequence was:

1. During a routine inspection with the plant in cold valves on both diesel generators were found shut.

closure was not known.

shutdown, the-fuel supply The cause of valve

2. Both fuel supply valves were reopened.

Corrective action;

1. The valve manual operators were chain locked in the open position.

Design purpose of failed system or component:

The diesel generators provide on-site emergency power for safety-related loads in the event of fsite power and the-~unit generator are unavailable.

Unavailability of system per W4ASH 140U;

  • emergency power:

3 x 10-2 /1)

Unavailability of component per WASH 1400:* diesel generators:

10-2 /D

  • Unavailabilities are in units of per demand D-1.

Failure rates are in units of per hour HR-1.

Unit in cold shut-Diesel-generator #1 Diesel-generator #2 down and plant fuel supply valve fuel supply valve inspection in found shut in found shut in progress violation of violation of procedures procedures Potential Severe Core Damage No -

unit in cold shutdown plus of fsite power available

[NO NSIC 132979 -

Actual Occurrence for Both Diesel Generator Fuel Supply Valves Found Shut at Millstone 2

Loss of Off site Power Turbine Generator Runs Back and Assumes House Loads Emer-._

gency Power Auxiliary PORV PORV or Feedwater and Demanded PORV Iso la-Secondary tion Valve Heat Removal Closure IHigh Pressure Inj ection Long Potential Term Severe Core Core Cooling Damage No Sequence No.

2 3

4 5

6 7

8 9

10 11 12 13 NSIC 132979 -

Sequence of Interest for Both Diesel-Generator Fuel Supply Valves Found Shut at Millstone 2

  • Not included in mitigation procedures.

CATEGORIZATION OF ACCIDENT SEQUENCE PRECURSORS NSIC ACCESSION NUIMER:

132979-DATE OF LER:

August 10,- 1.977 (Original report date June 14, 1977)

DATE OF EVENT:

May 15, 1977 SYSTEM'- INVOLVED:. on-site emergency.power COýONENT INVOLVED:

diesel-generators CAUSE:

fuel supply valves shut, human error SEQUENCE OF INTEREST:

loss of of fsite power ACTUAL OCCURRENCE:

fuel supply valves discovered to be. shut during an inspection-REACTOR NA11E:

Millstone 2 DOCKET NUMBER:

50-336 REACTOR TYPE:

PWR DESIGN ELECTRICAL RATING:

870 MWe REACTOR AGE:

2.0 yr VENDOR:

.Combustion Engineering ARCHITECT-ENGINEERS:

Bechtel OPERATORS:

Northeast Nuclear Energy Co.

LOCATION:

5 allea SI'tof New London, Comm.

DURATION:

180(a) hours PLANT OPERATING CONDITION:

cold shutdown SAFETY FEATURE TYPE OF FAILURE:

(a) inadequate performnance; (ba) failed to start; (Omade inoperable; (d)

DISCOVERY METHOD:

routine inspection COMIENT:

-