ML20160A065

From kanterella
Jump to navigation Jump to search
2 to Updated Final Safety Analysis Report, Chapter 6, Engineered Safety Features
ML20160A065
Person / Time
Site: Beaver Valley
Issue date: 05/20/2020
From:
Energy Harbor Nuclear Corp
To:
Office of Nuclear Reactor Regulation
Shared Package
ML20160A057 List:
References
L-20-051
Download: ML20160A065 (163)


Text

{{#Wiki_filter:BVPS UFSAR UNIT 1 Rev. 23 6-1 SECTION 6 ENGINEERED SAFETY FEATURES TABLE OF CONTENTS Section Title Page 6.1 GENERAL DESCRIPTION 6.1-1 6.2 EQUIPMENT - DESIGN AND CRITERIA 6.2-1 6.2.1 Pumps and Valves 6.2-1 6.2.2 Piping 6.2-1 6.2.2.1 Definition of Piping Classifications 6.2-2 6.2.2.2 Protection of Class I Piping 6.2-3 6.2.3 Motors 6.2-4 6.2.3.1 Motors Located Outside the Containment 6.2-4 6.2.3.2 Motors Located Inside the Containment 6.2-4 6.2.4 Ventilation 6.2-4 6.3 EMERGENCY CORE COOLING SYSTEM 6.3-1 6.3.1 Design Bases 6.3-1 6.3.1.1 Performance Objectives 6.3-1 6.3.1.2 ECCS Single Failure Criterion 6.3-2 Compliance 6.3.1.3 Codes and Classifications 6.3-4 6.3.2 System Design and Operation 6.3-4 6.3.2.1

System Description

6.3-4 6.3.2.2 Components 6.3-7 6.3.2.3 Electrical Supply 6.3-17 6.3.2.4 Protection Against Dynamic Effects 6.3-17 6.3.2.5 Environmental Effects Protection 6.3-18 6.3.3 Desiqn Evaluation 6.3-18 6.3.3.1 Range of Core Protection 6.3-18 6.3.3.2 Borated Water Injection Chemistry 6.3-20 6.3.3.3 System Response 6.3-20 6.3.3.4 Single Failure Analysis 6.3-21 6.3.3.5 Reliance on Interconnected System 6.3-23 6.3.3.6 Normal/Accident Function Evaluation 6.3-23 6.3.3.7 Passive Systems 6.3-24 6.3.3.8 External Recirculation Loop Leakage 6.3-25 6.3.3.9 Pump NPSH Requirements 6.3-25 6.3.4 Inspections and Tests 6.3-28 6.3.4.1 Inspection 6.3-28 6.3.4.2 Tests 6.3-28 6.4 CONTAINMENT DEPRESSURIZATION SYSTEM 6.4-1 6.4.1 Design Bases 6.4-1

BVPS UFSAR UNIT 1 Rev. 23 6-2 TABLE OF CONTENTS (CONTD) Section Title Page 6.4.2 Description 6.4-1 6.4.3 Evaluation 6.4-8 6.4.4 Tests and Inspections 6.4-14 6.5 POST DBA HYDROGEN CONTROL SYSTEM 6.5-1 6.5.1 Hydrogen Recombiner and Purge System 6.5-1 6.5.2 Containment Hydrogen Analyzer System 6.5-1 6.6 SUPPLEMENTARY LEAK COLLECTION AND 6.6-1 RELEASE SYSTEM 6.6.1 Desiqn Bases 6.6-1 6.6.2 Description 6.6-1 6.6.3 Evaluation 6.6-3 6.6.4 Tests and Inspections 6.6-4

BVPS UFSAR UNIT 1 Rev. 23 6-3 LIST OF TABLES Table Title 6.2-1 Summary of Required Examination and Tests for Nuclear Piping 6.2-2 Drawings Showing Piping Class Information 6.3-1 Single Active Failure Analysis ECCS 6.3-2 ECCS - Code Requirements 6.3-3 Readouts on the Control Board Which Operator Can Monitor During Injection Phase 6.3-4 Quality Standards of ECCS Components 6.3-5 Accumulator Design/Operating Parameters 6.3-6 Tank Data 6.3-7 Pump Parameters 6.3-8 ECCS Relief Valve Data 6.3-9 Nominal (Design) External Recirculation Loop Leakage (Safety Injection System Only) 6.3-10 Relocated to Table 6.2-1 6.3-11 Table of Fault Probabilities 6.3-12 Normal/Accident Functions Evaluation 6.3-13 Accumulator Inleakage 6.4-1 Quench Spray Subsystem Component Design Data 6.4-2 Component Design Data for the Recirculation Spray Subsystems 6.4-3 Consequences of Component Malfunctions in the Containment Depressurization System 6.4-4 Recirculation Spray Subsystem Leakage 6.4-5 Deleted

BVPS UFSAR UNIT 1 Rev. 22 6-4 LIST OF TABLES (CONTD) Table Title 6.5-1 Deleted 6.6-1 Supplementary Leak Collection and Release System - Design Data

BVPS UFSAR UNIT 1 Rev. 20 6-5 LIST OF FIGURES Figure Title 6.1-1 Engineered Safety Features Systems 6.3-1 Safety Injection Accumulators 6.3-2 (Deleted) 6.3-3 (Deleted) 6.3-4 (Deleted) 6.3-5 Performance Curve, Low Head Safety Injection Pump 6.3-6 (Deleted) 6.3-7 Fault Tree for Inadvertent Closure of One Normally Open ECCS Motor Operated Valve 6.3-8 Safety Injection System (Injection Mode) 6.3-9 Safety Injection System (Recirculation Mode) 6.3-10 Available NPSH for LHSI Pump, Pump Suction DER - Min. ESF 6.4-1A Containment Depressurization System Quench Spray Subsystem 6.4-1B Containment Depressurization System Recirculation Spray Subsystem 6.4-2 Containment Sump Screen 6.4-3 Typical - General Structural and Piping Arrangement Recirculation Spray and Low Head Safety Injection Systems Outside the Reactor Containment 6.4-4 Recirculation Cooler (Typical) Shell and Tube Design - Countercurrent Flow 6.4-5 (Deleted) 6.4-6 (Deleted)

BVPS UFSAR UNIT 1 Rev. 19 6-6 LIST OF FIGURES (CONTD) Figure Title 6.4-7 (Deleted) 6.4-8 Spray Patterns in Containment 6.4-9 Air Motion Induced by Recirculation Sprays 6.4-10 Available NPSH for Recirc Spray Pump, Hot Leg DER - Maximum ESF 6.6-1 Supplementary Leak Collection Release System

BVPS UFSAR UNIT 1 Rev. 27 6.1-1 SECTION 6 ENGINEERED SAFETY FEATURES 6.1 GENERAL DESCRIPTION The engineered safety features (ESF), together with the containment system (Section 5), serve as protection to the public in the unlikely event of a loss-of-coolant accident (LOCA). The ESF are designed to minimize the effects of a LOCA by performing five functions:

1.

To supply borated water to the reactor coolant system (RCS) to cool the core, decrease reactivity, limit fuel rod cladding temperatures and metal-water reaction and ensure that the core remains intact.

2.

To eliminate the driving potential (differential pressure) for leakage out of the containment.

3.

To reduce the concentration of airborne fission products in the containment available for leakage.

4.

To reduce the dose at the site boundary from any airborne fission products which leak from the containment.

5.

To control the buildup in the containment of an explosive mixture of hydrogen and oxygen, by mixing of the containment atmosphere. The first function is satisfied by the timely, continuous and adequate supply of borated water to the RCS and the reactor core. The second function is satisfied by the provision of:

1.

Heat sinks for the condensation of steam released inside the containment

2.

Depressurization of the containment following any LOCA

3.

Means for maintaining the containment at near atmospheric conditions for an extended period of time. The third function is satisfied by providing containment sump pH control: a chemical additive (sodium tetraborate decahydrate, denoted as NaTB) is provided for dissolution and transfer to the containment sump and recirculation spray to enhance the removal of radioactive iodine from the containment atmosphere in the event of a LOCA. The fourth function is provided by exhausting various areas contiguous to the containment to an elevated release point on top of the containment. The fifth function is satisfied by the containment depressurization system which provides the capability to thoroughly mix the containment atmosphere.

BVPS UFSAR UNIT 1 Rev. 27 6.1-2 The ESF systems provided for satisfying these functions are:

1.

A safety injection system, which injects borated water into the reactor coolant loops (Section 6.3).

2.

Two separate low pressure safety injection subsystems which provide long term reactor core decay heat removal (Section 6.3).

3.

The separate subsystems of the containment depressurization system (the quench spray subsystems and the recirculation spray subsystems) which, when operating together, reduce the containment pressure and temperature, remove heat from the containment and promote a mixed atmosphere required by 10 CFR 50.44. The recirculation spray subsystems transfer the heat from the containment to the river water system. A chemical additive (NaTB) provided for dissolution and transfer to the containment sump and recirculation spray subsystem reduces the concentration of airborne fission products in the containment (Section 6.4).

4.

The supplementary leak collection and release system, which normally exhausts the structures contiguous to the containment (except the main steam valve cubicle), the fuel building and the waste gas shortage area to an elevated release point. Following a DBA or a waste gas storage accident, the exhaust from these areas is diverted to a filter prior to being discharged at the elevated release point (Section 6.6). The filters are not credited in the radiological analysis. A composite schematic of the ESF systems is shown in Figure 6.1-1. The safety injection system provides for the injecting of borated water to the RCS from the accumulators following a LOCA. The three accumulators are self contained and are designed to supply water as soon as the RCS pressure drops below accumulator pressure. Continued makeup is provided by the charging pumps and the low head safety injection pumps. Both the charging and low head safety injection pumps are located outside the containment and are electric motor-driven, capable of being energized and operated rapidly and powered by the emergency buses. The pumps also ensure an adequate supply of borated water for an extended period of time by recirculation of the water from the containment sump to the reactor core through two entirely separate flow paths. The quench spray subsystems supply chilled borated water from the refueling water storage tank to the containment shortly after receipt of the containment isolation phase B (CIB) signal. The systems include two 100 percent design capacity electric motor-driven quench spray pumps which are located outside the containment and are supplied with power from the emergency buses.

BVPS UFSAR UNIT 1 Rev. 27 6.1-3 Containment sump pH control consists of six covered metallic buffer baskets filled with a predetermined quantity of NaTB, mounted to the containment basement floor. The baskets are designed to allow dissolution of the NaTB buffer as a result of contact with water released from a RCS break inside containment and from the quench spray subsystem. The alkalated water then passes into the containment sump where it will be absorbed into the recirculation spray subsystem upon commencement of the recirculation phase of a LOCA. The NaTB buffer baskets are passive components which increase the pH of the recirculation spray subsystem sprays to ensure effective removal and retention of radioactive iodine from the containment atmosphere following a LOCA. The baskets are periodically inspected for NaTB quantity and the buffer is tested for pH-raising effectiveness. The recirculation spray subsystems recirculate the alkalated water from the containment sump through river water cooled recirculation spray coolers to the recirculation spray headers. Two 50 percent design capacity, motor-driven recirculation spray pumps are located inside the containment and two additional 50 percent design capacity, motor-driven recirculation spray pumps are located outside the containment. The recirculation spray coolers are located inside the containment and transfer containment heat to the river water system. The recirculation spray subsystems, together with the quench spray subsystems, are capable of reducing the containment pressure. The supplementary leak collection and release system has two 100 percent design capacity leak collection exhaust fans and two 100 percent design capacity main filter banks. Each main filter bank consists of roughing filters, charcoal filters and HEPA filters. The supplementary leak collection and release system normally exhausts structures contiguous to the containment, the fuel building and the waste gas storage area directly to the elevated release point without the air stream going through the filters. On a containment isolation phase A (CIA) signal, a leak collection area high-high radiation signal, a fuel building high-high radiation signal or a waste gas storage area high-high radiation signal, the exhaust from all areas served by the supplementary leak collection and release system is diverted to the filters prior to being discharged at the elevated release point. The filters are not credited in the radiological analysis. The electrical requirements of all ESF are satisfied by normal outside a-c power provided from two independent emergency buses. Highly reliable onsite power is ensured by two emergency diesel generators, should all outside power sources fail. These systems are described in Section 8. All engineered safety features can be manually operated from the main control room. The minimum ESF equipment which can be started under emergency power conditions are:

1.

One charging pump

2.

One low head safety injection pump

3.

Two recirculation spray pumps

4.

One quench spray pump

5.

One leak collection exhaust fan

BVPS UFSAR UNIT 1 Rev. 27 6.1-4 An evaluation of these systems under various accident conditions is presented in Section 14.3. Routine periodic testing of the ESF components is performed as discussed under the individual systems and in the Technical Specifications. Components of the ESF system are located in accessible areas for periodic visual inspection. All ESF components (including duct work and piping) are designed as Seismic Category I (Appendix B).

BVPS UFSAR UNIT 1 Rev. 22 6.2-1 6.2 EQUIPMENT - DESIGN AND CRITERIA The containment depressurization system, emergency core cooling system (ECCS) and supplementary leak collection and release system are designed, fabricated, inspected and installed to meet the requirements as set forth by the applicable AEC General Design Criteria (Section 1.3.2 and Appendix lA). The above systems are considered to be essential to the prevention and/or mitigation of consequences of accidents which could affect the public health and safety. 6.2.1 Pumps and Valves The safety classes and codes to which pumps and valves are designed are indicated in individual subsections. All welding and nondestructive testing performed on the pumps and valves are performed by personnel meeting the requirements of the American Society for Mechanical Engineers (ASME) Boiler and Pressure Vessel Code, Section IX, and the American Society of Nondestructive Testing Specification SNT-TC-lA. Valve packings are selected to minimize or eliminate leakage where necessary. For motor operated valves, the operators are selected to ensure reliable operation under accident conditions. Periodic testing and inspections of the engineered safety features subsequent to installation supplement the design and fabrication criteria specified above. This testing and inspection is discussed in an individual section on each system and in the Technical Specifications. 6.2.2 Piping Piping fabrication, installation and testing was in accordance with American National Standards Institute (ANSI) B31.1-1967(1), with supplemental requirements as necessary for use in nuclear applications. These are listed in Table 6.2-1. Pipe routing and supports are such that missiles generated from postulated events or the effects of loss-of-coolant accidents do not impair or adversely affect the operation of the containment depressurization system, the emergency core cooling system, and the supplementary leak collection and release system. The inservice inspection requirements for piping are controlled under the BVPS Inservice Inspection Plan in accordance with 10 CFR 50.55a(g). Stresses and reaction forces/moments of piping and supports are computed for thermal gradients under normal conditions, with and without friction on sliding supports. The piping stress analysis work carried out on the BVPS-1 also includes these calculations under accident conditions. In addition, after the completion of a dead load hanger analysis, a dynamic study is made. Seismic loads are then calculated from the equivalent static loads and combined moments determined from the previously established dead load and pressure figures. All Seismic Category I systems are subjected to dynamic analysis (Appendix B.2.1).

BVPS UFSAR UNIT 1 Rev. 20 6.2-2 6.2.2.1 Definition of Piping Classifications The classifications listed below determine the fabrication, inspection and documentation requirements in the procurement and erection of piping. It should be noted that Table B.1-1 in Appendix B lists structures, systems and components which are safety related and which, therefore, are designed for seismic loadings. Some piping which would be identified from the following listing as Class II or III for fabrication, inspection and documentation purposes is identified as Seismic Category I for seismic design purposes in accordance with Appendix B. The following definitions are intended to require computations, inspection and documentation consistent with the severity of the service. The definition of Class I conforms with the requirements stated in the Federal Register(2). Line numbers on piping drawings for "Nuclear" systems will have a suffix, Q1, Q2 and Q3 to indicate the line's appropriate piping class. For a list of piping drawings that show piping class information see Table 6.2-2. Portions of systems which have no nuclear safety related function which may contain radioactive fluids and whose postulated failure would not result in conservatively calculated potential offsite dose that exceed 0.5 rem (in accordance with Regulatory Guide 1.26) to the whole body or its equivalent to any part of the body may be excluded from Q1, Q2 and Q3 classifications detailed below. Portions of systems which are not required to meet functional requirements (i.e., test lines) and are normally isolated from the system may be excluded from the following Ql, Q2 and Q3 classifications: Piping Class I (Ql) This classification encompasses the reactor coolant system and portions of auxiliary systems and emergency core cooling systems connected to the reactor coolant system. For piping of those auxiliary systems and emergency core cooling systems which penetrate containment, the piping Class I boundary extends to and includes the first containment isolation valve outside the containment capable of external actuation (simple check valves are excluded). For piping of those auxiliary systems which contain two valves, both of which normally are closed during normal operation, the piping Class I boundary extends to and includes the second of these valves. This second valve (excluding simple check valves) must be capable of external actuation, whether or not the system piping penetrates the containment. For piping of those emergency core cooling systems which does not penetrate the containment, the piping Class I boundary extends to and includes the second of two valves normally closed during normal operation. For piping of those auxiliary systems and emergency core cooling systems which contain a relief or safety valve, the piping Class I boundary extends to and includes the relief or safety valve. Piping Class II (Q2) This classification encompasses the following:

1.

Residual heat removal system

2.

Reactor coolant letdown and charging portions of chemical and volume control system

3.

Portions of the emergency core cooling and containment depressurization systems that may recirculate reactor coolant

BVPS UFSAR UNIT 1 Rev. 20 6.2-3

4.

Portions of the main steam and feedwater systems extending from and including the secondary side of the steam generator up to and including the outermost containment isolation valves and connected piping up to and including the first isolation valve

5.

Those portions of any other system used to effect isolation of containment Piping Class III (Q3) This classification encompasses the following:

1.

Chemical and volume control system including piping from boric acid tanks to charging pumps but excluding portions defined above as Class II and portions defined as QA Category II in accordance with Appendix A, "Quality Assurance."

2.

Containment depressurization system excluding those portions covered in Class II

3.

Accumulator and refueling water supply subsystems of the emergency core cooling system

4.

Auxiliary feedwater system

5.

Portions of the component cooling and river water systems that transfer heat from systems for emergency core cooling, containment depressurization, residual heat removal and reactor coolant letdown

6.

Vents and drains from Class I and Class II systems (except portions defined as QA Category II in accordance with UFSAR Appendix A, Quality Assurance)

7.

Any portion of primary plant not classified as Class I or II

8.

The reactor vessel flange leak detection lines up to and including valve SOV-RC-544. 6.2.2.2 Protection of Class I Piping Class I piping systems are protected from damage due to whipping pipe from other systems by one of the following methods:

1.

Class I pipe and equipment are shielded by a protective wall or enclosure

2.

Class I pipe and equipment are separated from non-Class I systems that could cause damage by a distance that is sufficient to prevent damage. Where a Class I system cannot be protected as in 1 or 2 above from a non-Class I system, the portion of the non-Class I system that threatens the Class I system is reclassified to Class I and is designed to the following criteria:

1.

Failure of the piping is precluded due to conservative piping, hanger and support design

BVPS UFSAR UNIT 1 Rev. 24 6.2-4

2.

In the unlikely events of severance of a pipe, the pipe restraints are so placed that whipping is impossible, or, if that is impractical, so that the maximum length of whipping pipe is of a length that is insufficient to reach the systems being protected. 6.2.3 Motors 6.2.3.1 Motors Located Outside the Containment Motor electrical insulation systems are in accordance with ANSI, Internal Electronic and Electrical Engineers (IEEE) and National Electrical Manufacturers Association (NEMA) standards and are tested as required by these standards. Temperature rise design is selected such that normal long life is achieved even under accident loading conditions. Periodic electrical insulation tests will be made during the lifetime of the equipment to detect deterioration, if any, of the insulation system. 6.2.3.2 Motors Located Inside the Containment The motors are selected to ensure operation during DBA conditions. Motor electrical insulation systems are in accordance with ANSI, IEEE and NEMA standards. The motors are tested as required by these standards. Winding insulation systems are provided which can operate at temperatures in excess of those calculated to occur under DBA conditions. Prototype tests are performed on each motor type required for operation after a DBA. Periodic electrical insulation tests will be made during the life of the equipment to detect any deterioration of the insulation to ensure that motors remain in a reliable operating condition. 6.2.4 Ventilation Safeguards areas are ventilated by a cooled recirculation type ventilation system designed to limit ambient air temperature buildup and to provide suitable environment for personnel and equipment. An exhaust system for these rooms is provided by the supplementary leak collection and release system described in Section 6.6. Engineered safety features equipment contained in the ventilated spaces includes the outside recirculation spray pumps, low head safety injection pumps, auxiliary feedwater pumps and quench spray pumps. Design air rates are based on maintaining a maximum space temperature of 120 F when the pumps are running.

BVPS UFSAR UNIT 1 Rev. 19 References for Section 6.2 1. "ANSI Power Piping Code", ANSI B31.1-1967, The American National Standards Institute. 2. Federal Register, Vol. 34, No. 226, Tuesday, November 25, 1969 - p. 18823. 6.2-5

BVPS UFSAR UNIT 1 Rev. 22 6.3-1 6.3 EMERGENCY CORE COOLING SYSTEM 6.3.1 Design Bases 6.3.1.1 Performance Objectives The design bases for the emergency core cooling system (ECCS) are:

1.

To protect the station personnel and the public by maintaining clad integrity, thus minimizing the release of fission products from the fuel during the unlikely event of a loss-of-coolant accident (LOCA).

2.

To protect the core for a range of possible mishaps, evaluated as less unlikely, thereby, minimizing financial loss and loss of power generation capability. The ECCS is designed to cool the reactor core, as well as to, provide additional shutdown capability following initiation of the following accident conditions:

1.

Pipe breaks and spurious relief or safety valve lifting in the reactor coolant system (RCS) which cause a discharge larger than that which can be made up by the normal system, up to and including the instantaneous circumferential rupture of the largest pipe in the RCS.

2.

Rupture of a control rod drive mechanism causing a rod cluster control assembly (RCCA) ejection accident.

3.

Pipe breaks and spurious relief or safety valve lifting in the steam system, up to and including the instantaneous circumferential rupture of the largest pipe in the steam system.

4.

A steam generator tube rupture. The acceptance criteria for the consequences of each of these accidents is described in Section 14 in the respective accident analyses sections. The primary function of the ECCS for the ruptures described above is to remove the stored and fission product decay heat from the core such that fuel damage, to the extent that would impair effective cooling of the core, is prevented. This implies that the core remain intact and in place, with its essential heat transfer geometry preserved. To ensure effective cooling of the core, limits on peak clad temperature and local metal-water reaction, as defined in Section 14, will not be exceeded. For any rupture of a steam pipe and the associated uncontrolled heat removal from the core, the ECCS will perform such that:

1.

In the event of an uncontrolled steam release resulting from any single active failure in the main steam system (such as the opening with failure to close, of any single steam relief, control or bypass valve) there is no return to criticality after reactor trip.

BVPS UFSAR UNIT 1 Rev. 19 6.3-2

2.

In the event of a steam line break together with the combined effects of any single control rod remaining stuck out of the core (after reactor trip) and the most restrictive single active failure in the engineered safety features (ESF), the core shall remain in place and intact with its essential heat transfer geometry preserved. The ECCS meets the intent of 1967 AEC General Design Criteria, as noted in Section 1.3.2 and discussed below:

1.

The ECCS objectives are met even though loss of normal station power has occurred coincident with the accident.

2.

Any single active failure during injection does not prevent the accomplishment of safety injection system objectives. The ECCS meets the single failure criterion discussed in Section 1.3.1.

3.

Critical parts of the ECCS and of the RCS may be physically inspected.

4.

Active components of the ECCS may be tested periodically to ensure that each component is operable.

5.

An integrated ECCS test of active components may be performed during shutdown without introducing flow into the RCS.

6.

Maintenance outages of active components is permitted for limited periods of time.

7.

It is assumed that the highest worth control rod assembly remains stuck out of the core upon reactor trip.

8.

Components exposed to the accident environment are designed to operate in that environment for the length of time required. 6.3.1.2 ECCS Single Failure Criterion Compliance Active Failure Criteria The ECCS is designed to accept a single active failure following the incident without loss of its protective function. The system design will tolerate the failure of any single active component in the ECCS itself or in the necessary associated service systems at any time during the period of required system operations following the incident. A single active failure analysis is presented in Table 6.3-1 and demonstrates that the ECCS can sustain the failure of any single active component in either the short or long term and still meet the level of performance for core cooling. Since the operation of the active components of the ECCS following a steam line rupture is identical to that following a LOCA, the same analysis is applicable and the ECCS can sustain the failure of any single active component and still meet the level of performance for the addition of shutdown reactivity.

BVPS UFSAR UNIT 1 Rev. 24 6.3-3 Passive Failure Criteria The following philosophy provides for necessary redundancy in component and system arrangement to meet the intent of the AEC General Design Criteria on single failure as it specifically applies to failure of passive components in the ECCS. Thus, for the long term, the system design is based on accepting either a passive or an active failure. The long term is defined in Section 1.3.1. Redundancy of Flow Paths and Components for Long Term Emergency Core Cooling In the design of the ECCS, the following criteria are utilized:

1.

During the long term cooling period following a LOCA, the emergency core cooling flow paths shall be separable into two subsystems, either of which can provide minimum core cooling functions and return spilled water from the floor of the containment back to the RCS.

2.

Either of the two subsystems can be isolated and removed from service in the event of a leak outside the containment.

3.

Adequate redundancy of check valves is provided to tolerate failure of a check valve during the long term as a passive component.

4.

Should one of these two subsystems be isolated in this long term period, the other subsystem remains operable.

5.

Provisions are also made in the design to detect leakage from components outside the containment, collect this leakage and to provide for maintenance of the affected equipment. Thus, for the long term emergency core cooling function, adequate core cooling capacity exists with an open flow path removed from service whether isolated due to a leak, because of blocking of one flow path, or because failure in the containment results in a spill of the delivery of one subsystem. Subsequent Leakage from Components in Engineered Safety Features Subsystems With respect to piping and mechanical equipment outside the containment, considering the provisions for visual inspection and leak detection, leaks will be detected before they propagate to major proportions. A review of the equipment in the system indicates that the largest sudden leak potential would be the sudden failure of a pump shaft seal. Evaluation of leak rate assuming only the presence of a seal retention ring around the pump shaft showed flow less than 50 gpm would result. Piping leaks, valve packing leaks or flange gasket leaks have been of a nature to build up slowly with time and are considered less severe than the pump seal failure.

BVPS UFSAR UNIT 1 Rev. 19 6.3-4 Larger leaks in the ECCS are prevented by the following:

1.

The piping is designed in accordance with ANSI B31.1-1967(6)

2.

The seismic design for piping, equipment and supports ensures no loss of function for the Design Basis Earthquake

3.

The system piping is located within a controlled area on the site

4.

The piping system receives pressure tests and is accessible for periodic visual inspection

5.

The piping is austenitic stainless steel which, due to its ductility, can withstand severe distortion without failure. 6.3.1.3 Codes and Classifications Table 6.3-2 tabulates the codes and standards to which the ECCS components are designed. 6.3.2 System Design and Operation 6.3.2.1

System Description

Adequate emergency core cooling following a LOCA is provided by the ECCS shown in Figures 6.3-1, and 6.3-8 or 6.3-9. A simplified composite flow diagram of the entire ECCS is given as part of Figure 6.1-1, which is a composite flow diagram of the ESF. The system components operate in the following possible modes:

1.

The injection mode in which any reactivity increase following the postulated accidents is terminated, initial cooling of the core is accomplished and coolant lost from the primary system in the case of a LOCA is replenished.

2.

The recirculation mode in which long term core cooling is provided during the accident recovery period. The initiation signal for core cooling by the safety injection charging pumps and the low head safety injection pumps is the safety injection signal (SIS) which is to be actuated by any of the following:

1.

Low pressurizer pressure (two-out-of-three)

2.

High containment pressure (two-out-of-three)

3.

Low steam line pressure (two-out-of-three detectors in any one main steam line)

4.

Manual actuation (1/2).

BVPS UFSAR UNIT 1 Rev. 32 6.3-5 Injection Phase The principle components of the ECCS which provide emergency core cooling immediately following a loss of coolant are the three accumulators (one for each loop), two of the three safety injection charging pumps (which perform the charging functions during normal operations) and the two low head safety injection pumps. The safety injection charging pumps are located in the auxiliary building. The two low head safety injection pumps are located in the safeguards area alongside the containment structure. The accumulators, which are passive components, discharge into the cold legs of the reactor coolant piping when RCS pressure decreases below accumulator pressure thus ensuring rapid core cooling for large breaks. They are located inside the containment and are protected against possible missiles. The SIS opens the boron injection header isolation valves and starts the safety injection charging pumps. The accumulator isolation valves also receive the SIS, even though these valves are normally open. The safety injection charging pumps deliver borated water to the three cold legs of the reactor coolant loops during the injection phase. These pumps provide for the makeup of coolant and add negative reactivity following a small break which does not immediately depressurize the RCS to the accumulator discharge pressure. For large breaks, they start delivery through separate lines after the accumulators start their discharge. The suction of the safety injection charging pumps is diverted from their normal suction at the volume control tank to the refueling water storage tank by the SIS. The pumps feed a common injection header. The injection header contains a boron injection tank on the discharge side of the safety injection charging pumps. The safety injection charging pumps discharge is isolated by the redundant normally closed parallel boron injection tank outlet valves. The valves open upon receipt of an SIS and refueling water flows from the discharge of the safety injection charging pumps through the boron injection tank and into the RCS cold legs. For large pipe ruptures, the RCS is depressurized and voided of coolant rapidly and a high flow rate of emergency coolant is required to quickly cover the exposed fuel rods and limit possible core damage. This high flow is provided by the passive accumulators, followed by the charging pumps and the low head safety injection pumps which discharge into the cold legs of the RCS. Manual valves in the ECCS are mainly those required for maintenance, refueling or test operations. Those manual valves that, if improperly positioned, would have an adverse effect on the performance of the ECCS, are administratively controlled in the correct position. The high head safety injection/charging pump recirculation line combined isolation valve (MOV-CH373) is administratively controlled in the deenergized and locked open position to prevent spurious closure. Manual throttle valves in the injection branch lines are properly adjusted by flow tests during system start-up testing. A detailed listing of the instrumentation readouts of the main control board which the operator can monitor during the initial injection is given in Table 6.3-3.

BVPS UFSAR UNIT 1 Rev. 24 6.3-6 Valves of the safety injection systems which are remotely operated and are normally in their ready position but do not receive a SIS have their positions indicated on a common portion of the control board. At any time during operation when one of these valves is not in the ready position for injection, it is shown visually on the board. In addition, an audible alarm alerts the operator to the condition. Safety Injection Recirculation Phase After the injection operation and when low level is reached in the refueling water storage tank, the reactor coolant and the injected refueling water spilled from the break and the water from the containment depressurization system (Section 6.4) collect in the containment sump and part is returned to the RCS by the low head safety injection pump(s). The balance flows to the recirculation spray subsystems. Because the injection phase of the accident is terminated before the refueling water storage tank is completely emptied, all pipes are kept filled with water before recirculation is initiated. The extreme low level setpoint on the RWST is set such that the containment sump level will be sufficient to provide adequate NPSH for the LHSI pumps when utilizing the sump suction path. Adequate NPSH for the LHSI pumps when utilizing the RWST suction path is available at the extreme low level setpoint. Two out of the four RWST level signals coincident with a safety injection signal will automatically initiate the transfer from injection to recirculation. The transfer occurs as described in Section 6.3.3.9. If the break is large, depressurization of the RCS occurs rapidly due to the large rate of mass and energy loss through the break to the containment. For small breaks, the depressurization of the RCS by the ECCS and by the rupture during the injection phase can be augmented by secondary steam dump and auxiliary feedwater addition. Operator action to dump steam augments RCS depressurization but credit is not taken for this in the safety analysis in Section

14.

For the expected accident progression, no manual operator actions are required until after the symptoms have been diagnosed and the specific type of accident is identified. If abnormal conditions are present, the operating procedures will permit actions for feedwater and RCS temperature control prior to identification of the type of accident. The procedures also provide guidance in differentiating between the various types of accidents. When the necessary depressurization has been accomplished, the low head safety injection pumps take suction from the containment sump and return the coolant to the reactor. If depressurization of the RCS proceeds slowly, recirculation of spilled coolant can be accomplished by aligning the discharge of the low head safety injection pumps with the suction of the safety injection charging pumps. The redundant features of the ECCS recirculation loop include one pump in each of two separable and redundant trains with crossover capability at the discharge of each pump. Each pump takes suction through separate cross-connected lines from the containment sump. The design of the containment sump and piping configuration from the containment sump to the low head safety injection pumps is illustrated in Figure 6.1-1.

BVPS UFSAR UNIT 1 Rev. 32 6.3-7 After one day, the spray water collected is cold enough to reduce the temperature of the combined mass sufficiently for recirculation without flashing. All heat removal is through the recirculation spray subsystem. There are no heat exchangers in the ECCS. Those portions of the ECCS located outside of the containment which are designed to circulate, under post accident conditions, radioactively contaminated water collected in the containment meet the following requirements:

1.

Shielding to maintain radiation levels within the guidelines set forth in 10 CFR 50.67.

2.

Collection of discharges from pressure relieving devices into closed systems.

3.

Means to detect and control radioactivity leakage into the environs, to the limits consistent with guidelines set forth in 10 CFR 50.67. This criterion is met by minimizing leakage from the system. Recirculation loop leakage is discussed in Section 6.3.3. Changeover from Injection Phase to Recirculation Phase During the injection phase, the RWST level decreases to the low level set point at which time sufficient water is delivered to the containment sump via the containment depressurization system, the ECCS and from the RCS through the break to provide the required NPSH of the low head safety injection pumps to change to recirculation. The automatic transfer sequence is provided in Section 6.3.3.9. Steam Break Protection A large break of a main steam system pipe causes an uncontrolled removal of heat which rapidly cools the reactor coolant causing insertion of reactivity into the core. Compensation is provided by injection of boric acid solution from the RWST through the boron injection tank into the cold legs. This system was originally designed and installed to maintain a nominal 12 weight percent concentration of the boric acid solution in the boron injection tank. However, the boron injection tank is no longer credited as a source of borated water for the accident analysis. Therefore, the boron concentration in the boron injection tank no longer needs to be sampled. 6.3.2.2 Components All associated components, piping, structures and power supplies of the ECCS are designed to conform with Seismic Category I criteria (Appendix B). All components inside the containment are capable of withstanding or are protected from differential pressure which may occur during the rapid pressure rise to containment design pressure.

BVPS UFSAR UNIT 1 Rev. 32 6.3-8 Accumulators The accumulators are pressure vessels filled with borated water and pressurized with nitrogen gas. During normal operation, each accumulator is isolated from the RCS by two check valves in series. If the RCS pressure falls below the accumulator pressure, the check valves open and borated water is forced into the RCS. Mechanical operation of the swing-disk check valves by means of differential pressure is the only action required to open the injection path from the accumulators to the core via the cold leg. The level of borated water in each accumulator tank is adjusted remotely as required during normal station operation. Makeup water from the refueling water storage tank is added using the positive displacement hydrotest pump. Water level is reduced by draining to the primary drain transfer tank. Samples of the solution in the accumulators are taken at the sampling station for periodic checks of boron concentration. The accumulators are passive engineered safety features because the nitrogen gas pressure forces injection; no external source of power or signal transmission is needed to obtain fast acting, high flow capability when the need arises. One accumulator is connected to each of the cold legs of the RCS. The accumulators are carbon steel, clad with stainless steel and designed to ASME Boiler and Pressure Vessel Code, Section III, Class C requirements. Redundant level and pressure indicators are provided with readouts on the control board. Each channel is equipped with high and low level alarms. The margin between the minimum operating pressure and design pressure provides a range of acceptable operating conditions within which the accumulator system meets its design core cooling objectives. The band is sufficiently wide to permit the operator to minimize the frequency of adjustments in the amount of contained gas or liquid to compensate for leakage. Limiting conditions for operation and surveillance are set forth in the Technical Specifications. The accumulator design/operation parameters are listed in Table 6.3-5. Environmental qualification of ECCS equipment, inside the containment, which is required to operate following a LOCA is discussed in Section 7.3.2.1.2. The quality standards of all ECCS components are tabulated in summary form in Table 6.3-4. Boron Injection Tank The boron injection tank is constructed of carbon steel and clad with stainless steel for corrosion resistance.

BVPS UFSAR UNIT 1 Rev. 31 6.3-9 Table A.1-1 identifies the portions of the equipment employed with the BIT which are designed as Category I. The design parameters are presented in Table 6.3-6. Pumps Charging pumps, which are also used as high head safety injection pumps, supply borated water to the RCS. The pumps are of the horizontal centrifugal type, driven by electric motors. Minimum operating requirements are provided in the periodic operating surveillance tests for these pumps. Procedure references are provided to ensure a safety evaluation is performed when pump performance requirement changes could affect accident analysis assumptions. The low head safety injection pumps are a vertical centrifugal pump equipped with a turbulence limiter and anti-vortexing devices (cruciforms and grating) to reduce vortexing and a false bottom pump-can to lower pump vibrations. These pumps supply borated water to the RCS during the safety injection and recirculation mode. The head-flow curve for the low head pumps is given in Figure 6.3-5. All pressure containing parts of the pumps were chemically and physically analyzed and the results were checked to ensure conformance with the applicable ASTM specification. In addition, all pressure containing parts of the pump were liquid penetrant inspected in accordance with the ASME Boiler and Pressure Vessel Code, Section VIII, Appendix VIII. The acceptance standard for the liquid penetrant test is ANSI B31.1, Case N-10. Parts of the pump in contact with borated water are stainless steel or equivalent corrosion resistant material. The pressure containing parts of the pumps are castings conforming to ASTM A-351(7) Grade CF8 or CF8M, or equivalent.(32) Stainless steel forgings were procured per ASTM A-182(8) Grade F 304 or F 316 or ASTM A-336,(9) Class F8 or F8M, or equivalent.(32) Stainless steel plate was constructed to ASTM A-240(10) Type 304 or 316, or equivalent.(32) All bolting material conforms to ASTM A-193(11) or equivalent.(32) Materials such as weld-deposited Stellite, Chromaloy or equivalent(32) are used at points of close running clearances in the pumps to prevent galling and to ensure continued performance capability in high velocity areas subject to erosion.

BVPS UFSAR UNIT 1 Rev. 31 6.3-10 Pump design is reviewed with special attention to the reliability and maintenance aspects of the working components. Specific areas include evaluation of the shaft seal and bearing design to determine that adequate allowances have been made for shaft deflection and clearances between stationary parts. Table 6.3-7 lists the design parameters for the safety injection charging and low head safety injection pumps. Where welding of pressure containing parts was necessary, a welding procedure including joint detail was submitted for review and approval. The procedure includes evidence of qualification necessary for compliance with the ASME Boiler and Pressure Vessel Code, Section IX. This requirement also applies to any repair welding performed on pressure containing parts. The pressure containing parts of the pump were assembled and hydrostatically tested to 1.5 times the design pressure for 30 minutes. Each pump is given a complete shop performance test in accordance with Hydraulic Institute Standards. The pumps were run at design flow and head, shutoff head and three additional points to verify performance characteristics. Where NPSH was critical, this value was established at design flow by means of adjusting suction pressure. Valves All parts of valves used in the ECCS in contact with borated water are austenitic stainless steel or equivalent corrosion resistant material. The motor operators on the injection line isolation valves are capable of rapid operation. All valves required for initiation of safety injection or isolation of the system have remote position indication in the main control room. Exceptional tightness is specified for all valves and, where possible, such as instrument valves, packless diaphragm valves are used. All valves, except those which perform a control function, are provided with backseats which are capable of limiting leakage to less than one cubic centimeter per hour per inch of stem diameter, assuming no credit taken for valve packing. Those valves which are normally open are backseated. Normally closed globe valves are installed with pressure under the seat to prevent leakage of recirculated water through the valve stem packing. Relief valves are installed with pressure under the seat to prevent leakage of recirculated water through the valve stem packing. Relief valves are totally enclosed. All modulating control valves of all sizes, which are exposed to normally radioactive fluid, are provided with double-packed stuffing boxes and stem leakoff connections which are piped to the vent and drain system.

BVPS UFSAR UNIT 1 Rev. 19 6.3-11 The check valves which isolate the ECCS from the RCS are installed adjacent to the reactor coolant piping to reduce the probability of a safety injection line rupture causing a LOCA. The gas relief valves on the accumulators protect them from pressures in excess of the design value. The specified leakage across the valve disk required to meet the equipment specification and hydrotest requirements for conventional globe valves, gate valves, motor operated valves, check valves and accumulator check valves is 3 cubic centimeters per hour per inch of nominal pipe size. Motor-Operated Valves The pressure containing parts (body, bonnet and disks) of the valves employed in the safety injection system were designed according to criteria established by the ANSI B16.5(12) or Manufacturers Standardization Society Standard Practice (MSS) SP-66(13) specifications. The materials of construction for these parts were procured as per ASTM A-182, F-316(14) or A-351, Gr CF8M or CF8, or equivalent.(32) Radiographic inspection was conducted in accordance with the procedure outlined in ASTM E-94(15). Radiographic acceptance standards were outlined in ASTM E-71(16), E-186(17), or E-280(18) whichever was applicable, and meet the requirements of severity level 2 except that D, E, F and G defects were not permissible. The body, bonnet and disk were liquid penetrant inspected in accordance with ASME Boiler and Pressure Vessel Code, Section III, Paragraph N-627. When a gasket was employed, the body-to-bonnet joint was designed as per ASME Boiler and Pressure Vessel Code, Section VIII or ANSI B16.5 with a fully trapped, controlled compression, spiral wound asbestos or equivalent(32) gasket with provisions for seal welding, or of the pressure seal design with provisions for seal welding. The body-to-bonnet bolting and nut materials were procured as per ASTM A-193(11) and A-194,(19) respectively. These body-to-bonnet bolting and nut materials may have been replaced with materials equivalent(32) to the requirements of ASTM A-193(11) and A-194.(19) The entire assembled unit was hydrotested in accordance with MSS SP-61(20) with the exception that the test was maintained for a minimum period of 30 minutes. Failure of the test was cause for rejection. The seating design was of the Darling parallel disk design, the Crane flexible wedge design or the equivalent. These designs have the feature of releasing the mechanical holding force during the first increment of travel. Thus, the motor operator has to work only against the frictional component of the hydraulic unbalance on the disk and the packing box friction. The disks are guided throughout their full travel to prevent chattering and provide ease of gate movement. The seating surfaces are hard faced (Stellite No. 6 or equivalent) to prevent galling and reduce wear. The stem material was ASTM A-276(21) Type 316 condition B or precipitation hardened 17-4 PH stainless steel procured and heat treated to Westinghouse specifications or equivalent(32) stainless steel.

BVPS UFSAR UNIT 1 Rev. 19 6.3-12 These materials were selected because of their corrosion resistance, high tensile properties and their resistance to surface scoring by the packing. The valve stuffing box was designed with a lantern ring leak-off connection with a minimum of a full set of packing below the lantern ring and a maximum of one-half of a set of packing above the lantern ring; a full set of packing was defined as a depth of packing equal to 1.5 times the stem diameter. The experience with this stuffing box design and the selection of packing and stem materials has been very favorable in both conventional and nuclear power stations. The motor operator is extremely rugged. Some units incorporate a "lost motion" feature that allows the motor to come up to operating speed prior to being fully loaded. These units also have a "hammer blow" feature that allows the stem nut threads of the actuator to be impacted away from the stem threads. This is necessary for these units since the stem nut lock nut arrangement is a rigid two piece system. For units that do not incorporate the "lost motion" feature and the "hammer blow" feature, the actuator utilizes a spring compensator to alleviate excessive closing thrusts due to inertia by allowing the stem nut to indirectly float against the compensator spring pack. The valve was assembled, hydrostatically tested, seat-leakage tested (fore and back), operationally tested, cleaned and packaged as per specifications. In some cases, extension stems were used on motor-operated valves. These valves were operationally tested initially without the extension stems. The valves were then operationally tested with the extension stems, after installation in the unit. All manufacturing procedures employed by the valve supplier such as hard facing, welding, repair welding and testing were submitted to Westinghouse for approval. The following generic design requirements were applied for the originally supplied valves. These values were not based on accident analyses. For those valves which must function on the SIS, the valve operator completes its cycle from one position to another in 10 seconds maximum (for valves up to and including 8 inches) and 49 inches per minute operation (for valves over 8 inches). For all other valves in the system, (for valves up to and including 8 inches) 12 inches per minute operation and (for valves larger than 8 inches) the valve operator completes its cycle from one position to another in 120 seconds maximum. Current valve stroke time requirements listed in the Licensing Requirements Manual may differ from these values. Valves which must function against system pressure were designed such that they function with a pressure drop equal to full system pressure across the valve disk. Manual Valves The stainless steel manual globe, gate and check valves were designed and built in accordance with the requirements outlined in the motor-operated valve description above. The carbon steel valves were built to conform with ANSI B16.5. The materials of construction of the body, bonnet and disk conform to the requirements of ASTM A-105(22) Grade II, A-181(23) Grade II, A-216(24) Grade WCB or WCC, or their equivalent.(32) The carbon steel valves pass only nonradioactive fluids and were subjected to hydrostatic tests as outlined in MSS SP-61, except that the test pressure was maintained for at least 30 minutes per inch of wall thickness. Since the fluid controlled by the carbon steel valves was not radioactive, the double packing and seal weld provisions were not provided.

BVPS UFSAR UNIT 1 Rev. 19 6.3-13 Accumulator Check Valves The pressure containing parts of this valve assembly are designed in accordance with MSS SP-

66. All parts in contact with the operating fluid are of austenitic stainless steel or of equivalent corrosion resistant materials procured to applicable ASTM or Westinghouse Nuclear Energy Systems specifications. The cast pressure containing parts are radiographed in accordance with the procedure outlined in ASTM E-94. Radiographic acceptance standards are as outlined in ASTM E-71, E-186 or E-280, whichever is applicable and meet the requirements of severity level 2, except that D, E, F and G defects are not permissible. The cast pressure containing parts, machined surfaces, finished hard facings and gasket bearing surfaces are liquid penetrant inspected as per ASME Boiler and Pressure Vessel Code, Section VIII and the acceptance standard is as outlined in ANSI B31.1 Code, Case N-10. The final valve is hydrotested in accordance with MSS SP-66, except that the test pressure is maintained for at least 30 minutes. The seat leakage test is conducted in accordance with the manner prescribed in MSS SP-61, except that the acceptable leakage is three cubic centimeters per hour per inch of nominal pipe diameter.

The valves were designed with a low pressure drop configuration with all operating parts contained within the body, which eliminates those problems associated with packing glands exposed to boric acid. The clapper arm shaft was manufactured from 17-4 PH stainless steel heat treated to Westinghouse specifications or equivalent.(32) The clapper arm shaft bushings were manufactured from Stellite No. 6 or equivalent(32) hardened material. The various working parts were selected for their corrosion resistant, tensile and bearing properties. The disk and seat rings were manufactured from a forging. The mating surfaces are hard faced with Stellite No. 6 or equivalent(32) wear resistant material to improve the valve seating life. The disk is permitted to rotate, providing a new seating surface after each valve opening. The valves are intended to be operated in the closed position with a normal differential pressure across the disk of approximately 1,600 psi. The valves remain in this position, except for testing and accumulator discharge. Since the valve is not required to normally operate in the open condition, and hence be subjected to impact loads caused by sudden flow reversal, it is expected that this equipment will satisfactorily perform its required functions indefinitely with minimal maintenance. When the valve is required to function, a differential pressure of less than 25 psig will shear any particles that may attempt to prevent the valve from functioning. Although the working parts are exposed to the boric acid solution contained within the reactor coolant loop, a boric acid "freeze up" is not expected with this low a concentration. The experience derived from the check valves employed in the emergency injection systems indicate that the system is reliable and workable; check valve leakage has not been a problem. This was substantiated by the satisfactory experience obtained from operation of the Ginna Nuclear Power Plant and subsequent plants where the usage of check valves is identical to this application.

BVPS UFSAR UNIT 1 Rev. 19 6.3-14 Accumulator Isolation Valve The isolation valve at each accumulator is closed when the reactor is intentionally depressurized. The only other time the isolation valve is closed is for testing or maintenance purposes, for which a time limitation is specified in the Technical Specifications. The valve is designed to operate with full system differential pressure. For a further discussion of these valves, see Section 6.3.3.7. Accumulator check valves are tested for leakage after entry into Mode 5 during each refueling outage, prior to reactor startup. Additional accumulator check valve leakage testing may be required after other plant outages in accordance with the Technical Specifications. The check valves are tested when the RCS is pressurized with a minimum of 150 psi differential across the valves. This test confirms the seating of the disk and whether or not there has been an increase in the leakage since the last test. Upon RCS heatup following the outage, there should be no increase in leakage since increasing reactor coolant pressure increases the seating force and decreases the probability of leakage. Relief Valves The accumulator relief valves are sized to pass nitrogen at a rate in excess of the accumulator gas fill line delivery rate. The relief valves also pass water in excess of the expected leak rate, but this is not necessary because the time required to fill the gas space gives the operator ample opportunity to correct the situation. For an inleakage rate 15 times the manufacturing test rate, there are about 1,000 days before water reaches the relief valves. Prior to this, level and pressure alarms would have been actuated. Table 6.3-8 lists all of the system's relief valves with their capacities and setpoints. Leakage Limitations of Valves Exceptional tightness is specified for all valves and where possible, such as instrument valves, packless diaphragm valves are used. Normally open valves have backseats which limit leakage to less than one cubic centimeter per hour per inch of stem diameter assuming no credit for packing in the valve. Normally closed globe valves are installed with pressure under the seat to prevent stem leakage from the more radioactive fluid side of the seat. The specified leakage across the valve disk required to meet the equipment specification and hydrotest requirements is as follows:

1.

Conventional globe valves - three cubic centimeters per hour per inch of nominal pipe size

2.

Gate valves - three cubic centimeters per hour per inch of nominal pipe size

3.

Motor-operated gate valves - three cubic centimeters per hour per inch of nominal pipe size

4.

Check valves - three cubic centimeters per hour per inch of nominal pipe size; ten cubic centimeters per hour per inch for 300 and 150 lb ANSI standard.

BVPS UFSAR UNIT 1 Rev. 19 6.3-15

5.

Accumulator check valves - two cubic centimeters per hour per inch of nominal pipe size. Leakage from components of the recirculation loop including valves is tabulated in Table 6.3-9. Piping All ECCS piping in contact with borated water is austenitic stainless steel. Piping joints are welded, except where flanged connections are required for instrumentation, test connections, or to facilitate equipment removal for maintenance. The piping beyond the accumulator stop valves is designed for RCS conditions (2,485 psig and 650°F). All other piping connected to the accumulator tanks is designed for 700 psig and 400°F. The safety injection charging pump suction piping from the refueling water storage tank is designed for low pressure losses to meet NPSH requirements of the pumps. The safety injection high pressure branch lines designed for high pressure losses to limit the flow rate out of the branch line which may have ruptured at the connection to the reactor coolant loop. The system design incorporates the ability to isolate the safety injection charging pumps on separate headers such that full flow from at least one pump is ensured should a branch line break. The piping was designed and fabricated to meet the minimum requirements set forth in the ANSI B31.1, ANSI B36.10(25) and ANSI B36.19,(26) ASTM Standards, supplementary standards and additional quality control measures. Table 6.2-1 provides a summary of required examination and tests for the different classifications of nuclear piping. Minimum wall thicknesses were determined by the ANSI Code formula found in Section 1 of B31.1. This minimum thickness was increased to account for the manufacturer's permissible tolerance of 12.5 percent of the nominal wall and 8 percent allowance for bending. Purchased pipes and fittings have a specified nominal wall thickness that was no less than the sum of that required for pressure containment, pipe bending, mechanical strength and manufacturing tolerance. Special attention is directed to the piping configuration at pumps with the objective of minimizing pipe imposed loads at the suction and discharge nozzles. Piping is supported to accommodate expansion due to temperature changes and hydraulic forces during an accident. The materials for pipes and fittings were procured in conformance with all requirements of the ASTM and ANSI specifications. All materials were verified for conformance to specification and documented by certification of compliance to ASTM material requirements. Specifications imposed additional quality control upon the suppliers of pipes and fittings as listed below.

1.

Check analyses were performed on both the purchased pipes and fittings.

2.

Pipe branch lines between the reactor coolant pipes and the isolation stop valves conform to ASTM A-376(27) or its equivalent(32) and meet the supplementary requirement S6 for ultrasonic testing.

BVPS UFSAR UNIT 1 Rev. 19 6.3-16

3.

Fittings conform to the requirements of ASTM A-403(28) or its equivalent.(32) Shop fabrication of piping subassemblies was performed in accordance with specifications which define and govern material procurement, detailed design, shop fabrication, cleaning, inspection, packaging and shipment. Welds for pipes sized 2.5 inches and larger were butt welded except for those welds in the LHSI pump suction piping within the valve pit, which were made when removing the two 12 inch manually operated maintenance valves at the suction of each of the LHSI pumps and reinstalling them as MOV-SI862A and B (see Figure 6.3-8 or 6.3-9). These piping welds were made using slip on couplings, fillet welded to the joined components. A piping flexibility analysis has confirmed the acceptability of these welds in lieu of butt welds. Reducing tees were used where the branch size exceeds one-half of the header size. Branch connections of sizes that were equal to or less than one-half of the header size were of a design that conforms to the ANSI rules for reinforcement set forth in the ANSI B31.1. Bosses for branch connections were attached to the header by means of full penetration welds. All welding was performed by welders and welding procedures qualified in accordance with the ASME Boiler and Pressure Vessel Code, Section IX. The shop fabricator was required to submit all welding procedures and evidence of qualifications for review and approval prior to release for fabrication. All welding materials used by the shop fabricator must have prior approval. All high pressure piping butt welds containing radioactive fluid, at greater than 600°F temperature and 600 psig pressure, were radiographed. The remaining piping butt welds were randomly radiographed. The technique and acceptance standards were those outlined in N-624.2 and N-625.3 of the ASME Boiler and Pressure Vessel Code, Section III. In addition, butt welds were liquid penetrant examined in accordance with the procedure of ASME Boiler and Pressure Vessel Code, Section III, Paragraph N-627.2 and the acceptance standard as defined in Paragraph N-627.3. Finished branch welds were liquid penetrant examined on the outside and the root passes were examined for sizes 6 inches and larger and for schedule 80S and heavier for all sizes. A post bending solution anneal heat treatment was performed on hot formed stainless steel pipe bends. Completed bends were then completely cleaned of oxidation from all affected surfaces. The shop fabricator was required to submit the bending, heat treatment and cleanup procedures for review and approval prior to release for fabrication. General cleaning of completed piping subassemblies (inside and outside surfaces) was governed by basic ground rules set forth in the specifications. For example, these specifications prohibited the use of hydrochloric acid and limit the chloride content of service water and demineralized water. Packaging of the piping subassemblies for shipment was done so as to preclude damage during transit and storage. Openings were closed and sealed with tight fitting covers to prevent entry of moisture and foreign material. Flange facings and weld end preparations were protected from damage by means of wooden cover plates and securely fastened in position. The packing arrangement proposed by the shop fabricator was subject to approval.

BVPS UFSAR UNIT 1 Rev. 19 6.3-17 Pump and Valve Motors Motors Outside the Containment Motor electrical insulation systems were supplied and tested in accordance with ANSI, IEEE and NEMA standards. Temperature rise design selection was such that normal long life is achieved even under accident loading conditions. Motors Inside the Containment Motors for those valves inside containment which must operate during and/or following the LOCA were designed for continuous service in the environmental conditions following the accident. This assures that the valves can perform their required safety function during the recovery period. Periodic operations of the motors and tests of the insulation ensure that the motors remain in a reliable operating condition. The only motors of the ECCS which must operate inside the containment are valve motors. Although these motors, which are provided only to drive ESF equipment, are normally run only for test, the design loading and temperature rise limits are based on the accident conditions. Normal design margins are specified for these motors to make sure the expected lifetime includes allowance for the occurrence of accident conditions. 6.3.2.3 Electrical Supply Details of the normal and emergency power source for the ECCS are presented in Section 8. 6.3.2.4 Protection Against Dynamic Effects The high head safety injection lines penetrate the containment adjacent to the auxiliary building. For most of the routing, these lines are outside each reactor coolant loop cubicle and hence are protected from missiles originating within these areas. Each line penetrates the cubicle as near the injection point to the reactor coolant pipe as possible. In this manner, maximum separation and hence protection is provided in the coolant loop area. All hangers, stops and anchors were designed in accordance with ANSI B31.1 and American Concrete Institute (ACI) 318(29) Building Code Requirements for Reinforced Concrete which provide minimum requirements on materials, design and fabrication with ample safety margins for both dead and dynamic loads over the life of the equipment. Specifically, these standards required the following:

1.

All materials used were in accordance with ASTM specifications which establish quality levels for the manufacturing process, minimum strength properties and for test requirements which ensure compliance with the specifications.

BVPS UFSAR UNIT 1 Rev. 19 6.3-18

2.

Qualification of welding processes and welders for each class of material welded for types and positions of welds.

3.

Maximum allowable stress values were established which provide an ample safety margin on both yield strength and ultimate strength. In the event of the hypothetical double-ended severance of a reactor coolant pipe, the functional integrity of the ECCS connections to the remaining reactor coolant loops is not impaired. This integrity is established and maintained by the application of the following design criteria:

1.

The reactor vessel, steam generators and pumps are supported and restrained to limit their movement under pipe break conditions (including a double-ended reactor coolant pipe rupture) to a maximum amount which ensures the integrity of the main steam and feedwater piping. The safety injection piping to the intact loops were designed to accommodate the limited movement of the loop components without failure.

2.

The safety injection piping serving each loop is anchored at the missile barrier in each loop area to restrict incident damage to that portion of piping downstream of this point. The anchorage is designed to withstand without failure the thrust force on the safety injection branch line severed from the reactor coolant pipe discharging safety injection flow to the containment, and to withstand a bending moment equivalent to that which produces failure of the safety injection piping under the action of free and end discharge or motion of the broken reactor coolant pipe to which the safety injection piping is connected. This anchorage prevents possible failure upstream from the support point where the branch line ties into the safety injection piping header. 6.3.2.5 Environmental Effects Protection All of the ECCS operating equipment, with the exception of the motor-operated valves in the accumulator injection lines, are located outside the containment, and hence are not required to operate in the steam-air environment produced by the accident. All motors, instruments, transmitters and their associated cables and penetrations located inside the containment are designed to function under the post accident temperature, pressure, radiation and humidity conditions for the length of time required. 6.3.3 Design Evaluation 6.3.3.1 Range of Core Protection The measure of effectiveness of the ECCS is the ability of the pumps and accumulators to keep the core flooded or to reflood the core rapidly where the core has been uncovered for postulated large area ruptures. The result of this performance is to sufficiently limit any increase in clad temperature below a value where emergency core cooling objectives are met as discussed in Section 6.3.1. The core protection over the range of break sizes provided by the minimum components of the ECCS is presented in Section 14.

BVPS UFSAR UNIT 1 Rev. 21 6.3-19 The following analyses are performed to ensure that the limits on core behavior following a RCS pipe rupture are met by the ECCS operating with minimum design equipment:

1.

Large pipe break analysis.

2.

Small line break analysis.

3.

Recirculation cooling. The flow delivered to the RCS by the ECCS as a function of reactor coolant pressure with the operation of minimum design equipment is analyzed in Section 14.3. The design basis performance characteristic is derived from the specified performance characteristic for each pump. The performance characteristic utilized in the accident analysis is derived in the same manner except that margin is included for uncertainties. If the rupture is assumed to be in an injection line, the injection curve utilized in the analysis is modified to account for the loss of injection water through the broken line. Large Break Analysis The large pipe break analysis is used to evaluate the initial core thermal transient for a spectrum of pipe ruptures up to the double-ended rupture of the largest pipe in the RCS. The injection flow from active components is required to control the cladding temperature subsequent to accumulator injection, complete reactor vessel refill and eventually return the core to a subcooled state. The results indicate that the maximum cladding temperature attained at any point in the core is such that the limits on core behavior as specified in Section 14.3 are met. Small Pipe Break Analysis The small pipe break analysis is used to evaluate the initial core thermal transient for a spectrum of pipe rupture from 3/8 inch up to and including the rupture of a 6 inch diameter pipe. For breaks 3/8 inch or smaller, the charging system can maintain the pressurizer level at the RCS operating pressure and the ECCS would not be actuated. The results of the small pipe break analysis indicate that the limits on core behavior are adequately met, as shown in Section 14. Recirculation Cooling Core cooling during recirculation can be maintained by the flow from one low head pump if RCS pressure is low. If RCS pressure remains high, one safety injection charging pump operating in series with the low head pump provides the added head capacity needed to maintain adequate cooling.

BVPS UFSAR UNIT 1 Rev. 27 6.3-20 Initially the recirculated water would be heated to the saturation temperature at the prevailing reactor coolant pressure when recirculated to the reactor. The system pressure at the time recirculation is initiated is dependent on the initiating break size. Heat removal from the recirculated sump water via operation of the recirculation spray coolers ensures a high degree of subcooling of the water from the sump and serves to limit the duration and extent of core boiling. 6.3.3.2 Borated Water Injection Chemistry During the injection of emergency cooling water into the RCS following a LOCA, the concentration of boron will vary depending on the depressurization history of the reactor. If depressurization were slow, the high head pumps would inject boric acid solution which would be diluted by the coolant remaining in the system. Rapid depressurization would bring about early injection of water from the accumulators. When recirculation begins, the average concentration of boric acid is (and will remain) about 1.4 weight percent. With chemical additive in the containment spray, the recirculated water will have a pH between 7.0 and 8.28. The concentrations of other materials, including chlorides, are quite low in this solution, corrosion products being generally insoluble in a basic solution. The principle fission product in solution (assuming a gross core failure) would be iodine at about 3.5 ppm, corresponding to 50 percent of the maximum core inventory. The temperature of the sump water is reduced below 150F, under normal operating conditions with a minimum of two recirculation spray coolers in operation, after a relatively short period of time (i.e., a few hours) and below 150F chloride stress corrosion does not constitute a problem. 6.3.3.3 System Response Time Response To provide protection for large area ruptures in the RCS, the ECCS must respond rapidly to reflood the core following the depressurization and core voiding that is characteristic of large area ruptures. The accumulators act to perform the rapid reflooding function with no dependence on the normal or emergency power sources and also with no dependence on the receipt of an actuation signal. Operation with two of the three available accumulators delivering their contents to the reactor vessel (one accumulator spilling through the break after termination of bypass) will meet the criteria stated in Section 6.3.1. The function of the safety injection pumps is to complete the refill of the vessel and ultimately return the core to a subcooled state. Initial response of the injection systems are automatic, with appropriate allowances for delays in actuation of circuitry and active components. The active portions of the injection systems are automatically actuated by the SIS (Section 7). In addition, manual actuation of the entire injection system and individual components can be accomplished from the control room. In analysis of system performance, delays in reaching the programmed trip points and in actuation of components were conservatively established on the basis that only emergency onsite power is available.

BVPS UFSAR UNIT 1 Rev. 28 6.3-21 The starting sequence of the safety injection charging pumps, the low head safety injection pumps and the related emergency power equipment is designed so that delivery of the full rated flow is reached within 27 seconds after the process parameters reach the setpoints for the injection signal. Reference is made to Section 8.5. For the small break analysis, an additional delay time is allowed for the SIS to activate when the appropriate setpoint is reached. Piping Restraints Following a SIS, the maximum velocity of water is approximately 110 fps in the accumulator discharge lines and 40 fps in the high head safety injection system lines (assuming two pumps deliver through 3 inch common cold injection lines). When the RCS pressure falls below the accumulator pressure, the check valve opens and borated water is forced into the coolant system. The resultant hydraulic forces are controlled by supports, including snubbers and limit stops located at various points in the piping system. Supports in the accumulator discharge lines do not eliminate the potential for water hammer, however, water hammer is not expected, since the relative low pressure of the low-head safety injection pumps would not rapidly close the check valves. Mechanical and hydraulic snubbers are utilized to limit piping movements resulting from dynamic loadings while permitting normal thermal expansion/contraction. Snubbers are designed for both tension and compression. Limit stops are also used. They perform the same function as a snubber in that they permit cyclic thermal movement. In a dynamic event, Limit Stops 'limit' pipe movement. Limit stops are a passive device and require no piston or piston valve arrangement to activate. Limit stops are designed for tension and compression. The valves of the high head safety injection system open or close in ten seconds (in contrast to accumulator check valves that open almost instantaneously); therefore, the hydraulic force should present no problem. The relatively slow closure time of these valves should present no water hammer problems. 6.3.3.4 Single Failure Analysis A single active failure analysis is presented in Table 6.3-1. Credible active system failures are considered. The analyses of the LOCA presented in Section 14 is consistent with the single failure analysis, based on a single failure in the ECCS. The analysis shows that the failure of any single active component does not prevent fulfilling the design function; also, operator action is not required to correct the malfunction.

BVPS UFSAR UNIT 1 Rev. 22 6.3-22 In addition to the single active failure capability, an alternate flow path is available through the high head safety injection pumps should any part of the flow path from the low head pumps to RCS cold legs become unavailable. This feature ensures that core cooling would be maintained in the event of a piping failure in the ECCS. It also should be noted that the reactor cold legs are fed via a common header in the injection mode and it is not possible to isolate the broken leg and prevent spilling under the present design. In the particular case of a pump being out for maintenance, an additional active or passive failure is not considered. The maximum period that operation would be continued with two pumps out for maintenance is specified in the Technical Specifications. Failure analysis of the emergency power supply under LOCA conditions are described in Section 8.5. Inadvertent Closure of Normally Open Motor-Operated Valves The ESF systems are designed to tolerate, without loss of their protective function, a single failure during the period of recovery following an incident such as a LOCA. The period of recovery includes both the injection phase and the recirculation phase. Compliance with the single failure criterion is discussed in Section 6.3.1.2. In order to assure that the accumulator isolation valves will be open during power operation when availability of the accumulator is required, the valve control circuit has the following features:

1.

The valves receive an "open" signal upon initiation of safety injection. Upon receipt of a safety injection signal, the valve is blocked from closing.

2.

The valves automatically receive an "open" signal when the pressurizer pressure exceeds a given pressure (safety injection unblocked).

3.

The valves have redundant position indication in the control room (Vertical Board and Bench Board) operated by independent limit switches in the motor operator.

4.

The valves have audible alarms, with the alarm circuits actuated by the diverse position sensors in the motor operator and stem mounted limit switches for each valve, to alarm whenever the valve is not fully open and reactor pressure is above a preset value.

5.

