Final ASP Analysis - Calvert Cliffs 1 (LER 317-79-031)
ML20168A446
Person / Time
Site: Calvert Cliffs 
Issue date: 06/16/2020
From: Christopher Hunter
NRC/RES/DRA/PRB
To:
Littlejohn J (301) 415-0428
References
LER 1979-031-00
Download: ML20168A446 (4)


Text

B-675 PRECURSOR DESCRIPTION AND DATA NSIC Accession Number:

152835 Date:

July 31, 1979

Title:

Engineered Safety Features Actuation System Failed at Calvert Cliffs 1 The failure sequence was:

1. With the reactor at power, trouble-shooting was in progress regarding a fault in the ESFAS Under-voltage (UV) "A" logic circuitry.
2. Both the ESFAS Channel A and B UV Actuation Cabinet Power Supplies were found dc-energized due to a trip of the power supply overvoltage protection circuitry.

Corrective action:

1. The power supplies were reset.
2. The over-voltage trip setpoints were raised to prevent future inadvertant trips.
3. Testing was in progress to determine if any common-mode interrelationships existed between the two channels.

Design purpose of failed system or component:

1. The UV Actuation Circuitry sends start commands to the diesel generator and sequencer in the event of a loss of offsite power.

Unavailability of system per WASH 1400:

  • Under voltage trip, not specifically addressed; Safety Injection Control System total failure:

5.4 x 10 5 /D Unavailability of component per WASH 1400:*

Unavailabilities are in units of per demand D_1.

Failure rates are iii Units of per hour HR-1

Reactor at Power ESFAS Actuation Channels Potential and ESFAS Under A and B UV Power Supply Severe Voltage (UIV) Logic Over-voltage Protection Core Circuit Trouble Found Actuated, Rendering Damage Shooting in Progress ESFAS Unable to Actuate on UIV No -

no requirement for ESFAS actuation

__-No

-4 NSIC 152835 -

Actual Occurrence for Engineered Safety Features Actuation System Failed at Calvert Cliffs 1

Loss of1 Offs ite Power Turbine Generator Runs Back and Assumes House Loads Emer-gency Power Auxiliary Feedwater and Secondary Heat Removal PORV PORV or High Long Potential 1Demanded PORV Isola-Pressure Term jSevere tion Valve Injection Core Core

]Closure CoolingJDamage Sequence No.

2 3

4 5

6 7

8 9

10 11 12 13

-4 NSIC 152835 -

Sequence of Interest for Engineered Safety Features Actuation System Failed at Calvert Cliffs 1

B-678 CATEGORIZATION OF ACCIDENT SEQUENCE PRECURSORS NSIC ACCESSION NUMBER:

152835 DATE OF LER:

August 14, 1979 DATE OF EVENT:

July 31, 1979 SYSTEM INVOLVED:

Engineered Safety Features Actuation System COMPONENT INVOLVED:

Under-Voltage Actuation Cabinet Power Supplies CAUSE:

De-energized due to trip of over-voltage protection circuitry.

SEQUENCE OF INTEREST:

LOOP ACTUAL OCCURRENCE. Over-voltage protection trip detected during trouble-shooting REACTOR NAMEz Calvert Cliffs 1 DOCKET NUbMBER :50-317 REACTOR TYPE:

PWR DESIGN ELECTRICAL RATING:

845 MWe REACTOR AGE:

4.8 yr VENDOR. Combustion Engineering ARCHITECT-ENGINEERS:

Bechtel OPERATORS:

Baltimore Gas & Electric Co.

LOCATION:

40 miles south of Annapolis, MD DURATION:

7.5 hours5.787037e-5 days <br />0.00139 hours <br />8.267196e-6 weeks <br />1.9025e-6 months <br /> PLANT OPERATING CONDITION:

At power SAFETY FEATURE TYPE OF FAILURE:

(a) inadequate performance; (b) failed to start; 0

made inoperable; (d)___________

DISCOVERY METHOD:

During troubleshooting of UV logic cir~uits COMMENT:

-