ML20168A562

From kanterella
Jump to navigation Jump to search
Final ASP Analysis - Indian Point 3 (LER 286-77-003)
ML20168A562
Person / Time
Site: Indian Point 
Issue date: 06/16/2020
From: Christopher Hunter
NRC/RES/DRA/PRB
To:
Littlejohn J (301) 415-0428
References
LER 1977-003-00
Download: ML20168A562 (4)


Text

PRECURSOR DESCRIPTION AND DATA NSIC Accession Number:

143219 Date: August 4, 1977

Title:

Offsite Power to Station Lost at Indian Point 3 The failure sequence was:

1. While at hot shutdown following a reactor trip, offsite power was lost due to severe electrical storms.
2. The emergency generators started and assumed required safety-related loads.

Corrective action;

1. Offaite power was restored.

Design purpose of failed system or component; Offsite power provides the preferred source of electric power for safety-related loads on this plant.

Unavailability of system per WASH 140G:

  • offsite power:

2 x 10-5 /hr Unavailability of component per WASH 1400:*

Unavailabilities are in units of per demand D-1.

Failure rates are in units of per hour HR-1.

Potential Severe Core Damage No No Yes No NSIC 143219 -

Actual Occurrence for Loss of Offsite Power at Indian Point 3

Loss of Turbine Emer-Auxiliary PORV PORV or High Long Offsite Generator gency Feedwater and Demanded PORV Isola-Pressure Term Power Runs Back Power Secondary tion Valve Injection Core and Assumes Heat Removal Closure Cooling House Loads Potential Severe Core Damage Sequence No.

2 3

4 5

6 7

8 9

10 11 12 13 NSIC 143219 -

Sequence of Interest for Loss of Offsite Power at Indian Point 3 not included in mitigation procedures.

CATEGORIZATION OF ACCIDENT SEQUENCE PRECURSORS NSIC ACCESSION NUMBER:

143219 DATE OF LER: August 4, 1977 DATE OF EVENT:

July 13, 1977 SYSTEM INVOLVED:

Offsite power COMPONENT INVOLVED:

Transmission network CAUSE:

Severe electrical storms SEQUENCE OF INTEREST:

Loss of off site power ACTUAL OCCURRENCE:

Loss of offsite power REACTOR NAME:

Indian Point 3 DOCKET NUMBER:

50-286 REACTOR TYPE:

PWR DESIGN ELECTRICAL RATING:

965

.MWe REACTOR AGE:

1.8 yr VENDOR:

Westinghiouse ARCHITECT-ENGINEERS:

United Engineers & Constructors OPERATORS:

Consolidated Edison Co. of New York LOCATION:.25 -amIle. -se~t" of New York, NY DURATION:

N/A PLANT OPERATING CONDITION:

Hot shutdown SAFETY FEATURE TYPE OF FAILURE:

(a) inadequate performance; (b) failed to start; e

made inoperable; (d)

DISCOVERY METHOD:

During operation COMMENT:

-