The audible alarm is timed to reactivate at approximately one hour intervals as long as the valve is not fully open and system pressure is above the preset value.

6.

The valve control circuit has power lock out jacks and automatic indication of grounding or shorting of the lock out jack as described below. Each accumulator isolation valve control circuit also contains a power lock out jack. Removal of the power lock out jack will remove power from the valve actuating contacts, but will permit the operation of the valve position indicating lights.

BVPS UFSAR UNIT 1 Rev. 23 6.3-23 The power lock out jacks are installed only during plant heat up and cool down. As the plant pressure exceeds a specified pressure, the accumulator isolation valves are opened and the power lock out jacks are removed thus preventing inadvertent closure of the valves. Similarly, the lock out jacks are not installed during plant cooldown until the plant pressure is below the specified pressure and the valves are required to be closed. The installation of the power lock out jacks and operation of the valves is covered by the Technical Specifications. The power lock out jack circuits also contain an automatic indication of grounding or shorting of at least one of the two controls in the power isolation jack. A failure analysis has been done to investigate the probability that such a valve would be closed during the short time required following a LOCA. Using the fault tree technique, the various combinations of equipment faults and human errors leading to spurious valve closure were evaluated and the probability of such an occurrence was determined to be 0.65 x 10-7 per demand for a single valve. Failure rates for the various equipment faults were taken from data in References 1, 2, 3 and 4. Conservative engineering judgement was applied where specific data on identical components in required failure modes were unavailable. Refer to Table 6.3-11 and Figure 6.3-7. Based on this analysis it can be stated that this situation of spurious valve closure can indeed be considered extremely unlikely. 6.3.3.5 Reliance on Interconnected System During the injection phase, the safety injection charging pumps are not dependent on any portion of other systems with the exception of the suction line from the refueling water storage tank. During the recirculation phase of the accident for small breaks, suction to the safety injection charging pumps is provided by the low head safety injection pumps. An installed bypass line connects the outside recirculation spray pumps to the safety injection charging pumps. This bypass line is not intended nor is it assumed to function in any design basis event. It serves only as a tool to address beyond design basis events such as multiple LHSI system failures. Administrative control of the locked closed manual valves ensures strict compliance with this intent. (See Figure 6.1-1) To limit post accident pressure and temperature in containment to less than design values and provide a means for long term containment heat removal, spray recirculation and cooling must be continued following a LOCA. Initially spray recirculation is continuous, but as the core residual heat level decreases, the recirculation rate is reduced and, eventually, the system may be operated intermittently. Since the heat removal from the containment must be accomplished initially through the recirculation spray subsystems and since this represents a more than adequate heat removal mechanism for the containment, the use of heat exchangers in the low head safety injection system for cooling is not required. The low head safety injection system operates to provide long term core cooling with no heat exchangers in the system by using water from the containment sump. 6.3.3.6 Normal/Accident Function Evaluation Table 6.3-12 is an evaluation of the main components, which have been previously discussed, and a brief description of how each component functions during normal operation and during the accident.

BVPS UFSAR UNIT 1 Rev. 19 6.3-24 6.3.3.7 Passive Systems The accumulators are a passive safety feature in that they will perform their design function in the total absence of an actuation signal or power source. The only moving parts in the accumulator injection train are in the two check valves. The working parts of the check valves are exposed to fluid of relatively low boric acid concentration. Even if some unforeseen deposition accumulated, a reversed differential pressure of about 25 psi would shear any particles in the bearing that tended to prevent valve functioning. This is demonstrated by calculation. The isolation valve at each accumulator is normally open with power to the motor operator locked out via banana type lock out jack, located on the main control board. Redundant position indicating lights located at the control room switch are provided for each valve. In addition, an indicating light is provided on each control circuit to show grounding or shorting of the lock out jack. The isolation valve is closed when the RCS is intentionally depressurized or to test the check valves in the line to the accumulator while the RCS is pressurized. An alarm annunciator point is activated by both a valve motor operator limit switch and by a valve position limit switch activated by stem travel, whenever an accumulator valve is not fully open for any reason with the system at pressure (the pressure at which the safety injection block is unblocked). A separate annunciator point is used for each accumulator valve. This alarm will be recycled at approximately one hour intervals to remind the operator of the improper valve lineup. The check valves operate in the closed position with a nominal differential pressure across the disk of approximately 1,600 psi. They remain in this position, except for testing or when called upon to function. Since the valves operate normally in the closed position and, therefore, are not subject to the abuse of flowing operation or impact loads caused by sudden flow reversal and seating, they do not experience any wear of the moving parts, and therefore, will function with reliability. Accumulator check valves are tested for leakage after entry into Mode 5 during each refueling outage, prior to reactor startup. Additional accumulator check valve leakage testing may be required after other plant outages in accordance with the Technical Specifications. The check valves are tested when the RCS is pressurized with a minimum of 150 psi differential across the valves. This test confirms the seating of the disk and whether or not there has been an increase in the leakage since the last test. Upon RCS heatup following the outage, there should be no increase in leakage since increasing reactor coolant pressure increases the seating force and decreases the probability of leakage. The accumulators are able to accept leakage from the RCS without any effect on their availability. Table 6.3-13 indicates what inleakage rates, over a given time period, require readjusting the level at the end of the time period. The manufacturing acceptance test is 36 cubic centimeters per hour (i.e., three cubic centimeters per hour per inch of pipe diameter).

BVPS UFSAR UNIT 1 Rev. 24 6.3-25 The accumulators are located inside the reactor containment and protected from the RCS piping and components by missile barriers. When the accumulators are completely discharged, the pressurizing gas exhausts to the containment. Release of the gas charge in the accumulators would cause an increase in the containment pressure, but occurs after containment peak pressure has been reached. This release of gas has been included in the containment pressure analysis for the LOCA Section 14.3. During normal operation, the flow rate through the reactor coolant piping is approximately five times the maximum flow rate from the accumulator during injection. Therefore, fluid impingement as a result of accumulator discharge on reactor vessel components is not restricting during operation of the accumulator. 6.3.3.8 External Recirculation Loop Leakage Table 6.3-9 summarizes the nominal (design) leakage from the leak sources of the recirculation loop which goes through the low head safety injection pumps and through the safety injection charging pumps if required. The recirculation loop is shown in Figure 6.3-9. The nominal (design) leakage resulting from all sources is 2,382 cubic centimeters per hour to the auxiliary building atmosphere and 60 cubic centimeters per hour to the waste drain tanks. Leakage specified in Table 6.3-9 are nominal (design) values and limiting values are specified in Section 14.3.5.2. During recirculation, a significant margin exists between the design and operating conditions of the low head safety injection system components. In view of these margins, it is considered that the leakage rates tabulated in Table 6.3-9 are conservative. Leakage detection exterior to the containment is achieved through the use of sump level detection (Section 9.7). The auxiliary building sump pumps start automatically in the event that liquid accumulates in the sump and an alarm in the main control room indicates that water has accumulated in the sump. Valving is provided to permit the operator to isolate individually the low head safety injection pumps. 6.3.3.9 Pump NPSH Requirements Low Head Safety Injection Pumps The NPSH of the low head safety injection pumps is evaluated for both the injection and recirculation phase operation of the design basis accident. The limiting available NPSH occurs at the initiation of the recirculation phase following a LOCA. A transient calculation of the available NPSH is performed with the MAAP-DBA computer code described in Section 14.3 for the containment evaluation. However, the available NPSH transient analysis maximizes the energy addition to the containment sump instead of the atmosphere as was done in the Section 14.3 analysis. The major differences are:

1.

The pressure flash model is used for break fluid flashing.

2.

The release streams are mixed prior to flashing to direct higher enthalpy water to the sump.

BVPS UFSAR UNIT 1 Rev. 24 6.3-26 As shown in Figure 6.3-10, the minimum available NPSH is 16.0 ft and occurs at the initiation of LHSI recirculation mode following a pump suction double-ended rupture. The minimum NPSH required is 10.6 feet for the LHSI pumps. Lines diverting cold discharge water from the quench spray headers assist in ensuring this NPSH requirement is met during DBA conditions. The limiting single failure is the loss of one emergency diesel. This results in the loss of two recirculation spray heat exchangers and therefore minimizes heat removal from the sump water before the LHSI pump suctions are switched to the sump. The LHSI pumps will be automatically throttled during all operating modes (initial injection, cold leg recirculation and hot leg recirculation) using cavitating venturies. The cavitating venturi is designed to reduce the pressure below the fluid vapor pressure and thus choke the flow. Pressure recovers downstream of the venturi near its initial value. Safety Injection Charging Pumps The NPSH for the safety injection charging pumps is calculated for both the injection and recirculation phase operation of the design basis accident. The end of injection phase operation gives the limiting NPSH requirement and the NPSH available is determined from the elevation head and vapor pressure of the water in the refueling water storage tank, and the pressure drop in the suction piping from the tank to the pumps. The required NPSH for these pumps is 39.5 ft and the minimum available NPSH is 53.5 ft. Automatic Transfer from Safety Injection to Recirculation The transfer from the safety injection mode to the recirculation mode will automatically take place on an extreme low level signal from the refueling water storage tank (RWST). The transfer to recirculation actuation signal will be from a "two out of four energize to trip" logic circuit coincident with a safety injection signal. Three of the level transmitters will have indication in the control room and the fourth will be recorded. Extreme low level, via any one of the four channels, is annunciated in the main control room. At the termination of the injection phase:

1.

The suction of the low head safety injection pumps is realigned from the RWST to the containment sump

2.

The four LHSI pumps' minimum recirculation valves are closed

3.

The four valves in the charging pumps' suction are realigned from the RWST to the discharge of the LHSI pumps. Transfer Description The following paragraphs are a description of the transfer from the injection mode to the recirculation mode. Refer to Figure 6.1-1 for valve locations.

BVPS UFSAR UNIT 1 Rev. 24 6.3-27 Upon initiation of a safety injection signal, the LHSI pumps start and recirculate to the RWST until the reactor coolant pressure drops to a pressure commensurate with their discharge head. The safety injection accumulators discharge automatically as the reactor coolant pressure decreases. The charging pumps' normal suction and discharge paths are isolated and a suction path is opened from the RWST. A new discharge path through the boron injection tank is simultaneously opened. As the water level in the RWST decreases to the designated extreme low level initiation point, any two out of the four low level transmitters, coincident with a safety injection signal, will energize and initiate the automatic transfer sequence. Immediately upon receipt of the transfer signal, valves MOV-SI885A, B, C and D on the LHSI pump minimum flow and test lines begin to close. Miniflow is the difference between flow for a given pump head and the measured flow developed at the header. This ensures that potentially radioactive containment sump water is not returned to the RWST. A simultaneous signal is sent to open valves MOV-SI863A and B, which ensures a continuous LHSI pump discharge flow path even if reactor coolant pressure is still relatively high (i.e., a small break). Additionally, valves MOV-SI860A and B in each of the two suction lines from the containment sump are signaled to open. These valves are normally closed during plant operation and an alarm occurs when they are not fully closed. Valves MOV-CH115B and D are normally closed during plant operation but were opened on either low-low level in the volume control tank or on the initial safety injection signal. In order to ensure a continued suction source for the charging pumps, these valves remain open after the initiation of the transfer signal. However, after a 30 second time delay, the valves are signaled to close to provide redundant (with check valve SI-27) isolation of the LHSI pump discharge from the RWST. In order to guarantee the continued availability of borated water to the LHSI pumps, valves MOV-SI862A and B remain open following initiation of the transfer signal. After a 2 minute time delay, the valves are signaled to close to preclude sump water from reaching the RWST. The system flow paths and valve positions are shown in the safety injection mode and after completion of the transfer to cold leg recirculation in Figures 6.3-8 and 6.3-9, respectively. Table 6.3-1 contains a single failure analysis. Approximately 6.5 hours after the loss of coolant accident, the cold leg only recirculation mode will be terminated and the simultaneous cold leg and hot leg recirculation mode initiated. The change-over is accomplished by realigning the LHSI pumps to deliver to the hot legs. During the change-over, the HHSI pumps will continue injection to the cold legs.

BVPS UFSAR UNIT 1 Rev. 23 6.3-28 6.3.4 Inspections and Tests 6.3.4.1 Inspection Quality standards of safety injection system components are presented in Table 6.3-4. All components of the ECCS system are inspected periodically to demonstrate system operability. The pressure containing components are inspected for leaks from pumps seals, valve packing, flanged joints and safety valves during system testing. 6.3.4.2 Tests Preoperational Component Testing Preoperational performance tests of the components were performed in the manufacturer's shop. The pressure containing parts of the pumps were hydrostatically tested in accordance with ASME, Boiler and Pressure Vessel Code, Paragraph UG-99. Each pump was given a complete shop performance test in accordance with Hydraulic Institute Standards. The pumps were run at design flow and head, shutoff and head and at additional points to verify performance characteristics. NPSH was established at design flow by means of adjusting suction pressure for a representative pump. This test was witnessed by qualified Westinghouse and licensee personnel. The remote operated valves in the ECCS are motor or air operated. Shop tests for each valve included a hydrostatic pressure test, leakage tests, a check of opening and closing time and verification of torque switch and limit switch settings. The ability of the operator to move the valve with the design differential pressure across the gate was demonstrated by opening the valve with an appropriate hydrostatic pressure on one side of the valve. The recirculation piping and accumulators are initially hydrostatically tested at 150 percent of design pressure. Pre-operational System Testing After hot functional testing and prior to initial fuel loading, the ECCS was operationally tested. These tests included individual pump full flow tests, accumulator operation and complete system operational flow tests, with the reactor head removed. The purpose of this test was to demonstrate the proper functioning of the instrumentation and actuation circuits and to evaluate the dynamics of placing the system in operation. Water was supplied from the refueling water storage tank for this series of tests. Actuation of the pressurizer low level and pressure signals initiated the automatic startup of the ECCS. The operability of the accumulators was checked by closing the stop valve, raising the pressure in the accumulator and then opening the stop valve and observing the accumulator level change to provide indication of system delivery.

BVPS UFSAR UNIT 1 Rev. 24 6.3-29 For those portions of the ECCS and CVCS containing concentrated boric acid, the preoperational test of the heat tracing system included review of manufacturers' design and field testing of all areas, using thermocouples to verify the adequacy of the installations. A complete check was also made of the controls and alarms of each redundant circuit. Tests During Refueling Shutdowns Testing can be conducted to demonstrate proper automatic operation of the ECCS. The test of the safety injection charging pumps can use the minimum flow recirculation lines which return to the volume control tank and can also be tested at any time during station operation due to their dual charging and ECCS function. A test of the low head safety injection pumps can use the recirculation lines which return to the refueling water storage tank. The operation of the remote stop valves in the accumulator discharge line are tested by opening the remote test valves in the test line between the remote stop valves and the check valves. Flow through the test line is measured and the opening and closing of the discharge line stop valves is verified by the flow instrumentation. The test line can also be used to check leakage through both the check valves and to ascertain that these valves seat whenever the reactor system pressure is raised. Since the isolation valves are open with power removed during plant operation, and required periodic surveillances verify that power to the valve motor operators is removed, the valves are open, and no position alarms are present, the possibility of inadvertent closure of the isolation valves is eliminated. Because the valves are energized for only brief intervals to change valve position during startup or shutdown, the automatic features to assure the valves will open when required serve no useful function. Thus, the auto open and blocking of closing on an SI signal and auto open on RCS pressure greater than 2000 psig are not required to be tested. Testing During Normal Operation Each active component of the ECCS may be individually actuated at any time during operation of the unit to demonstrate operability. The CVCS charging pumps serve as the high head safety injection pumps. As such, the operability of at least one pump is demonstrated by continuous charging operation while the unit is at power. Demonstration tests can be performed at other times on the other two pumps while charging with the third by employing the minimum flow recirculation line which returns to the volume control tank. The tests of the low head safety injection pumps employ the minimum flow recirculation test line which returns to the refueling water storage tank. Remotely operated valves are exercised and actuation circuits are tested during this flow test. The accumulator pressure and level are continuously monitored during station operation and any RCS leakage past the accumulator check valves can be checked at any time using test lines.

BVPS UFSAR UNIT 1 Rev. 32 6.3-30 The accumulators are maintained full of borated water while the unit is in operation. The accumulators are refilled with borated water from the refueling water storage tank by using the positive displacement hydrotest pump. The concentration in the accumulators is checked periodically by sampling. On January 11, 2008, the NRC issued Generic Letter 2008-01, Managing Gas Accumulation in Emergency Core Cooling, Decay Heat Removal, and Containment Spray Systems. Generic Letter 2008-01 requested licensees to evaluate the licensing basis, design, testing, and corrective action programs for the emergency core cooling, decay heat removal, and containment spray systems. As a result, the company performed evaluations that included the review of gas susceptible piping locations, the development of activities to monitor various piping locations as appropriate based on industry experience and plant specific experience, and acceptance of some generic locations that normally accumulate voids that do not adversely affect the design function(s) of the system. The company established a gas accumulation prevention and management program to ensure that gas accumulation is reasonably prevented or maintained less than the amount that challenges the functionality of the applicable systems and that appropriate action is taken when conditions adverse to quality are identified.

BVPS UFSAR UNIT 1 Rev. 23 6.3-31 References for Section 6.3

1.

T. L. Benes, "Minuteman Electronic Parts Failure Rates," D2-14134, The Boeing Co. (January 1963, revised November 1965).

2.

Military Standardization Handbook, "Reliability Stress and Failure Rate Data for Electronic Equipment," MIL-HDBK-217A (December 1965).

3.

A. E. Green and A. J. Bourne, "Safety Assessment with Reference to Automatic Protective Systems for Nuclear Reactors," AHSB (S) R 117, United Kingdom Atomic Energy Authority (1966).

4.

M. E. Steward, J. F. White, J. 0. Zane, "Reliability Analysis of the Power Burst Facility Reactor Protection System," IN-ITR-200, Idaho Nuclear Corporation, (December 1969).

5.

Deleted, Rev. 19.

6.

"Code for Pressure Piping," ANSI B31.1, The American National Standards Institute.

7.

"ASTM Specification for Austenitic Steel Castings for High-Temperature Service," ASTM A-351, The American Society for Testing and Materials.

8.

"ASTM Specification for Forced on Steel Rolled Alloy-Steel Pipe Flanges, Forged Fittings, and Valves and Parts for High-Temperature Service," ASTM A-182, The American Society for Testing and Materials.

9.

"ASTM Specification for Forgings for Pressure and High-Temperature Service," ASTM A-336, The American Society for Testing and Materials.

10.

"ASTM Specification for Heat-Resisting Chromium and Chromium-Nickel Stainless Steel Plate, Sheet, and Strip for Fusion-Welded Unfired Pressure Vessels," ASTM A-240, The American Society for Testing and Materials.

11.

"ASTM Specification for Alloy-Steel and Stainless Steel Bolting Materials for High-Temperature Service," ASTM A-193, The American Society for Testing and Materials.

12.

"ASTM Steel and Pipe Flanges, Flanged Valves and Fittings," ANSI B16.5, The American National Standards Institute.

13.

"Pressure-Temperature Ratings for Steel Butt-Welding End Valves," MSS-SP-66, The Manufacturers Standardization Society Standard Practice.

14.

"ASTM Test for Pore Size Characteristics of Membrane Filters for Use With Aerospace Fluids," ASTM F-316, The American Society for Test and Materials.

15.

"ASTM Recommended Practice for Radiographic Testing," ASTM E-94, The American Society for Test and Materials.

BVPS UFSAR UNIT 1 Rev. 23 6.3-32 References for Section 6.3 (CONTD)

16.

"ASTM Reference for Radiographs for Steel Castings Up to 2 Inches in Thickness," ASTM E-71, The American Society for Test and Materials.

17.

"ASTM Reference for Radiographs for Heavy-Walled [2 to 4 1/2 inch (51 to 114 mm)] Steel Castings," ASTM E-186, The American Society for Test Materials.

18.

"ASTM Reference Radiographs for Heavy-Walled [4 1/2 to 12 inch (114 to 305 mm)] Steel Castings," ASTM E-280, The American Society for Test and Materials.

19.

"ASTM Specification for Carbon and Alloy Steel Nuts for Bolts for High-Pressure and High-Temperature Service," ASTM A-194, The American Society for Test and Materials.

20.

"Hydrostatic Testing of Steel Valves," MSS-SP-61, The Manufacturers Standardization Society Standard Practice.

21.

"ASTM Specification for Stainless and Heat-Resisting Steel Bars and Shapes," ASTM A-276, The American Society for Test and Materials.

22.

"ASTM Specification for Forging, Carbon Steel, for Piping Components," ASTM A-105, The American Society for Test and Materials.

23.

"ASTM Specification for Forgings, Carbon Steel for General Purpose Piping," ASTM A-181, The American Society for Test and Materials.

24.

"ASTM Specification for Carbon Steel Castings Suitable Fusion Welding for High-Temperature Service," ASTM A-216, The American Society for Test and Materials.

25.

"Welded and Seamless Wrought Steel Pipe," ANSI B36.10, The American National Standards Institute.

26.

"Stainless Steel Pipe," ANSI B36.19, The American National Standards Institute.

27.

"ASTM Specification for Seamless Austenitic Steel Pipe for High-Temperature Central-Station Service," ASTM A-376, The American Society for Test and Materials.

28.

"ASTM Specification for Wrought Austenitic Stainless Steel Piping Fittings," ASTM A-403, The American Society for Test and Materials.

29.

"ACI Building Code Requirements for Reinforced Concrete," ACI-318, The American Concrete Institute.

30.

Deleted, Rev. 19.

31.

Deleted, Rev. 19.

32.

The term "Equivalent" is described in UFSAR Section 1.8.2, "Equivalent Materials."

BVPS UFSAR UNIT 1 Rev. 27 6.4-1 6.4 CONTAINMENT DEPRESSURIZATION SYSTEM 6.4.1 Design Bases The containment depressurization system is composed of two groups of subsystems: the quench spray subsystems and the recirculation spray subsystems. These systems are designed to provide the necessary cooling and depressurization of the containment after any LOCA. The subsystems are designed in accordance with 1971 General Design Criteria 38 through 43 of Appendix A to 10CFR50. Operating together, these subsystems cool and depressurize the containment to less than 1/2 of the peak calculated pressure within 24 hours following the Design Basis Accident (DBA), assuming the operation of at least minimum engineered safety features as defined in Section 14.3. In addition, the recirculation spray subsystems are capable of reducing and maintaining the containment pressure in the containment for an extended period following the DBA. Equipment in the containment depressurization system are designed according to the code criteria and earthquake criteria specified in Section 6.2 and 2.5, respectively. 6.4.2 Description The quench and recirculation spray subsystems are sized to satisfy the following design bases:

1.

The containment shall be depressurized (to less than 1/2 of the peak calculated pressure within 24 hours) following a LOCA.

2.

The LOCA to be considered is a double-ended rupture of a reactor coolant pump suction line.

3.

The temperature of the RWST is in the range of 45F to 65F.

4.

The inlet temperature of the cooling (river) water for the recirculation cooler is at a maximum of 90F.

5.

The minimum engineered safeguards configuration (one 360 degree quench spray header and two 180 degree recirculation spray headers) shall be used.

6.

Initiation of a recirculation spray subsystem shall be delayed to ensure adequate water in the containment sumps and to provide high containment back pressures to enhance ECCS effectiveness during reflood.

7.

The quantity of buffer provided for dissolution and transfer to the recirculation spray subsystem shall be sufficient to maintain the containment pH of 7 or greater during the recirculation phase of a LOCA response.

BVPS UFSAR UNIT 1 Rev. 27 6.4-2 The function of the sprays is to remove heat from the containment atmosphere by convection and condensation. Heat is transferred out of the containment by means of the recirculation coolers. Table 6.4-2 lists the design parameters for components of the heat removal system. All parts in contact with the pumped fluids are made of austenitic stainless steel. The tube side fouling factor is assumed to be 0.0005. The shell side fouling factor is assumed to be zero, as the shell will be laid up dry. Any shell side fouling occurring during service is more than compensated for since the heat duty required of the cooler decreases rapidly with time. The fluid flow paths through a recirculation spray cooler is shown in Figure 6.4-4. Quench Spray Subsystem Two quench spray subsystems, shown in Figure 6.4-1A, are made up of two separate parallel subsystems, each of 100 percent capacity. Each of these subsystems draws water independently from the refueling water storage tank and supplies it to a quench spray header located inside the containment. In addition, quench spray water is also directed to the suction of the outside and inside recirculation spray pump at a nominal flow rate of 300 gpm and 150 gpm respectively. Component design data for the quench spray subsystems are given in Table 6.4-1. During design of the containment spray subsystem, it was assumed that the quench spray pumps became effective momentarily after receipt of a containment isolation phase B signal. The quench spray delay was intended to provide time for diesel generator startup, pump startup, discharge valve opening time and piping fill time. Analysis of the quench spray subsystem showed that up to 43.9 seconds may be required from receipt of a CIB signal to achieve rated flow through the nozzles. The quench spray will have a pH of no lower than 4.6 based on a maximum boron concentration of 2600 ppm. The final pH in the containment after a LOCA, considering acid production, the contents of the RWST, and the sodium tetraborate decahydrate buffer baskets, is 7 or greater.

BVPS UFSAR UNIT 1 Rev. 27 6.4-3 A piping loop seal has been added to each of the quench spray flow paths which are maintained full during normal operation. This prevents air ingestion into the suction of the Recirculating Spray and Low Head Safety Injection pumps. The ultimate pH of the containment sump is determined from the boric acid concentration of the reactor coolant system, RWST, boric acid addition tank and the three safety injection accumulators, plus the dissolution of sodium tetraborate decahydrate buffer. No provisions for monitoring or adjusting the pH of the sump water are necessary. The only way in which the pH of the sump water could be altered would be leakage of river water at the recirculation coolers. This is prevented by maintaining the recirculation water pressure greater than the river water pressure. Any possible radioactive outleakage through a heat exchanger would be detected by the use of the four recirculation spray heat exchanger river water radiation monitors. The RWST is a vertical cylindrical tank with flat bottom and hemispherical top, mounted on and secured to a reinforced concrete foundation. Maximum tank volume is approximately 441,000 gallons. The tank is fabricated of ASTM A-240, Type 304L, or equivalent,(6) stainless steel plates. Operational parameters for the RWST are provided in the Technical Specifications and Licensing Requirements Manual.

BVPS UFSAR UNIT 1 Rev. 27 6.4-4 The water in the RWST is cooled prior to initial unit startup, during unit operation, and following refueling operations, to a temperature corresponding to the requirements of the Technical Specifications and Licensing Requirements Manual by circulating it through a heat exchanger which uses chilled water to remove heat. The tank is insulated to limit the temperature rise of the water to 1/2F or less per 24 hour period. During normal plant operation, after the water in the tank has been cooled initially by the RWST coolers, it is maintained at the required temperature by circulation through either of two mechanical refrigeration units. Freezing in the RWST during cold weather periods is prevented by the RWST insulation and by maintaining the RWST temperature above the minimum temperature specified in the Technical Specifications and Licensing Requirements Manual. Heat tracing is provided on all lines exposed to the weather. During normal operation, RWST water may be processed through the fuel pool cooling and purification system to meet water chemistry requirements and/or to reduce radiation levels. The tank is provided with a manhole for access into the tank for inspection during the refueling periods. The tank is designed as a Seismic Category I component to withstand design seismic loadings. An evaluation is made to establish that there is no loss of function following the design earthquake conditions. The connecting piping is also designed to withstand seismic loading, to ensure the functioning of the system. Figure 1.2-1 shows the refueling water storage tank (RWST) in relation to adjacent facilities. The following protective measures have been taken to prevent the tank from being functionally degraded by missiles generated by rotating equipment, fires, explosions and the failure of adjacent nonseismic structures:

1. The RWST has concrete shielding completely surrounding the tank to El. 762 ft 6 inches. The chemical addition tank pump and the chemical injection pumps now abandoned-in-place, were the only rotating equipment in this area. Therefore, the need for missile protection from rotating equipment has been eliminated.
2.

Degradation of the RWST from fires is considered highly unlikely. The transformer located west of the RWST has a sprinkler system provided to handle accidental fire. No combustible materials are stored in this area. The concrete shielding, metal covering and insulation provide protection of the tank from fire.

3.

The nonseismic structures in the vicinity of the RWST are the service building and warehouse. These structures will collapse in place during a seismic disturbance. The distance from these structures and the concrete shielding provides adequate protection.

BVPS UFSAR UNIT 1 Rev. 25 6.4-5 Lines connected to the RWST that are essential in attaining and maintaining a safe shutdown during accident conditions are 12"-SI-1-153W-Q3, 12"-QS-1-153B-Q3 and 12"-QS-2-153B-Q3. All essential piping from the RWST is routed through missile protected pipe trenches before entering the safeguards or the cable vault structures. All lines in unheated spaces have insulation and heat tracing provided to prevent freezing of the pipes. All lines connected to the RWST have valves that can be either manually or remote manually closed in case of line rupture. Redundant level alarms in the main control room will annunciate when water level drops below normal liquid elevation. Each quench spray pump alone is capable of supplying about 2,000 gpm of borated water to separate 360 degree quench spray ring headers located approximately 96 ft. above the operating floor in the curved section of the dome. The quench spray ring headers have a centerline diameter of about 67 ft. and a total of 196 nozzles per header. Each of the quench spray headers has 118 Spraying Systems Co. Type 1/2-B40 nozzles. These nozzles produce a relatively fine hollow cone spray pattern. These nozzles are positioned to spray downward and have a spray angle of 70-80 degrees. There are also 40 quench spray nozzles that are plugged on each header. The remaining 78 nozzles, on each quench spray header, are Spraying Systems Co. Type 1713A nozzles. These nozzles are positioned to spray upward at an angle of 22.5 degrees from horizontal. The spray nozzles are positioned so that there are two nozzles side by side with a 10.75 inch distance between them. A 21.5 inch space is then provided on the header before the next two nozzles are located. This symmetrical configuration is utilized the entire distance of the quench spray header. The mean equivalent diameter of the quench spray droplets is less than 1,000 microns. The quench spray pumps are located adjacent to both the containment structure and the RWST. Each quench spray pump discharge line contains a weight-loaded check valve inside the containment. One-half inch drain lines are located immediately after the check valves which are provided with normally closed double isolation valves. These lines provide flow path to containment sump, normally used during refueling outage. A stainless steel strainer is provided in the discharge of each quench spray pump. The quench spray pumps shall be flow tested at the frequency specified in ASME Section XI. A deviation from flow rates and discharge pressures, as previously determined during preoperational tests, will indicate either particulate buildup in the strainers or clogging of the test spray nozzles (smallest size nozzles orifice) in the refueling water storage tank. Strainers and test nozzles are easily removable if cleaning is required. The strainers located on the discharge of the quench spray pumps have a 4 mesh per inch (0.063 inch diameter wire) outer basket and a 20 mesh per inch (0.014 inch diameter wire) inner basket.

BVPS UFSAR UNIT 1 Rev. 27 6.4-6 Recirculation Spray Subsystem Each of the four recirculation spray subsystems, shown in Figure 6.4-1B, consists of a recirculation spray pump and a recirculation spray cooler and feeds a 180 degree spray ring header located approximately 80 ft above the operating floor. Component design data for the recirculation spray subsystems is given in Table 6.4-2. Analysis of the recirculation spray subsystem showed that approximately 65 seconds may be required from receipt of a containment isolation phase B signal in conjunction with a RWST low level signal to achieve rated flow through the nozzles. This reflects the time required to fill the system piping and deliver rated flow. The total delay in the recirculation spray effective time was selected to provide sufficient sump level to submerge the containment sump strainers. Two of the recirculation spray ring headers have a radius of 49 ft-3 inches. The other two have a radius of 50 ft-3 inches. Each of the headers has 195 fittings for spray nozzles, with each fitting having two spray nozzles. Ninety-eight of these fittings have two Spraying Systems Co. Type 1/2-B60 nozzles. These nozzles are similar to the quench spray 1/2-B40 nozzles in having a relatively fine spray, but have a larger orifice. One nozzle per fitting is positioned to spray vertically downward while the other is positioned to spray horizontally toward the center of the containment. Each of the remaining 97 fittings per header is equipped with one Spraying Systems Co. Type 1/2-B60 nozzle and either a Spraying Systems Co. Type 1713A nozzle or a plug. Per header, there are 64 Spraying Systems Co. Type 1713A nozzles and 33 plugs. The 1/2-B60 nozzle is positioned to spray horizontally toward the center of the containment while the 1713A nozzles are positioned to spray upward at an angle of 45 degrees to the horizontal toward the center of the containment. The 1713A nozzles on the lower headers are provided with 9 inch extensions so that the spray can clear the upper header. The two nozzle arrangements are positioned alternately on each recirculation spray ring header. The mean equivalent diameter of the recirculation spray droplets is less than 1,000 microns. The four recirculation spray pumps take suction from the containment sump, which is protected from debris by a strainer assembly. The strainer assembly consists of two strings of strainer modules which provide approximately 3400 square feet of strainer area through the use of 1/16 perforations. The two strings of modules provide clean containment water flow to a channel box. The channel boxes are connected to each of the module strings and are connected to a common channel box which enters the suction box surrounding the containment sump. The containment sump strainer assembly provides protection for both trains of the recirculation spray pumps. A passive single failure is not assumed credible for the strainer assembly as it meets the requirements of Section 1.3.1 for passive failure exclusion criteria. Figure 6.4-2 shows the containment sump strainer assembly. The recirculation spray subsystem provides for containment sump pH control. Prior to entering the containment sump, water in the containment basement infiltrates six sodium tetraborate decahydrate baskets to dissolve a predetermined quantity of buffer. The baskets are passive devices which permit the post-LOCA containment pH to be maintained at 7 or greater by virtue of the subsystems recirculation action. Table 6.4-2 provides data for the buffer baskets.

BVPS UFSAR UNIT 1 Rev. 24 6.4-7 Two of the recirculation spray pumps and associated motors are located outside the containment and two pumps and motors are located inside the containment. The four pumps are of the vertical deep-well type. The outside pumps have shaft extensions to permit locating the pump suctions at a level below the containment sump, with the motors at an elevation slightly above grade. Each pump has a capacity of approximately 3,300 gpm. The recirculation spray pump motor supports are located at El. 702 ft 10 5/8 inch inside containment. The maximum post accident water level in the containment is at El. 698 ft 9 inch. The recirculation spray pump motors have been selected to ensure their operation under accident conditions. The outside recirculation spray pumps are fitted with a tandem mechanical seal arrangement. The tandem mechanical seal arrangement provides a positive seal against leakage of radioactive fluid from the seals of the outside recirculation spray pumps. The seal arrangement also provides adequate lubrication and cooling for the seals. Level alarms are provided to ensure that adequate accumulator water volume is available and to indicate the failure of either seal. The seal arrangement consists of two mechanical face seals (Items No. 2 and No. 7), arranged to enclose a non-radioactive seal fluid. After the pump is started, the pressure between the seals is maintained higher than the pressure outside either seal by an accumulator with a weight loaded diaphragm. The accumulator is fitted with two sealed level switches and alarms for annunciation in the main control room. The seal fluid is cooled by being pumped by the pumping ring (Item No. 6) through an air cooler. The accumulator is conservatively sized to allow for sufficient volume of demineralized water outleakage during operation of the pump. The total volume of the seal water system accumulator is 2.6 gallons. The volume in the lower section of the seal chamber between level alarms is 1,085 ml. The normal outleakage rate, obtained from Crane Packing Company, is 0.26 ml per hour. Based on the normal outleakage rate and the volume of the lower section of the accumulator between level alarms, the recirculation spray pump could be operated for 5.8 months without requiring a supply of makeup water to the accumulator. A seal water accumulator low level alarm at this point will warn the operator of the pending loss of seal water (1.75 months remaining of seal water). A valved hose connection is provided on the seal piping in order to fill the accumulator and associated piping from nearby demineralized water hose connections. Operating the pumps without seal water will cause eventual seal failure and subsequent loss of radioactive fluid to the safeguards area. However, a recirculation spray pump will not be operated without seal water. Twenty-four hours after a DBA only one recirculation spray pump is required for intermittent operation in order to remove decay heat being generated in the reactor core to maintain near atmospheric conditions in the containment. Sufficient time is available to allow for refill of one outside recirculation spray accumulator or use of one of the other three recirculation spray pumps.

BVPS UFSAR UNIT 1 Rev. 24 6.4-8 The seal water accumulator and piping are constructed of stainless steel and designed for service at peak operating conditions. The accumulator is designed to ASME Boiler and Pressure Vessel Code, Section III, Class C. The space between the seal faces is maintained at a pressure greater than the recirculation water with demineralized water as seal fluid, thus preventing leakage of the recirculation water, which may be radioactive. The recirculation water flows through recirculation spray coolers, where it is cooled by river water (Section 9.9). The entire containment depressurization system is constructed of corrosion resistant materials, primarily stainless steel. However, other materials are used where suitable, such as brass for the quench spray nozzles. The system has a 150 psig design pressure. 6.4.3 Evaluation The containment depressurization system consists of two 100 percent capacity quench spray subsystems and four 50 percent capacity recirculation spray subsystems. The use of separate spray headers on the discharge of each pump allows for the selection of spray nozzle sizes (0.516 inch, 0.360 and 0.375 inch) to give optimum combination of small spray particles for maximum heat transfer and larger particles for better coverage toward the center and sides of the containment. The components of the containment depressurization system have been selected so that the conditions of service (pressure, temperature and fluid composition) do not prevent the system from performing its intended function. The methods of preventing the plugging of spray nozzles in the two systems differ. For the quench spray subsystems, the materials of construction, as well as the pump discharge strainer, prevent nozzle plugging. A method of nozzle testing is provided in the refueling water storage tank to ensure that no particulates which could plug the quench spray nozzles collect in the refueling water storage tank. A temporary strainer is provided in the quench spray pumps suction piping for initial system cleanout. Despite this and regardless of screen opening, some type of particle could conceivably pass lengthwise through the screen and cause clogging of a spray nozzle. However, since the final screen opening is smaller than the smallest spray nozzle size, which is 0.360 inch, such an occurrence is considered to be highly improbable. For the recirculation spray subsystems, the screen assemblies in the containment sumps are arranged with a common containment sump strainer assembly (Section 6.4.2). The containment sump strainer is designed in response to NRC issued Generic Letter 2004-02. Sufficient area has been provided to insure that the specific BVPS-1 debris strainer loading does not impair system operation. The containment sump strainer provides protection for both trains of the Recirculation Spray System. A passive single failure is not assumed credible for the strainer assembly as it meets the requirements of Section 1.3.1 for passive failure exclusion criteria.

BVPS UFSAR UNIT 1 Rev. 27 6.4-9 During normal unit operation, the recirculation spray coolers are dry on the shell side and filled with river water with corrosion preventatives on the tube side as described in Section 9.9.2. For long term operation, on the order of weeks, there may be some fouling of the tubes on the river water side, with resultant loss in heat transfer capability. The loss of heat transfer capability will be more than offset by the decrease in necessary heat load due to decreasing decay heat production. One day after a loss-of-coolant accident, the drop in decay heat is such that one pump and heat exchanger has sufficient heat-removal capacity to hold the containment depressurized. With an expected maximum river water temperature of 90F, the recirculation spray subsystem design is conservative, with a minimum 100 percent backup capacity at the onset of an accident. Within one day after the LOCA, the backup capacity exceeds 400 percent. The recirculation spray coolers have welded construction at all points where there is a potential for leakage of radioactive recirculation water into the river water. The maximum pressure differential which can occur between the river water and the recirculation water is 150 psi; under these conditions, leakage flow from the recirculation spray subsystems is toward the river water system. The river water is monitored for leakage by means of radiation monitors. The defective subsystems are shut down if leakage above the allowable values (within the limits of 10CFR20) is detected. The recirculation spray coolers low point piping or shell drain valve caps have 1/8 inch holes to permit drainage of any liquid buildup, thereby eliminating any stagnant boric acid and potential stress corrosion cracks. The addition of 1/8 inch holes to the recirculation spray coolers drains has been analyzed and determined to have no effect on the spray function of the recirculation spray system.

BVPS UFSAR UNIT 1 Rev. 23 6.4-10 Because two of the recirculation spray pumps and associated valves and piping are outside the containment, a potential danger of radioactive leakage exists. Valves have been selected to reduce this leakage potential to a negligible amount. To protect against large leaks the following is done:

1.

On the discharge of the recirculation spray pumps, gross leaks are detected by variations in the pump discharge pressure readings in the main control room.

2.

Large leaks in the suction piping in the safeguards area are detected by liquid level measuring devices. The floor of the safeguards area is provided with baffles, dividing the floor into two sections. Thus, leakage from recirculation suction lines is detected by the increased liquid level on the affected section of the floor. Upon detection, the operator in the main control room remote-manually isolates the leaking pipe, leaving three recirculation spray loops operating. In the case of small leaks, detection and isolation of leaks are not possible; however, the gaseous contents of the structure (Figure 6.4-3) enclosing the piping outside the containment are normally discharged to the atmosphere via the elevated release point in the supplementary leak collection and release system (Section 6.6). Consistent with letters from the ACRS(1) concerning vital piping which must function during a LOCA, passive failure of the recirculation spray pump suction piping during a LOCA is not considered credible during the injection phase of the LOCA. The valves located in the safeguards valve pit area are the outside recirculation spray pump suction isolation valves, outside recirculation spray bypass isolation valve and the low head safety injection pump suction isolation valves. The safeguards area suction valve pit is shown in Figure 6.1-1 and in Figure 5.1-5 at El. 687 ft-11 inches. Valve operators are located at El. 747 ft in the safeguard area structure. Valve extensions are totally enclosed and water tight. The valve pit structure is attached directly to the reactor containment mat and lower portion of the shell. Porous concrete is placed below the pit and against its three sides. The pit is designed for seismic and hydrostatic loading in addition to dead and live loads. The pit pump casings are completely enclosed by the butyl waterproof membrane surrounding the reactor containment, up to El. 730 ft. where it terminates between the bottom mat of the safeguard building and the containment shell. The concrete which surrounds the safeguards area is sealed to prevent entry of ground water into the safeguards area. The seal membrane also serves to prevent leakage of any recirculation water from the safeguards area into the earth backfill between the cofferdam and the containment. The inside and outside recirculation spray pumps are capable of meeting NPSH requirements under LOCA conditions.

BVPS UFSAR UNIT 1 Rev. 24 6.4-11 A transient analysis of the available NPSH is performed with the MAAP-DBA computer code described in Section 14.3. Some modifications are made to the assumptions in the Section 14 containment pressure analysis to provide conservatism in the NPSH analysis. Generally, these assumptions tend to maximize sump water temperature and minimize containment pressure. Inputs and assumptions are also chosen to minimize the available NPSH and are based on the results of a sensitivity study which determines the direction of limiting bias for key inputs. The major model differences are as follows:

1.

Break fluid flashing is modeled by a pressure flash.

2.

Spray thermal effectiveness is assumed to be 100 percent.

3.

Maximum engineered safety features are assumed operable. As shown in Figure 6.4-10, the minimum available NPSH is 14.7 ft. for the inside recirculation spray pumps and 14.4 ft. for the outside recirculation spray pumps. The minimum available NPSH occurs following a hot leg double-ended rupture at approximately 400 seconds after the pumps start. The deep well pumps require approximately 9.8 ft NPSH at a flow of 3400 gpm. Lines diverting cold discharge water from the quench spray headers are provided to assist in ensuring the NPSH requirement is met during DBA conditions. The containment depressurization system provides the capability to thoroughly mix the containment atmosphere and minimize the possibility of hydrogen accumulating in the containment subcompartments and escaping the mixing action of the spray water. The internal design of the containment structures allows air to circulate freely. All cubicles and compartments within the containment are open at the top and allow air circulation. Convective mixing in conjunction with containment spray assures a uniform mixture of hydrogen in the containment. BVPS thus complies with 10 CFR 50.44(b)(1). Provisions for sampling the containment atmosphere following a LOCA are provided. A failure mode analysis for the components of the containment depressurization system is included in Table 6.4-3. The air recirculation cooling system may be used to limit the buildup of pressure in the containment structure for small reactor coolant system (RCS) and steam line leaks which are not sufficient in magnitude to automatically initiate operation of the containment depressurization system. The containment depressurization system is automatically initiated upon receipt of a containment isolation phase B signal. The operator does not have the option of preventing the actuation of containment spray system through the use of the air recirculation cooling system. Portions of the containment depressurization system can be bypassed for testing. Containment depressurization system pumps and valves are assigned to ESF actuation slave relays and are tested as described in Section 7.3. Assignments of the containment depressurization system components to these relays, which are individually tested one at a time, are made so that the containment depressurization is not inadvertently initiated due to testing and also so that redundant devices remain functional during the testing.

