ML20168A554

From kanterella
Jump to navigation Jump to search
Final ASP Analysis - Hatch 1 (LER 321-76-088)
ML20168A554
Person / Time
Site: Hatch 
Issue date: 06/16/2020
From: Christopher Hunter
NRC/RES/DRA/PRB
To:
Littlejohn J (301) 415-0428
References
LER 1976-088-00
Download: ML20168A554 (4)


Text

PRECURSOR DESCRIPTION AND DATA NSIC Accession Number:

120293 Date:

November 11, '1976

Title:

Plant Service Water Strainers Plug at Hatch 1 The failure sequence was:

1. While operating at 85% power, both division I and II service water strainers plugged, thus reducing the plant service water to the turbine and Reactor building. The strainer drive motors had failed.

Corrective action:

The strainers were manually back flushed twice per shift until the drive motors were repaired.

Design purpose of failed system or component:

the drive motors power the pumps that keep the service water strainers clean.

Unavailability of system per WASH 1400: *High Pressure Service Water:

1.1 X 1lO4 Unavailability of component per WASH 1400: *Pumps failure to run:

3 x lO-5IHr Unavailabilities are in units of per demand D-1.

Failure rates are in units of per hour 1R-1.

Reactor Operating Operator Receives an Strainers are Manually Backflushed at 85% Power Alarm that Both Serý-.

Twice Per Shift Until Motors are vice Water Strainers Repaired are Plugged Potential Severe Core Damage No No No NSIC 120293 -

Actual Occurrence of Plant Service Water Strainers Plug at Hatch 1

Loss of Reactor jOffsite Scram Power I

Diesel Start and Load Reactor Made Sub-critical by the SBLCS Or Rods Are Manually Driven In RCIC/HPCI ADS/LPCI Long Potential Initiates CS Trerm Severe Initiates Core Core Cooling Damage r

No Yes No Yes Yes No (C 0)

Yes Yes No Yes No Yes Yes Yes Yes Sequence No.

1 2

3 4

5 6

7 8

9 10 11 12 13 14 15 NSIC 120293 -

Sequence of Interest of Plant Service Water Strainers Plug at Hatch 1

CATEGORIZATION OF ACCIDENT SEQUENCE PRECURSORS NSIC ACCESSION NUMBER: 120293 DATE OF LER: November 11, 1970 DATE OF EVENT:

Unknown SYSTEM INVOLVED:

Service Water COMPONENT INVOLVED:

Strainers CAUSE: Plugging SEQUENCE OF INTEREST: 'LOOP ACTUAL OCCURRENCE:

Plant Service Water Strainers Plug at Hatch 1 REACTOR NAME:

Hatch 1 DOCKET NUMBER: 50-321 REACTOR TYPE:

BWR DESIGN ELECTRICAL RATING:

777 ilWe REACTOR AGE:

2.2 yr VENDOR:

General Electric ARCHITECT-ENGINEERS:

Southern Services OPERATORS:

Georgia Power LOCATION:

Eleven miles N of Baxley, GA DURATION:

12.(a) hours PLAN~T OPERATING CONDITION:

85%

SAFETY FEATURE TYPE OF FAILURE: (,W,,inadequate performance; (b) failed to start; Q)ade inoperable; (d)_____________

DISCOVERY METHOD:

COMMENT: