ML20168A445

From kanterella
Jump to navigation Jump to search
Final ASP Analysis - Calvert Cliffs 1 (LER 317-78-020)
ML20168A445
Person / Time
Site: Calvert Cliffs 
Issue date: 06/16/2020
From: Christopher Hunter
NRC/RES/DRA/PRB
To:
Littlejohn J (301) 415-0428
References
LER 1978-020-00
Download: ML20168A445 (4)


Text

PRECURSOR DESCRIPTION AND DATA NSIC Accession Number:

137543 Date:

April 13, 1978

Title:

Diesel Generator Fails to Start Following a Loss of All Offeite Power at Calvert Cliffs 1 The failure sequence was:

1. With the plant shutdown, switchyard breaker protective relaying automatically opened the switchyard breakers, resulting in a loss of offsite power.
2. Diesel generator 11 failed to start.
3. Diesel generator 12 started and provided power to safety-related loads.

Corrective action:

None -

the cause of the diesel-generator failing to start was not determined.

Design purpose of failed system or component:

1. Off site power provides the preferred source of power to safety-related equipment when the unit generator is not operating.
2. The diesel-generators provide a standby source of power to safety related loads when neither the unit generator nor offsite power is available.

Unavailability of system per WASH 1400:

  • off site power:

2 x 10-5/hr onsite power:

1 X 10 2/1)

Unavailability of component per WASH 1400:

  • diesel generator: 3 x 10-'/D Unavailabilities are in units of per demand D-1.

Failure rates are in units of per hour HR-1

With the Reactor Diesel-Generator 11 Diesel-Generator 12 Shutdown, Switchyard Fails to Start Starts and Provides Breaker Protection Power to Safety-Relaying Automatically Related Loads Opened Breakers, Resulting-in a Loss of Off site Power Potential Severe Core Damage

-No - steam driven auxiliary feedwater system available for reactor cooling at RCS temperatures above n,25OPF.

NSIC 137543 - Actual Occurrence for Diesel Generator Fails to Start Following a Loss of All Offaite Power at Calvert Cliffs 1

L~,ss of Turbine Emer-Auxiliary PORV PORV or High Long Offsite Generator gency Feedwater and Demanded PORV Isola-Pressure Term Power Runs Back Power Secondary Ition Valve Injection Core and Assumes Heat Removal Closure Cooling House Loads Severe Core Damage Sequence No.

2 3

4 5

6 7

8 9

10 11 12 13 NSIC 137543 -

Sequence of Interest for Diesel Generator Fails to Start Following a Loss of All Off site Power at Calvert Cliffs 1 Not included in mitigation procedures.

CATEGORIZATION OF ACCIDENT SEQUENCE PRECURSORS NSIC ACCESSION NUMBER:

137543 DATE OF LER: April 14, 1978 DATE OF EVENT:

April 13, 1978 SYSTEM INVOLVED:

off site power, onsite power COMPONENT INVOLVED: diesel generator CAUSE:

failure to start SEQUENCE OF INTEREST:

loss of off site power ACTUAL OCCURRENCE:

loss of offsite power while shutdown REACTOR NAME:

Calvert Cliffs 1 DOCKET NUMBER:

50-317 REACTOR TYPE:

PWR DESIGN ELECTRICAL RATING:

845 MWe REACTOR AGE:

3.5 yr VENDOR:

Combustion Engineering ARCHITECT-ENGINEERS:

Bechtel OPERATORS:

Baltimore Gas & Electric Co.

LOCATION:

40 miles south of Annapolis, Nd.

DURATION:

N/A PLANT OPERATING CONDITION:

shutdown SAFETY FEATURE TYPE OF FAILURE:

(a) inadequate perfornance;(afailed to start; (c) made inoperable; (d)

DISCOVERY METHOD:

during operation COMMENT:-