BVPS UFSAR UNIT 1 Rev. 23 6.4-12 Post test requirements followed to ensure availability for activation for the components grouped on common test-table relays are established in approved BVPS test procedures. The requirement for performance of these tests is that minimum engineered safety features are available at all times during testing. Electrical interlocks which prevent the operator from tripping the spray pumps inadvertently or prematurely from the main control room are accomplished by use of a control switch trip action blocking contact. Upon the receipt of a containment isolation phase B signal, a contact from the pump motor starting timer produces this signal instantaneously. The containment spray pumps suction and discharge valves are protected from inadvertent closure by a control room operator during pump operation by either a normally closed pump switchgear auxiliary contact placed in the closing circuit of the motor-operated valve, or by access covers placed over the benchboard control switch. To deactivate any containment spray pump would require two operator actions: (1) manually reset the containment isolation phase B train signal associated with the equipment and (2) place the control switch for the pump in the stop position. Above the operating floor (El. 767 ft-10 inches), the quench sprays cover a volume of approximately 431,102 cu ft and the recirculation sprays cover a volume of approximately 529,625 cu ft. The total free volume above the operating floor is approximately 1,030,000 cu ft. Because of the forced circulation set up by the sprays, the entire volume above the operating floor is considered to be uniformly mixed and scrubbed by the sprays. Below the operating floor, the quench sprays cover approximately 55,443 cu ft and the recirculation sprays cover approximately 219,711 cu ft. The total free volume below the operating floor is approximately 724,000 cu ft. All of the subcompartments, with the exception of the volume below the reactor vessel, the refueling cavity and the incore instrumentation passage, are well vented and scrubbed by the sprays. The following regions are not directly covered by sprays: Area Region (cubic ft) Incore instrumentation passage 6,500 Volume below reactor vessel 2,000 Volume below refueling cavity 21,750 Note that this volume is a portion of the base mat floor. As such, it has no side walls, is not enclosed and is subject to good mixing with the main spray volume.

BVPS UFSAR UNIT 1 Rev. 23 6.4-13 The spray patterns for the quench and recirculation sprays are depicted in Figure 6.4-8. These spray patterns are based on minimum engineered safeguards. The degree of mixing between the regions covered by the quench and recirculation sprays can be estimated by the amount of overlap of coverage by the quench and recirculation sprays and from the forced circulation set up by the containment sprays. The volume above the operating floor which is covered by overlapping quench and recirculation sprays is 253,878 cubic ft. The mixing from forced circulation induced by the sprays may be visualized by inspection of Figure 6.4-9, which shows a simplified diagram of the air flow in the containment set up by the sprays. Consider that the containment volume is split into two concentric cylindrical regions. In the outer region, air is entrained by sprays and forced downward. In the inner portion, the air moves upward. This circulation pattern is augmented by rising air currents from hot components, such as the reactor pressure vessel, steam generators and pressurizer. The effectiveness of the sprays in mixing the containment atmosphere has been verified by BNWL(2) in which measurements, made at different points in the containment systems experiment vessel (similar to the BVPS-1 containment) for iodine and noble gases, showed that iodine was completely distributed throughout the containment, even at the high points in the vessel. The design of the containments and containment spray systems for BVPS-1 and BVPS-2, are similar to those of the Surry Power Station, Units 1 and 2, for which it has been concluded by the Atomic Energy Commission(3) that the containment spray systems provide adequate mixing of the containment atmosphere in the post LOCA environment. A measure of the mixing between subcompartments below the operating floor (such as the steam generator cubicles and the pressurizer cubicle), that are covered by the sprayed volume, may be determined by the natural circulation set up by the difference in air/steam densities between the subcompartment volumes and the containment volume covered by the sprays. The flow due to "stack effect" can be computed from the following equation:(4) Q = 7.2 A ) t-(t h o i (6.4-1) where: Q = air flow, cubic feet per minute A = free area of inlets or outlets (assumed equal; if different, the smaller of the two is used), sq ft h = height from inlets to outlets, ft ti = average temperature of inside air, °F to = temperature of outside air, °F 7.2 = constant of proportionality, including a value of 50 percent for effectiveness of openings

BVPS UFSAR UNIT 1 Rev. 23 6.4-14 From the above equation, circulation rates ranging from 1,500 cfm to 61,000 cfm were computed. In addition to the mixing of the containment atmosphere with the sprays due to natural and forced convection, there will be direct coverage by the sprays in the form of "rain" falling through the opening in the operating floor into the volumes below. No credit is taken in the analysis for iodine removal below the operating floor by sprays falling in the form of rain. The design pressure drop across the quench spray nozzles is 40 psi. Estimated Leakage During Recirculation A periodic inspection is made of all potential points of leakage. Table 6.4-4 summarizes the potential leakage from the recirculation spray subsystems. Leakage of a pumped fluid from the outside recirculation spray pumps cannot occur, due to the manner in which the pump shafts are sealed. Two mechanical seals are arranged in tandem with a seal fluid between them. The seal fluid is supplied from a reservoir arranged in such a manner that the pressure of the seal fluid is slightly above (about 1 psi) the pumped fluid pressure at the inboard side of the inboard seal. This arrangement means that, assuming a single seal failure, seal fluid leaks through the failed seal and the other seal remains available to prevent escape of pumped fluid to the atmosphere. A level alarm on the reservoir provides indication of seal failure. 6.4.4 Tests and Inspections After the quench spray subsystems have been completely installed, temporary connections are made on the spray headers and pipe plugs placed in the spray nozzle sockets and header drain lines. The quench spray pumps are started and tested, circulating water through the spray header supply lines to the spray headers and out the temporary test connections. This is to provide a system capability test to ensure that the system meets flow requirements. It also provides a complete flush of the system to remove any particulate matter which could conceivably result in plugging of the spray nozzles at a future time. At the completion of this test, the temporary test connections are removed, the pipe plugs are removed and the spray nozzles are installed. The subsystems then are ready for operation. With a complete system flush to remove all particulate matter prior to the installation of spray nozzles and with corrosion resistant nozzles and piping, it is not considered credible that a significant number of nozzles could become plugged during the life of the unit to reduce the effectiveness of the subsystems, therefore, no means are provided for intermittent testing of the nozzles using water flow. Nozzle tests are performed following maintenance that results in the potential for nozzle blockage as described below. Means are provided for intermittent testing of the quench spray pumps. This testing is performed periodically by opening the normally closed valves on the recirculation line returning water to the refueling water storage tank. Initiation of the subsystem allows the pumps to operate and recirculate water back to the tank. The purpose of the recirculation is to test pump operation and to detect the presence of particulate matter in the refueling water storage tank that could clog spray nozzles.

BVPS UFSAR UNIT 1 Rev. 29 6.4-15 Periodic activation of the containment depressurization signals ensures operability of the initiation signals and control circuitry. Prior to unit startup, an initial full flow system test with water is performed on the recirculation spray system, as follows:

1.

With the nozzle openings blocked off, temporary connections are made between the nozzle headers and the containment sumps.

2.

Sufficient water is then added to the containment sump so that a recirculation spray pump can recirculate water up through its respective cooler and header.

3.

The full flow test through the shell side initially ensures that the required recirculation spray for containment depressurization is achieved.

4.

Upon completion of the above system test, the water is drained from each recirculation spray cooler, the pumps, the headers and the sumps. The temporary connections between the headers and sumps are removed and the nozzles installed. Since the system is left in a dry, ready condition after the initial full flow tests, no further testing with water flow through the shell side of the recirculation spray heat exchangers is deemed necessary to ensure system capability. Periodic flow testing of the outside recirculation spray pumps is performed as follows:

1.

The pump discharge containment isolation valves are closed

2.

The pump casing is filled with water

3.

The test line valves are opened

4.

The pump is started, taking suction from the casing, discharging through the test line with its installed flow instrument and returning to the casing. Testing to verify that spray nozzles are not obstructed is performed following maintenance that results in the potential for nozzle blockage. A blind flange in the piping upstream of each spray header is provided for this purpose. Each nozzle is tested individually to verify that there is no flow blockage. Maintenance with the potential for nozzle blockage is determined by engineering evaluation as required by Technical Specifications. The volume and pH-raising effectiveness of the sodium tetraborate decahydrate buffer is surveilled each refueling outage to ensure the radiological and equipment qualification functions of the containment depressurization system will be fulfilled in the event of a LOCA. On January 11, 2008, the NRC issued Generic Letter 2008-01, Managing Gas Accumulation in Emergency Core Cooling, Decay Heat Removal, and Containment Spray Systems. Generic Letter 2008-01 requested licensees to evaluate the licensing basis, design, testing, and corrective action programs for the emergency core cooling, decay heat removal, and containment spray systems.

BVPS UFSAR UNIT 1 Rev. 32 6.4-16 As a result, the company performed evaluations that included the review of gas susceptible piping locations, the development of activities to monitor various piping locations as appropriate based on industry experience and plant specific experience, and acceptance of some generic locations that normally accumulate voids that do not adversely affect the design function(s) of the system. The company established a gas accumulation prevention and management program to ensure that gas accumulation is reasonably prevented or maintained less than the amount that challenges the functionality of the applicable systems and that appropriate action is taken when conditions adverse to quality are identified.

BVPS UFSAR UNIT 1 Rev. 29 6.4-17 References for Section 6.4

1.

Letter from Stephen H. Hanauer, Chairman, Advisory Committee on Reactor Safeguards, to Honorable Glenn T. Seaborg, Chairman, U.S.A.E.C., dated May 15, 1969, subject: "Report on Edwin I. Hatch Nuclear Plant" and letter from Stephen H. Hanauer, Chairman, Advisory Committee on Reactor Safeguards, to Honorable Glenn T. Seaborg, Chairman, U.S.A.E.C., dated May 15, 1969, subject: "Report on Brunswick Steam Electric Plant".

2.

Hilliard, et al, "Removal of Iodine Particles from Containment Atmosphere by Sprays", BNWL-1244, Battelle Pacific Northwest Laboratory (February 1970).

3.

Safety Evaluation by the Division of Reactor Licensing, Atomic Energy Commission in the Matter of Virginia Electric and Power Company, Surry Power Station - Units 1 and 2, Docket No. 50-280 and 50-281 (February 23, 1972).

4.

ASHRAE Handbook of Fundamentals, page 344 (1972).

5.

"ASTM Specification for Heat-Resisting Chromium and Chromium-Nickel Stainless Plate, Sheet, and Strip for Fusion-Welded Unfired Pressure Vessels", ASTM A-240, The American Society for Testing and Materials.

6.

The term "equivalent" is described in UFSAR Section 1.8.2, "Equivalent Materials."

BVPS UFSAR UNIT 1 Rev. 22 6.5-1 6.5 POST DBA HYDROGEN CONTROL SYSTEM 6.5.1 Hydrogen Recombiner and Purge System 10 CFR 50.44 was revised in 2003 to eliminate the requirement for hydrogen recombiners and hydrogen purge systems. Elimination was based on improved understanding of combustible gas behavior during severe accidents and confirmation that the hydrogen release postulated from a design-basis LOCA was not risk-significant because it was not large enough to lead to early containment failure, and that the risk associated with hydrogen combustion was from beyond design-basis accidents. The revised rule retained the requirement that containments for all currently licensed power plants ensure a mixed atmosphere. Also, it acknowledged the existing "industry-wide commitment" to include combustible gas control strategies in the severe accident management guidelines (SAMGs) as the basis for not including a requirement related to purging and/or venting capabilities. Section 14.3.4.4 addresses the mixed atmosphere requirement and plant SAMGs provide combustible gas control strategies that do not rely on the hydrogen recombiners or hydrogen purge blowers for beyond design-basis accidents. Therefore, there is no requirement to maintain the hydrogen recombiner and purge system. 6.5.2 Containment Hydrogen Analyzer System The containment hydrogen analyzer system consists of two redundant hydrogen monitors energized from separate Class lE Power supplies to provide protection against single failure and single loss of power. Containment samples are obtained through independent sample lines for each monitor. Indication is provided for each hydrogen analyzer, on the vertical board in the main control room, with an indicating range of 0-10 percent hydrogen. A recorder is provided to record the Train A hydrogen level. The hydrogen analyzer system is designed to provide a continuous positive indication of the containment hydrogen concentration within 30 minutes after the initiation of safety injection. The containment hydrogen analyzer system was added as a requirement of an NRC Order1 in response to NUREG 0737 TMI Issue II.F.1. The hydrogen analyzer units are located in the cable vault areas (Train "A" in the west cable vault and Train "B" in the east cable vault). The hydrogen analyzer units are of the thermal conductivity type. Each hydrogen analyzer has sampling lines running to two containment locations. One sample line from each analyzer connects to a dome snorkle line which runs to the top of the containment dome. The second sample line for each analyzer runs to a location high within the pressurizer cubicle. Each of the four sample lines contains silver zeolite filters which remove iodine from the air sample prior to leaving containment. All sample lines are sloped to loop seal drains which allow condensate to drain while preventing air from being drawn in through the drain. Each analyzer has one line for returning samples to containment. There are two normally closed (fail closed) solenoid operated valves on each sample and return line. One valve is located in containment and the other outside containment in the cable vault. The solenoid valves are remotely operated from the main control room with key switches. Valve position indicating lights (open/closed) are provided for each solenoid valve. The analyzer control panels located in the switchgear area contain supporting electronics, signal conditioning, digital readouts, recorder outputs, caution and high alarm setpoint controls, span gas controls, zero and span adjustments and main system power controls. Span gases are supplied directly to the analyzers to allow for periodic calibration of the units.

BVPS UFSAR UNIT 1 Rev. 22 Reference for Section 6.5 1. S. A. Varga, Jr. (USNRC) BVPS-1 Order Modifying License, letter to J. J. Carey (BVPS) (July 10, 1981). 6.5-2

BVPS UFSAR UNIT 1 Rev. 26 6.6-1 6.6 SUPPLEMENTARY LEAK COLLECTION AND RELEASE SYSTEM 6.6.1 Design Bases The supplementary leak collection and release system is designed according to the following criteria:

1.

The maintenance of 0.125 inch water gauge negative pressure in most areas contiguous to the containment (with the exception of the main steam valve area, the steam generator blowdown room, the purge air duct area, east cable vault and west cable vault), the waste gas storage area and the fuel building.

2.

The filtration by impregnated charcoal of contaminated air for radioactive iodine removal with individual charcoal cells sized for 600 cfm. The filters are not credited in the radiological analysis.

3.

The discharge of exhaust air at the SLCRS Vent.

4.

The use of redundant filter banks and exhaust fans with the fans operable/functional on emergency power.

5.

Equipment and system capability of withstanding the design basis earthquake without loss of function.

6.

Removal of heat from areas containing safety related equipment following a design basis accident with loss of offsite power.

7.

Maintain the containment contiguous areas below 10 CFR 50.49 radiological limits. 6.6.2 Description The elements of the supplementary leak collection and release system are shown in Figure 6.6-1. The design data is provided in Table 6.6-1. One function of the system is to ensure that radioactive leakage from recirculating ECCS systems following a DBA is filtered for iodine removal prior to discharge to the atmosphere at the SLCRS Vent. The filters are not credited in the dose consequence analysis. Another function of the system is the removal of heat from areas contiguous to containment where equipment important to safety is located (i.e., the charging pump cubicles, the low head safety injection pump cubicles, the recirculation spray pump cubicles, the auxiliary feedwater pump room, the east and west cable vaults, the MCC room, and the safeguards pipe tunnel). The heat removal function is also credited for minimizing the radiation level in these areas. Following a loss of offsite power, SLCRS is the only available means of assuring that components in these areas do not exceed the design temperatures and following an accident, do not exceed the radiological environmental levels associated with the Equipment Qualification (EQ) radiation zones. Temperature switches are provided to open SLCRS dampers when area temperatures exceed 110F.

BVPS UFSAR UNIT 1 Rev. 23 6.6-2 The supplementary leak collection and release system consists of two 100 percent capacity leak collection exhaust fans with a design capacity of 50,000 cfm each. Air is exhausted from the fuel building, waste gas storage area auxiliary building, blowdown tank room, personnel access hatch area, purge air duct area, east cable vault, pipe tunnel and north and west safeguards areas and, during refueling, the containment. The capacity of each fan is in excess of the estimated air inleakage to the containment contiguous areas, fuel building and waste gas storage area auxiliary building. An intake damper is provided at the suction header of the fans to provide makeup air. The excess capacity of the fan ensures a minimum of the required negative pressure in the exhausted areas. Provision is made in the various exhausted areas to permit confirmation that they are maintained at the required negative pressure. The provision made to confirm the maintenance of required negative pressure areas served by the supplementary leak collection and release system consists of the use of differential pressure gauges. These gauges are portable instruments which indicate pressure in inches water gauge either above or below the prevailing atmospheric pressure. Periodic observation of gauge pressure readings will confirm that the subject areas are maintained at the required negative pressure. In order to limit air leakage into the above structures to the capacity of a leak collection exhaust fan, penetration pipes, ducts and cables are sealed as required at or near the point where they pass from the contiguous structure to some other structure, e.g., the auxiliary building. Inleakage of air at doors in exhausted structures is limited by gasketing. Doors are either locked or are self-closing and are under administrative control. One of the leak collection exhaust fans is normally used to exhaust the various areas. The other fan is used as a standby. During normal operation, the exhaust to the fan does not go through filters. On a containment isolation phase A signal or a high-high radiation signal from monitors in the ventilation exhausts from the fuel building, the waste gas storage area, or from areas contiguous to the containment with the exception of the main steam valve cubicle, the leak collection system exhaust is diverted so that it first flows through one of the two parallel main filter banks before flowing to the leak collection exhaust fans. The other main filter bank is used as a backup. Each main filter bank consists of roughing filters, charcoal filters and pleated glass fiber type HEPA filters. The roughing filters remove large particulates to prevent excessive pressure drop buildup on the charcoal and HEPA filters. The charcoal filters are effective for radioactive iodine removal, and the HEPA filters, at a rated efficiency of 99.97 percent where tested with 0.30 micron diameter of particle, remove particulates and charcoal fines. Each charcoal filter is rated at 600 cfm. Each roughing and HEPA filter is rated at 1,200 cfm. It is of flat parallel tray design, containing approximately 44 lb of charcoal in two 2 inch beds having a total of about 8 sq ft of face area. The media is new impregnated activated coconut shell charcoal. The media particle size is from 8 to 16 U.S. Sieve mesh with not more than 5.0 percent retained on 8 mesh nor more than 5.0 percent passing through 16 mesh. Charcoal cells are leak tested in accordance with Technical Specifications. Charcoal filter efficiency is based on the attenuation of radioactive iodine with a minimum composite efficiency of 95 percent.

BVPS UFSAR UNIT 1 Rev. 23 6.6-3 A heat detection and alarm and automatically actuated water spray deluge system is provided for the charcoal cells to maintain cooling of the media and prevent ignition in the event of decay heat buildup. The leak collection exhaust fans discharge through a duct to the SLCRS Vent. The SLCRS Vent is located on the top of the containment structure. The containment extends 144 ft above grade. The duct and supporting structure is designed to accommodate seismic forces. The release above the containment is a high-velocity discharge at an elevation of 150 ft above grade. During refueling, the fuel building is normally maintained at negative pressures of 0.125 inches of water column, by the operating leak collection exhaust fan. During Mode 6, SLCRS ventilation damper VS-D-4-18A may be closed and the upstream containment contiguous areas may not be ventilated. If there should be a fuel building high-high radiation signal, the exhaust from the fuel building along with the rest of the leak collection system exhaust, may be diverted to one of the main filter banks in the leak collection release system before being released at the SLCRS Vent. 6.6.3 Evaluation The supplementary leak collection and release system incorporates redundant 100 percent capacity leak collection exhaust fans and main filter banks. In addition, there are redundant dampers where required. The redundant fans and dampers are connected to different emergency buses, which are capable of being supplied either from normal or emergency power sources. Thus, there is sufficient redundancy in the system to ensure system reliability. Proper operation of the system is further ensured by the capability for testing the system periodically. The instrumentation, control and electrical equipment of the supplemental leak collection system are in accordance with IEEE 279(1)-1971 and IEEE 308(2)-1971 with one exception. IEEE 279-1971 requires that the "protection system shall, with precision and reliability, automatically initiate appropriate protective action whenever a condition monitored by the system reaches the preset level". It also requires that this be accomplished with a single failure. The exhausts from the contiguous areas, (with the exception of the main steam valve cubicle), the fuel building and the waste gas storage area auxiliary building are each monitored by a radiation monitor which automatically diverts the exhaust through a filter path when the radiation reaches a preset level. Should any of these systems fail, a redundant backup radiation monitor, located in the SLCRS Vent duct, would indicate and alarm to the operator that the preset level had been reached, which would alert the operator to manually divert the exhaust through the filters. The automatic and manual systems are redundant and on separate power supplies. The post accident dose from radioactivity released from the contiguous and waste gas storage areas is expected to be much less than specified by the guidelines described in Section 14.3.5 and Section 11.2.3.4, respectively.

BVPS UFSAR UNIT 1 Rev. 22 6.6-4 The supplementary leak collection and release system collects, filters and releases at an elevated point (SLCRS Vent) the leakage from the containment following a DBA. Essentially, all the leakage from the containment following a DBA flows into those containment contiguous areas which house the various containment penetrations and the engineered safeguards equipment circulating radioactive water. Although a negative pressure of.125 inch water gauge in the areas contiguous to Containment is adequate to prevent exfiltration under DBA conditions, no credit has been taken for the collection of containment leakage through any electrical penetration in the LOCA analysis of Section 14.3. Such leakage is modeled as the release of.1% volume per day directly to the environment without regard to the specific location of the containment isolation failure. Similarly, no credit is taken for collection and filtration by the SLCRS of leakage from ESF piping systems and components that recirculate containment sump water outside the containment. However, a negative pressure of.125 inch water gauge is required for these areas. 6.6.4 Tests and Inspections All systems are tested and inspected as separate components and as an integrated system. The testing and visual inspection of all equipment and systems is in accordance with the Technical Specifications. Anemometer or velometer readings are taken to ensure that all air systems are balanced to exhaust the required air quantities at design conditions, for the purposes of maintaining negative pressure and removing heat from safety related equipment. Materials and construction methods for ventilation systems are inspected for compliance with National Fire Protection Association (NFPA) Standard 90A(3) and NFPA Standard 91.(4) Capacity and performance of centrifugal fans conform to the required conditions and are tested or rated for compliance with Advanced Material Concept Agency (AMCA) test codes and certified ratings program. Filter cells are individually tested after fabrication and again as an integrated system after installation. Filter banks are tested for leakage while in place using methods outlined in the operating Technical Specifications. Defective cells are replaced where test requirements are not satisfied. The frequency of and requirements for the tests are given in the Technical Specifications.

BVPS UFSAR UNIT 1 Rev. 19 6.6-5 References for Section 6.6

1.

"IEEE Criteria for Protection Systems for Nuclear Power Generating Stations," IEEE-279-71, The Institute of Electrical and Electronic Engineers.

2.

"IEEE Standard Criteria for Class lE Electric Systems for Nuclear Power Generating Stations," IEEE-308-71, The Institute of Electrical and Electronic Engineers.

3.

"NFPA Standard for The Installation of Air Conditioning and Ventilation Systems," NFPA Std. 90A, The National Fire Protection Association.

4.

"NFPA Standard for the Installation of Blower and Exhaust Systems for Dust Stock and Vapor Removal or Conveying," NFPA Std. 91, The National Fire Protection Association.

BVPS UFSAR UNIT 1 TABLES FOR SECTION 6

BVPS UFSAR UNIT 1 Rev. 19 1 of 8 Table 6.2-1

SUMMARY

OF REQUIRED EXAMINATION AND TESTS FOR NUCLEAR PIPING Material Group Q1 Group Q2 Group Q3 Identification (May be in addition to requirements of the ASTM material specification)

1.

Specification and grade Required for each length or part. Required for each length or part. Required for each length or part.

2.

Heat number and piping classification number Required for each length or part. Required for each length or part. Required for each length or part. Examination and Test

1.

Seamless and welded (without filler metal) tubular products and fittings In accordance with material specification and complete examination by either of the following: In accordance with material specification. In accordance material specification.

1.

Ultrasonic examination.

2.

Eddy Current examination.

3.

Radiography plus magnetic particle or liquid penetrant examinations on accessible surfaces.

4.

Magnetic particle or liquid penetrant examination on all surfaces, both inside and outside.

5.

A combination of these methods.

BVPS UFSAR UNIT 1 Rev. 19 2 of 8 Table 6.2-1 (CONTD)

SUMMARY

OF REQUIRED EXAMINATION AND TESTS FOR NUCLEAR PIPING Examination and Test Group Q1 Group Q2 Group Q3

2.

Welded (with filler metal) tubular products and fittings In accordance with material specification and examinations as follows:

1.

All longitudinal or girth welds made in accordance with ASTM A-155 or A-358 for pipe and the WPW grades of ASTM A-234, A-403 and A-420 for fittings shall be completely examined by radiography. In accordance with material specification ASTM A-144 Class 1 or A-358 Class 1 do not require supplementary examination. All welds made with filler metal in fittings as per WPW grades of A-234, A-403 and A-420 shall be completely radiographed. In accordance with material specification

2.

The accessible surface of the welds and heat-affected zone of the base metal adjacent to the welds shall be examined by magnetic particle or by liquid penetrant methods.

3.

Plates used in fabrication of pipe and fittings In accordance with material specification and complete examination by ultrasonic method in accordance with ASTM A-435 to cover entire surface of plate. In accordance with material specification. In accordance with material specification.

BVPS UFSAR UNIT 1 Rev. 19 3 of 8 Table 6.2-1 (CONTD)

SUMMARY

OF REQUIRED EXAMINATION AND TESTS FOR NUCLEAR PIPING Examination and Test Group Q1 Group Q2 Group Q3

4.

Forgings and bar used in fabrication of flanges and fittings (over 2 inches in size) In accordance with material specification and examination by the ultrasonic method in the as furnished or finished condition and by the magnetic particle or liquid penetrant method in the finished condition. In accordance with material specification. In accordance with material specification.

5.

Static or centrifugally cast pipe and fittings In accordance with material specification. Statically cast items shall be examined by radiographic methods. Centrifugally cast products may be examined by ultrasonic methods in lieu of radiography if it can be demonstrated that a meaningful examination can be made. All ferritic steel castings over 12 inches thick shall be examined by both radiographic and ultra-sonic methods. In addition all cast products shall be examined by either magnetic particle or liquid penetrant methods. In accordance with material specification. Examination to be same as for Group Q1. In accordance with material specification.

BVPS UFSAR UNIT 1 Rev. 19 4 of 8 Table 6.2-1 (CONTD)

SUMMARY

OF REQUIRED EXAMINATION AND TESTS FOR NUCLEAR PIPING Examination and Test Group Q1 Group Q2 Group Q3

6.

Bolting Visual examination shall be applied after final heat treatment to the areas of threads, shanks and heads of final machined parts. Harmful discontinuities such as laps, seams or cracks that would be detrimental to the intended service are unacceptable. All bolts, studs and nuts greater than 1 inch nominal bolt size shall be examined by the magnetic particle method in accordance with ASTM E-109 and E-138 or the liquid penetrant method in accordance with ASTM E-165. This examination shall be performed on the finished component after threading or on the material stock at approximately the finished diameter before threading and after heading (if involved). Linear nonaxial indications are unacceptable. Linear axial indications greater than 1 inch in length are unacceptable.

BVPS UFSAR UNIT 1 Rev. 29 5 of 8 Table 6.2-1 (CONTD)

SUMMARY

OF REQUIRED EXAMINATION AND TESTS FOR NUCLEAR PIPING Welding Group Q1 Group Q2 Group Q3 Girth Butt Welds

a. Radiography 100% required.

100% required. Not required.

b. Magnetic Particle 100% required Not required.

100% required over

c. Liquid Penetrant of (b) or (c).

Not required. 4 inch pipe size of (b) or (c). Longitudinal Butt Welds

a. Radiography 100% required.

100% required. Not required.

b. Magnetic Particle 100% required Not required.

100% required over

c. Liquid Penetrant of (b) or (c).

Not required. 4 inch pipe size of (b) or (c) Fillet and Socket Welds

a. Radiography Not required.

Not required. Not required.

b. Magnetic Particle 100% required 100% required 100% required over
c. Liquid Penetrant of (b) or (c).

of (b) or (c). 4 inch pipe size of (b) or (c). Seal Welds

a. Radiography Not required.

Not required. Not required.

b. Magnetic Particle 100% required 100% required Not required.
c. Liquid Penetrant of (b) or (c).

of (b) or (c). Not required.

BVPS UFSAR UNIT 1 Rev. 19 6 of 8 Table 6.2-1 (CONTD)

SUMMARY

OF REQUIRED EXAMINATION AND TESTS FOR NUCLEAR PIPING Welding Group Q1 Group Q2 Group Q3 Welded Branch Connections

a. Radiography 100% required over 4 inch pipe size.

100% required over 4 inch pipe size. Not required.

b. Magnetic Particle 100% required 100% required on 100% required over
c. Liquid Penetrant of (b) or (c).

4 inch and under of (b) or (c). 4 inch pipe size of (b) or (c). Attachment Welds - Supports, Legs, Anchors and Guides

a. Radiography Not required.

Not required. Not required.

b. Magnetic Particle 100% required 100% required Not required.
c. Liquid Penetrant of (b) or (c).

of (b) or (c). Not required. Miscellaneous Requirements

1. Welding and brazing materials Shall conform to requirements of Section IX of the ASME Boiler and Pressure Vessel Code.

Same as for Group Q1. Same as for Group Q1.

BVPS UFSAR UNIT 1 Rev. 19 7 of 8 Table 6.2-1 (CONTD)

SUMMARY

OF REQUIRED EXAMINATION AND TESTS FOR NUCLEAR PIPING Miscellaneous Requirements Group Q1 Group Q2 Group Q3 Materials not incorporated in Section IX may be used if a procedure qualification test is successfully made in accordance with Section IX. Materials shall be clearly identified on the package or container and shall remain legible until the material is actually consumed in the process. Identification shall include material specification grade and classification number, supplier's name and trade designation and the control or heat number.

2.

Erected Pipe System

a. Hydrostatic Test All installed piping shall be tested by a hydrostatic test at test pressures specified in line designation tables prior to initial operation to demonstrate leak tightness.

Same as Group Q1. Same as Group Q1.

BVPS UFSAR UNIT 1 Rev. 19 8 of 8 Table 6.2-1 (CONTD)

SUMMARY

OF REQUIRED EXAMINATION AND TESTS FOR NUCLEAR PIPING Miscellaneous Requirements Group Q1 Group Q2 Group Q3

b. Pneumatic Test A pneumatic test may be substituted where a hydrostatic test is not practicable. There shall be no leakage for satisfactory performance of the tests.
c. Mass Spectrometer and Halide Leak Test Systems with conditions of operation and design that require leak tightness of a greater degree of sensitivity than can be obtained by a hydrostatic or pneumatic test shall be leak tested by other methods, such as helium mass spectrometer leak test or halide leak test, which have the required sensitivity.

BVPS UFSAR UNIT 1 Rev. 23 1 of 2 Table 6.2-2 DRAWINGS SHOWING PIPING CLASS INFORMATION The piping class information shown on the station drawings listed below is incorporated by reference into the UFSAR. Other information presented on these drawings is not considered part of the UFSAR. The contents of these station drawings are controlled by station procedure. SYSTEM STATION DRAWING Reactor Coolant System RM-37A RM-37B Containment Vacuum & Leakage Monitoring System RM-412-1 Safety Injection System RM-411-1 RM-411-2 Containment Depressurization System RM-513-1 RM-513-2 Post DBA Hydrogen Control System RM-546-1 Post DBA Hydrogen Analyzer System RM-546-2 Chemical and Volume Control System RM-39A RM-39B Boron Recovery System RM-29A RM-29B Residual Heat Removal System RM-410-1 Primary Plant Component Cooling Water System RM-22A RM-22B RM-22C RM-22D RM-22E Fuel Pool Cooling and Purification System RM-420-1 Sample System RM-32A RM-32B Vent and Drain System RM-34A RM-34B Compressed Air System RM-434-1 Instrument Air & Containment Instrument Air System RM-434-2 River Water System (Flow Diagram Intake Structure) RM-430-1 RM-430-2 RM-430-3 RM-430-4

BVPS UFSAR UNIT 1 Rev. 20 2 of 2 Table 6.2-2 (CONT'D) DRAWINGS SHOWING PIPING CLASS INFORMATION SYSTEM STATION DRAWING Fuel Oil System for Emergency Diesel Generators RM-53A Main Steam System RM-14A Auxiliary Steam and Air Removal System RM-16A Feedwater System RM-18A Steam Generator Blowdown RM-50A Gaseous Waste Disposal System RM-43A RM-43B

BVPS UFSAR UNIT 1 Rev. 32 1 of 2 Table 6.3-1 SINGLE ACTIVE FAILURE ANALYSIS ECCS Component Malfunction Comments A. Accumulator (injection phase) Delivers to broken loop Totally passive system with one accumulator per loop. Evaluation based on two accumulators delivering to the RCS and one spilling from ruptured loop after termination of bypass. B. Pump: (injection phase)

1) Safety injection charging Fails to start Three provided. Evaluation based on operation of one.
2) Low head safety injection Fails to start Two provided. Evaluation based on operation of one.

C. Automatically Operated Valves: (one on safety injection signal) - (injection phase)

1) Boron injection tank outlet isolation valves at discharge of high head safety injection pumps.

(cold leg injection) Fails to open One of two parallel valves is required to open.

2) Accumulator stop valves Fails to open One valve per accumulator, normally open, or opened if initially closed.

Analysis assumes all three accumulator stop valves are open.

3) Refueling water storage tank to charging pump suction valves Fails to open Two valves; only one valve in either line is required to open.

D. Valves automatically closed on Safety Injection Signal

BVPS UFSAR UNIT 1 Rev. 31 2 of 2 Table 6.3-1 (CONTD) SINGLE ACTIVE FAILURE ANALYSIS ECCS

1) Charging line injection Fails to close Two valves in series; only one valve required to close.
2) Volume control tank outlet Fails to close Two valves in series; only one valve required to close.

E. Valves Operated on Automatic Transfer From Safety Injection to Recirculation

1) MOV-SI862A or B (Close to realign LHSI pump suction from the refueling water storage tank)

Fails to close The affected LHSI pump would continue to take suction from the RWST until pump NPSH was lost. However, operation of the LHSI pump on the other parallel suction path would be unaffected. Since minimum safeguards analysis is based on only one LHSI pump operation, the single failure criteria is satisfied.

2) MOV-SI860A or B (Open to realign LHSI pump suction to the containment sump)

Fail to open The affected LHSI pump would lose NPSH as its associated RWST valve closed. However, operation of the LHSI pump on the other parallel suction path would be unaffected. Since minimum safeguards analysis is based on only one LHSI pump operating, the single failure criterion is not violated. Closure of RWST valve prevents containment sump water from entering the RWST.

3) MOV-SI885 A, B, C or D (Close to prevent LHSI pump discharge back to the RWST)

Failure to Close There are redundant (2) valves in series in each of the LHSI pump minimum flow bypass lines to the RWST. Should one of these valves fail to close the other valve in the associated line would close, thus meeting the single failure criterion.

4) MOV-SI863A or B (Open to align LHSI pump discharge to charging pump suction)

Failure to Open The LHSI pumps supply a common charging pump suction header via independent parallel paths. Should one of the paths be blocked, the other LHSI pump would adequately supply the suction header, thus meeting single failure criterion.

5) MOV-CH115B or D (Close to realign charging pump suction from RWST)

Failure to Close A check valve (SI-27) on the common line supplying both parallel valves will prevent flow returning to the RWST should either valve fail to close. Therefore, the single failure of either of the valves will not permit return flow to the RWST.

BVPS UFSAR UNIT 1 Rev. 19 1 of 1 Table 6.3-2 ECCS - CODE REQUIREMENTS Component Code Accumulators ASME Section III Class C Boron Injection Tank ASME Section III Class C Valves ANSI B16.5 Piping ANSI B31.1

BVPS UFSAR UNIT 1 Rev. 32 1 of 4 Table 6.3-3 READOUTS ON THE CONTROL BOARD WHICH OPERATOR CAN MONITOR DURING INJECTION PHASE VALVES(1) FSAR Actuation Position Figure on Injection Valve No. Description 6.3-8 Normally Closed MOV-SI836 ALT. HI-HEAD COLD LEG ISOLATION 6.3-8 Open MOV-SI867 C, D B.I.T. OUTLET ISOLATION VALVES 6.3-1 Normally Open MOV-SI865 A, B, C(2)(3) S.I. ACCUM ISOLATION VALVES 6.3-8 Normally Open MOV-SI890 C(2)(3) LOW-HEAD S.I. ISOLATION TO COLD LEGS 6.3-8 Normally Open MOV-SI862 A, B LOW-HEAD S.I. PUMP RWST ISOLATION 6.3-8 Normally Closed MOV-SI860 A, B CONTAINMENT SUMP ISOLATION VALVES 6.3-8 Normally Closed MOV-SI863 A, B LOW-HEAD TO HI-HEAD S.I. PUMP ISOLATION 6.3-8 Normally Open MOV-SI864 A, B LOW-HEAD S.I. PUMP DISCHARGE CROSS-CONNECT ISOLATION

BVPS UFSAR UNIT 1 Rev. 19 2 of 4 Table 6.3-3 (CONT'D) READOUTS ON THE CONTROL BOARD WHICH OPERATOR CAN MONITOR DURING INJECTION PHASE VALVES(1) 6.3-8 Normally Open MOV-SI885 A, B, C, D(2) LOW-HEAD S.I. PUMP MINIFLOW ISOLATION 6.3-8 Normally Closed MOV-SI869 A, B HI-HEAD S.I. HOT LEG 6.3-8 Normally Closed MOV-SI890 A, B LOW-HEAD, HOT LEG POST ACCIDENT RECIRC. ISOLATION 6.3-8 Closed MOV-CH289 NORMAL CHARGING ISOLATION OUTSIDE CONTAINMENT 6.3-8 Closed MOV-CH310 NORMAL CHARGING ISOLATION INSIDE CONTAINMENT 6.3-8 Closed MOV-LCV-CH 115 C, E VCT TO CHARGING PUMP ISOLATION 6.3-8 Open MOV-LCV-CH 115 B, D RWST TO HI-HEAD S.I./ CHARGING PUMP ISOLATION

BVPS UFSAR UNIT 1 Rev. 19 3 of 4 Table 6.3-3 (CONT'D) READOUTS ON THE CONTROL BOARD WHICH OPERATOR CAN MONITOR DURING INJECTION PHASE INSTRUMENTS FSAR Figure Instrument No. Description 6.3-8 FI-SI946 Low Head S.I. Pump B Flow 6.3-8 FI-SI945 Low Head S.I. Pump A Flow 6.3-8 FI-SI943 Cold Leg Hi-Head Inj. Header Flow 6.3-8 FI-SI940 Hot Leg Hi-Head Recirculation Header Flow 6.3-8 FI-SI960 Loop 2 Hot Leg Hi-Head Recirculation Flow 6.3-8 FI-SI961 Loop 1 Cold Leg Hi-Head Inj. Flow 6.3-8 FI-SI962 Loop 2 Cold Leg Hi-Head Inj. Flow 6.3-8 FI-SI963 Loop 3 Cold Leg Hi-Head Inj. Flow 6.3-8 FI-SI932 Loop 3 Hot Leg Hi-Head Recirculation Flow 6.3-8 FI-SI933 Loop 1 Hot Leg Hi-Head Recirculation Flow

BVPS UFSAR UNIT 1 Rev. 27 4 of 4 Table 6.3-3 (CONT'D) READOUTS ON THE CONTROL BOARD WHICH OPERATOR CAN MONITOR DURING INJECTION PHASE PUMPS FSAR Figure Pump 6.3-8 Low Head Safety Injection 6.3-8 Safety Injection Charging 6.4-1A Quench Spray 6.4-1B Recirculation Spray Notes: (1) Individual position lights are provided to indicate the full open or full closed position of each valve. (2) Valves actuate a combination light and alarm if not fully open. (3) If valve position is not corrected after alarm defined by note two occurs, an hourly reflash will occur.

BVPS UFSAR UNIT 1 Rev. 19 1 of 2 Table 6.3-4 QUALITY STANDARDS OF ECCS COMPONENTS PUMPS A. Tests and Inspection

1.

Performance test

2.

Dye penetrant of pressure retaining parts

3.

Hydrostatic test B. Special Manufacturing Process Control

1.

Weld, NDT and inspection procedures review and approval

2.

Surveillance of suppliers quality control system and product ACCUMULATORS AND BORON INJECTION TANK A. Tests and Inspections

1.

Hydrostatic test

2.

Radiography of longitudinal and girth welds

3.

Dye penetrant/magnetic particle of weld B. Special Manufacturing Process Control

1.

Weld, fabrication, NDT and inspection procedure and review

2.

Surveillance of suppliers quality control and product VALVES I. Tests and Inspections A. 200 psig and 200 F or below (stainless steel valves only)

1.

Dye penetrant test

2.

Hydrostatic test

3.

Seat leakage test B. Above 200 psig and 200 F

1.

Forged valves

a.

UT of billet prior to forging

b.

Dye penetrant check 100 percent of accessible areas after forging

c.

Hydrostatic test

d.

Seat leakage test

BVPS UFSAR UNIT 1 Rev. 19 2 of 2 Table 6.3-4 (Cont'd) QUALITY STANDARDS OF ECCS COMPONENTS

2.

Cast valves

a.

Radiograph 100 percent(1)

b.

Dye penetrant check all accessible areas(1)

c.

Hydrostatic test

d.

Seat leakage test C. Performance Tests Required for:

1.

Motor-operated valves

2.

Auxiliary relief valves

3.

Air-operated valves D. Auxiliary relief valves (these valves are not included in the above categories)

1.

100 percent dye penetrant check of nozzles and disks

2.

100 percent dye penetrant check of bodies(1)

3.

Hydrotest bodies, nozzles and disks

4.

Seat leakage test

5.

Operational tests II. Special Manufacturing Process Control A. Weld, NDT, performance testing, assembly and inspection procedure review B. Surveillance of suppliers quality control and product C. Special weld process procedure qualification (e.g. hard facing) Notes: (1) For valves with radioactive service only.

BVPS UFSAR UNIT 1 Rev. 23 1 of 1 Table 6.3-5 ACCUMULATOR DESIGN/OPERATING PARAMETERS Number 3 Type Stainless steel lined/ carbon steel Design pressure, psig 700 Design temperature, F 300 Operating temperature, F 100 to 150 Normal Operating Pressure, psig 685 Minimum Operating Pressure, psig 611 Total Volume, ft3 1,450 Water Volume at Operating Conditions, gallons 6,681 to 7,645(2) Minimum Boron Concentration (as boric acid), ppm 2,300 Relief Valve Setpoint, psig(1) 700 (1) The relief valves have soft seats and are designed and tested to ensure zero leakage at the normal operating pressure. (2) The volumes do not include the tank undeliverable volume below the elevation of the discharge nozzle. The discharge piping volume is also not included in this value.

BVPS UFSAR UNIT 1 Rev. 31 1 of 1 Table 6.3-6 TANK DATA BORON INJECTION TANK Number 1 Total Volume, gallons 900 Design Pressure, psig 2,735 Design Temperature, F 300 Operating Pressure, nominal, psig 100 Material Stainless steel clad/ carbon steel

BVPS UFSAR UNIT 1 Rev. 31 1 of 1 Table 6.3-7 PUMP PARAMETERS Safety Injection Charging Pumps Number of Pumps 3 Design Pressure, Discharge, psig 2,800 Design Pressure, Suction, psig 200 Design Temperature, °F 300 Design Flow Rate, gpm 150 Maximum Flow Rate, gpm 580 Runout Design Head, ft 5,800 (minimum) Type Horizontal centrifugal Low Head Safety Injection Pumps Number of Pumps 2 Type Vertical centrifugal Design Pressure, Discharge, psig 300 (150 lb ASA discharge flange) Design Temperature, °F 300 Design Flow, gpm 3,000 Design Head, ft 257 Maximum Flow Rate, gpm 4,000

BVPS UFSAR UNIT 1 Rev. 19 1 of 1 Table 6.3-8 ECCS RELIEF VALVE DATA Descriptions Fluid Discharged Fluid Inlet Temp. Normal °F Temp. Relieving Fluid °F Set Pressure Psig Back Pressure Constant Psig Build-Up Capacity N2 supply to Accumulators N2 120 70 700 0 0 1,500 scfm LHSI Pump Discharge Water 120 120 235 3 50 20 gpm Boron Injection Boric Acid 165 180 2,735 3 12 20 gpm Tank Relief Solution Accumulator Water or 120 120 700 0 0 1,500 scfm to Containment N2 Gas

BVPS UFSAR UNIT 1 Rev. 19 1 of 1 Table 6.3-9 NOMINAL (DESIGN) EXTERNAL RECIRCULATION LOOP LEAKAGE (SAFETY INJECTION SYSTEM ONLY) Leakage to Leakage to No. of Type of Leakage Control and Unit Atmosphere, Vent and Drain Items Units Leakage Rate cc per hr System, cc per hr

1.

Low Head Safety Injection Pumps 2 Tandem mechanical seal with demineralized water interface between seals - leakage essentially zero(1) 0 0

2.

Safety Injection Charging (High Head) Pumps 3 Mechanical seal with leakoff - (10 cc/hr/seal) 2 seals per pump 0 60

3.

Flanges:

a.

Pumps Gasket - adjusted to zero leakage following any test - ten drops per (1) LHSI 2 minute, per flange (30 cc/hr) 60 0 (2) HHSI 15 450 0

b.

Misc. large valves 57 Gasket and/or packed stems (20 cc/hr) 1,140 0 > 2 inches

c.

Misc. flanges 10 Gasket - ten drops per minute, per flange (30 cc/hr) 300 0

4.

Misc. Small Valves < 2 inches 144 Gasket and/or packed stems (3 cc/hr) 432 0 TOTALS 2,382 60 (1) Seals are acceptance tested to essentially zero leakage.

BVPS UFSAR UNIT 1 Rev. 19 1 of 1 Table 6.3-11 TABLE OF FAULT PROBABILITIES Motor Starter Au. 5 x 10-7/hr P (failure during mission) = Closed contacts 5 x 10-7 hr-1 x 0.1 hr = 5 x 10-8 Short Out Manual Switch 7.5 x 10-8/hr P (failure during mission) = Closing Contacts 7.5 x 10-8 hr-1 x 0.1 hr = 7.5 x 10-9 Short Out Hot Short in 1.0 x 10-9/hr P (failure during mission) = Cable Run - 1.0 x 10-9 hr-1 x 0.1 hr = 1 x 10-10 Voltage to closing coil Hot Short in 1.0 x 10-9/hr P (failure during mission) = MCC-bypasses 1.0 x 10-9 hr-1 x 0.1 hr = 1 x 10-10 Switch (closed) contact only Operator Fails to 1 x 10-3/hr P (no action for 1 shift) = Take Action On 10-3/hr-1 x 8 hr = 8 x 10-3 Light Indication Limitorque Fails 7.5 x 10-8/hr P (limitorque failure/shift) = Indicating Open .75 x 10-7/hr-1 x 8 hr = 6 x 10-7 Operator Fails to 1 x 10-3/main-P (error for 1 shift) = Open Valve After tenance 10-3 x 1 maint x 8 hr = 9 x 10-7 Maintenance maint 8.8 x 103 hr

BVPS UFSAR UNIT 1 Rev. 32 1 of 1 Table 6.3-12 NORMAL/ACCIDENT FUNCTIONS EVALUATION Normal Operating Normal Operating Accident Accident Component Function Arrangement Function Arrangement Boron Injection Tank(1) None Lined up from the discharge of safety injection charging pumps to the closed BIT outlet valves. Pathway to RCS Lined up to discharge of safety injection charging pumps for cold leg injection Refueling Water Storage Tank Storage tank for refueling water Lined up to suction of high head safety injection charging, low head safety injection and containment depressurization system quench pumps Source of borated water for core and containment cooling Lined up to suction of safety injection charging, low head safety injection and containment depressuri-zation system quench pumps. (1) During normal operation the boron injection tank is isolated from the cold leg by redundant parallel BIT outlet valves, both of which receive a signal to open via the safety injection signal. Accumulators (3) None Lined up to discharge to cold legs of reactor coolant piping Fast supply of borated water to core Lined up to discharge to cold legs of reactor coolant piping Safety Injection Charging Pumps (3) Charging Take suction from volume control tank and discharge to normal charging connections Supply borated water to core Lined up to take suction from RWST or low-head safety injection pumps and discharge to cold legs of reactor coolant piping Low Head Safety Injection Pumps (2) Refueling fill or refueling cavity Lined up to take suction from refueling water storage tank and discharge to cold legs of reactor coolant piping Supply borated water to core Lined up to take suction from refueling water storage tank and discharge to reactor coolant system cold legs during injection phase or recirculation phase lined up to RCS hot or cold legs

BVPS UFSAR UNIT 1 Rev. 19 1 of 1 Table 6.3-13 ACCUMULATOR INLEAKAGE(1) Observed Leak Rate, Time Period Between cc per hr Level Adjustments 543 1 month 272 2 months 30.3 18 months (1) A total of 14 cubic feet, added to the initial amount, can be accepted in each accumulator before an alarm is sounded.

BVPS UFSAR UNIT 1 Rev. 27 1 of 3 Table 6.4-1 QUENCH SPRAY SUBSYSTEM COMPONENT DESIGN DATA Refueling Water Storage Tank Number 1 Capacity, gallons 441,100 Design pressure Atmospheric Design temperature, F 150 Operating pressure Atmospheric Operating temperature,F Per requirements of Technical Specification and Licensing Requirements Manual Material(2) ASTM A240 Type 304L Refueling Water Storage Tank Coolers Number 2 Design Duty, Btu/hr 375,000 Shell Tube Fluid Chilled Water Refueling Water Design pressure, psig 100 100 Design temperature, F 250 250 Operating 35 to 70 45 to 140 temperature, F Operating pressure, 75 85 psig Material(2) ASME SA-53-B ASTM A249 Type 304

BVPS UFSAR UNIT 1 Rev. 27 2 of 3 Table 6.4-1 (CONTD) QUENCH SPRAY SUBSYSTEM COMPONENT DESIGN DATA Quench Spray Pumps Number 2 Type Horizontal, Centrifugal Motor horsepower 200 Seals Single Mechanical Capacity, gpm 2,500 Head at rated capacity, ft 270 Design pressure, psig 250 Design temperature, F 45 Materials(2) Pump casing ASTM A351 CF8 Shaft ASTM A182 F-316 Impeller ASTM A351 CF8 Refueling Water Circulation Pumps Number 2 Type Horizontal, Centrifugal Motor horsepower 15/3.7(1) Capacity, gpm 375/36(1) Head at rated capacity, ft 70/31(1) Design pressure, psig 225 Operating temperature, F 45-100

BVPS UFSAR UNIT 1 Rev. 27 3 of 3 Table 6.4-1 (CONTD) QUENCH SPRAY SUBSYSTEM COMPONENT DESIGN DATA Refueling Water Circulation Pumps (Contd) Materials(2) Pump casing ASTM A-296 - CF8M Shaft ASTM A-276 - Type 316 Impeller ASTM A-296 - CF8M NOTES: (1) Two speed pumps (2) Materials listed in this table may be replaced with materials of equivalent design characteristics. The term "equivalent" is described in UFSAR Section 1.8.2, "Equivalent Materials."

BVPS UFSAR UNIT 1 Rev. 19 1 of 2 Table 6.4-2 COMPONENT DESIGN DATA FOR THE RECIRCULATION SPRAY SUBSYSTEMS Recirculation Spray Pumps Number 4 Type Vertical-deep well type turbine Motor horsepower 300 Seals Tandem Mechanical seal plus mechanical throttle bushing (outside) (inside) Capacity, gpm 3,300 TDH at rated capacity, ft 260 Design Pressure, psig 265 Design Temperature, °F 280 Materials(4) Pump bowls ASTM A351-CF8 Shaft 17-4 pH Impeller ASTM CF8 Recirculation Spray Coolers RS-E-1A & 1C RS-E-1B & 1D Number 2 2 Design Duty, Btu per hr(3) 61 x 106 59.25 x 106 Shell Tube Shell Tube Fluid Recirculated Ohio River Recirculated Ohio River spray water water spray water water Design Pressure, psig 150 int. 150 int. on tubes and channel 150 int. 150 int. on tubes and channel Design Temperature, °F 280 280 280 280 Operating Temperature, °F 139 in 85 in 142.9 in 90 in 104 out(1) 115.6 out(1) 105.3 out(1) 119.5 out(1)

BVPS UFSAR UNIT 1 Rev. 22 2 of 2 Table 6.4-2 (CONTD) COMPONENT DESIGN DATA FOR THE RECIRCULATION SPRAY SUBSYSTEMS RS-E-1A & 1C RS-E-1B & 1D Shell Tube Shell Tube Operating Pressure, psia 115 int. at 65 int. at inlet 115 int. at 65 int. at inlet inlet and channel inlet and channel Material(4) Stainless Stainless Stainless Stainless Steel - Steel - Steel - Steel - Type 304L Type 304L Type 304L Type AL6XN(2) NOTES: (1) Temperatures vary as a function of time following a DBA. (2) A low carbon, high purity, nitrogen bearing super austenitic stainless steel manufactured by Allegheny Ludlum. (3) Original design for RS-E-1A & 1C did not include fouling factor. Rerated conditions for heat exchangers based on fouling factors, higher allowable river water temperature, and better defined containment conditions, provide a minimum rating for RS-E-1A and 1C used in containment analysis, that is other than the original design specification. (4) Materials listed in this table may be replaced with materials of equivalent design characteristics. The term equivalent is described in UFSAR Section 1.8.2, Equivalent Materials.

BVPS UFSAR UNIT 1 Rev. 19 1 of 4 Table 6.4-3 CONSEQUENCES OF COMPONENT MALFUNCTIONS IN THE CONTAINMENT DEPRESSURIZATION SYSTEM Components Malfunction Comments and Consequences

1.

Quench Pumps Pump casing ruptures The casing is designed for 450°F temperature; standard test pressure is 250 psig and maximum test pressure is 375 psig. These conditions exceed those which could occur during any operating conditions. The casings are made from cast steel (ASTM A351-CF8) or equivalent;(1) this metal has corrosion-erosion resistance and produces sound castings. The pumps conform to Seismic Category I design. Pumps are missile protected and may be inspected at any time. Rupture by missiles is not considered credible. Rupture of the pump casing is, therefore, not considered credible.

2.

Quench Pumps Pump fails to start The quench spray subsystem has two parallel 100 percent capacity pumps. Sufficient capacity is provided by one pump in case of failure of the other pump.

3.

Quench Pump Discharge Valve Valve fails to open Redundant parallel path is provided from second pump. Sufficient capacity is provided by one pump.

4.

Quench Pump Discharge Valve Rupture of valve body Valve body is designed for 150 lb. The castings are made from stainless steel; this material has corrosion-erosion resistance and produces sound castings. The valves are designed to be missile protected. Rupture of valve body is not considered credible.

5.

Quench Pumps Weight loaded check valve in pump discharge line sticks closed Valve is checked during cold shutdown. In addition, a parallel100 percent capacity quench spray subsystem is operable.

BVPS UFSAR UNIT 1 Rev. 19 2 of 4 Table 6.4-3 (CONTD) CONSEQUENCES OF COMPONENT MALFUNCTIONS IN THE CONTAINMENT DEPRESSURIZATION SYSTEM Components Malfunction Comments and Consequences

6.

Quench Piping Pipe rupture Piping is designed for 100°F temperature and 20 psig to 185 psig. These conditions exceed those which could occur during operation. The piping is fabricated of Type 304, or equivalent,(1) ASME Boiler and Pressure Vessel Code, stainless steel; this metal has corrosion-erosion resistance. Piping is designed for ASME Code, Class III or Class II (Section 6.2-2). Pipe rupture is not considered credible. However, in case of pipe rupture for pipe lines from the quench pumps, isolation valves are provided.

7.

Recirculation Spray Pump Pump fails to start Four 50 percent capacity recirculation spray pumps are provided. Only 2 out of 4 must operate.

8.

Recirculation Spray Cooler Tube or shell rupture Four 50 percent capacity recirculation spray coolers are provided. The recirculation spray coolers are designed to the ASME Code, Section III, Class C and Seismic Category I. A special jet force protective shield is installed for each cooler to ensure integrity of the coolers considering possible high energy sprays during a LOCA. Rupture of a cooler is considered unlikely and 150 percent backup exists. The river water discharged from the coolers is monitored for radiation. A high radiation level indicates the tube leakage. The river water lines to the affected cooler can be remote-manually isolated as necessary.

9.

Outside Recirculation Spray Pump Rupture of pump casing The casing is fabricated of Type 304 stainless steel; this metal is very corrosion resistant. The casings are missile protected and set in concrete. Rupture of the pump casing is not considered credible.

BVPS UFSAR UNIT 1 Rev. 24 3 of 4 Table 6.4-3 (CONTD) CONSEQUENCES OF COMPONENT MALFUNCTIONS IN THE CONTAINMENT DEPRESSURIZATION SYSTEM Components Malfunction Comments and Consequences

10.

Recirculation Piping Rupture of piping Piping is fabricated of Type 304 stainless steel and designed to safety ASME Code, Class 2. Piping is also missile protected. Rupture of piping is not considered credible. However, in case of pipe rupture for pipe lines outside the containment to and from recirculation pumps, isolation valves are provided.

11.

Outside Recirculation Spray Pump Discharge Valve Rupture of valve body Valve body is designed for 150 lb. The castings are made from stainless steel; this material has corrosion erosion resistance and produces sound castings. The valves are designed to be missile protected. Rupture of valve body is not considered credible.

12.

Motor Operated Valves (where opening is required) Loss of power to one valve due to failure of electric bus Electric power to valves in redundant line is supplied from separate bus.

13.

Automatic Electric and Control Instrumentation Trains to Actuate Containment Depressurization System Failure of one train Redundant train actuates redundant equipment.

14.

Spray Nozzles Spray nozzles plugged Strainers are provided in the discharge of the quench spray pumps. The containment sump strainer assembly is made up of strainer modules with 1/16 diameter perforations. The perforation size is small enough to prevent any material which could plug the spray nozzles from passing through. Sufficient margin is provided to accommodate plugging of 25 percent of the nozzles.

15.

Sump Screens clogged The clogging of all screens so as to prevent water reaching the pumps is not credible.

BVPS UFSAR UNIT 1 Rev. 27 4 of 4 Table 6.4-3 (CONTD) CONSEQUENCES OF COMPONENT MALFUNCTIONS IN THE CONTAINMENT DEPRESSURIZATION SYSTEM Components Malfunction Comments and Consequences NOTES: (1) The term "equivalent" is described in UFSAR Section 1.8.2, "Equivalent Materials."

BVPS UFSAR UNIT 1 Rev. 19 1 of 1 Table 6.4-4 RECIRCULATION SPRAY SUBSYSTEM LEAKAGE Leakage to No. Uncollected Vent and of Type of Leakage Control and Unit

Leakage, Drain System, Item Units Leakage Rate Used in the Analysis cc per hr cc per hr Recirculation spray pumps 4

No leakage of spray water due to tandem seal arrangement (See text) 0 0 Flanges: Adjusted to zero leakage following any test - assumed 10 drops per minute per flange

a.

Pump 8 240 0

b.

Valves - body to bonnet (larger than 2 inches) 8 230 0 Valves - stem leakoffs 8 Backseated, double packing with leakoff - 1 cc per hr per inch stem diameter 0 8 Miscellaneous small valves 4 Flanged body, packed stems - 1 drop per minute 12 0 Total 482 8

BVPS UFSAR UNIT 1 Rev. 19 1 of 1 Table 6.6-1 SUPPLEMENTARY LEAK COLLECTION AND RELEASE SYSTEM - DESIGN DATA Number of Unit Capacity, Static Pressure,

Motor, Service Units Cfm in W.G.

H.P. Leak Collection Exhaust Fans 2 50,000 15.0 150 Main Filter Bank 2 36,000 3.67

REV 32 OUT SIDE REACTOR CONTA INMENT ~-~-~-~~~-~2_-_,._o~*-o_u_E.. NCH S,P;*::*::_Y_:_H:,::E.:*::oE::*:.:;s:_ __ ~:=::=;:::::::::~::::~=-1 ~*0 ea~ro, ~---* INS IDE REACTOR CONTAINMENT c 1e Pl QUENCH SPRAY SU B SYS TEMS FROM WAT ER CHI L L ERS OR HEAT EllCHANGERS AlL OAM PE II SIZEO ( 0 11 IOO"A. FLOW ' ' I SUPPLEMENTARY LEAK COLLECT ION AND RELEASE SYS TEM FUEL BUIL DING INF'ILTFIATION DISCHARGE TO EMERGEN CY FUEL BUILOING EMERGENCY EXHAUST FANS PURGE FILTER ATMOSPHERE EllHAUST FILTER (NOTE : FUEL BUILDING EMERGENCY EXHAUST SYSTEM IS DEACTIVATED) POST OBA HYD ROGEN CONTROL AND PURGE SYSTEM (NOTE 1) RIVER WATER RECOMBINERS 4 - 18D 0 RECIRCULATION SPRAY HEADERS

====:'.:~~='.::~:;:=======:

CONTA INM(NT PURGE E* t1AUST ~


=,==1='r=------'

~ r--- --4---c-l-l-----'------ 1 --1----1----,," ~ 1 ~ I==-: l=--=----l--;C;'\\ l --4-------c-[_ l I ~ 1-- I j' ~ LOOP IF~OM AC. ULATOR No. J r~oM ~ I f~~)LEG z-r<J I :...-~-- ----7 ACCUMU¥T01" No. 3 ~ -- I 1 3---..,::::J 1 1 ,._~<--+---+-----L--_-_-_-_-_-_-___ _J_i_ L ___ #_ -~---_-___ L_*_~_~~_:_ ~~_,,_.. _'~~ L -- -- ~ F ROM CONTAINMENT AIR RECIRCU L ATION ---;-------------------------1 ~ 1, 11-r-----+-------( ~A~~ .. r~:f's Al/I ~:~~yc;~::;r~o~ 1s:c;~~~~E-< 1 LINE 1 L 1H---r--'---kc-', ,0~;~~':,';,~"":, r RECIRCULATION SPRAY -t__,,.,....,""'..+--,-,-,-' HEAT EXCHANGERS 1~==<--==>J ~ LI l1 TO HY-101A AND 101B 0-100/o H2 CONCENTRATION ANALYZER CONTAINMENT SUMPS PI PING FROM CONTAINMENT SUMPS TO VALVE PIT IS COATED. WRAPPED AND BUR!EO IN TEN FOOT THICK REINFORCEO CONCRETE CONTAINMENT MAT. ~--- -------- -- - --- ------- ---------- NOTE 1 - THE POST DBA HYDROGEN CONTROL AND PURGE SYSTEM (EXCEPT FOR HYDROGEN ANALYZERS) IS NO LONGER REQUIRED TO BE MAINTAINED. REFER TO UFSAR SECTION 6.5.1. M:\\Ul\\USFAR\\FIGURES_6.1_6.3_6.4\\FIGURE 6.1-1.DGN CIB ~------~---C-_'\\-r---<<1-------' SIS NORMAL BORO N INJECTION TANK L nc FROM VOLUME CONTROL TANK SIS TO WATER CHILLERS OR HEAT EllCHANGEFlS VIA REC IRC PUMPS EME RGENC Y CORE COOL ING SYS T EM

  • BLANKED OFF

~-----REi~~i~~i10N-----cl+1 +-I--, PLO=POWER OUT AT MOTOR CONTROL CENTER RR=REACH ROD Al/lTEST CONHECT IC'N OUTS IDE RECIRCULAT ION SPRAY PUMPS SPRAY PUMPS I I I I I Pl i I I i, 11 rrsr I CONNECTION I A PUMPS Fl l ___ --- - ------ -----------7 g~~y~~UES 1-------1 I ~ - --~ ~~ r------- ____ _ J VALVE PITli I I L __________ ___________ ___________________ J FIGURE 6.1-1 ENGINEERED SAFETY FEATURES SYSTEMS BEAVER VALLEY POWER STATION UNIT NO. 1 UPDATED FINAL SAFETY ANALYSIS REPORT

REV. IB FROM RWST 89J 26 38 HYDRO TEST PUMP Sl-P-2 40 <w 8MB 653B TO FLOOR DAMN SYSTEM OUTSIDE CONTAINMENT INSCE CONTAINMENT 42 181-1 FROM << NITROGEN HEADER \\g> W1-2 8S8C 8MC TO FLOOR DRAIN SYSTEM "C" SAFETY INJECTION ACCUMULATOR SI-TK-1C ALL VALVE AND EQUIPMENT IDENTIFICATION NUMBERS ON MS FIGURE ARE PRECEDED BY THE SYSTEM DESIGNATOR "SI* UNLESS OTHERWISE INDICATED. FIGURE 6.3-1 SAFETY INJECTION ACCUMULATORS REFERENCE; STATION DRAWING RM-511 BEAVER VALLEY POWER STATION UNIT NO. I UPOATEO FINAL SAFETY ANALYSIS REPORT

350-300-250-iz Z 20°" 150-100-50-n 1000 2000 a 3000 0W RATE 6PM \\ 4000 l REV. 0 (1/82) \\ 5000 FIGURE 6-3-5 PERFORMANCE

CURVE, LOW HEAD SAFETY INJECTION PUNP BEAVER VALLEY POWER STATION UNIT NO.

1 UPDATED FINAL SAFETY ANALYSIS REPORT

REV. 0 (1/82) ONE VALVE CLOSED INADVERTANTLY PROBABILITY << 6.5X10** A. VALVE LEFT CLOSED AFTER MAINTENANCE PROBABILITY = 7.2XI0"9. MOTOR STARTER AUX. a(c) CONTACTS SHORTED PROBABILITY = 5XI0"8 MANUAL SWITCH CLOSED CONTACTS SHORTED PROBABILITY = 7.5XI0"9 HOT SHORT IN CABLE OR IN MCC PROBABILITY = 2.0XI0"10 JL OPERATOR ERROR AFTER MAINTENANCE PROBABILITY = 9XI0"7 LIGHT INDICATION INEFFECTIVE PROBABILITY = 8XI0"3 J. HOT SHORT IN CABLE RUN BYPASSES SWITCH PROBABILITY

I.OXIO CH "10 HOT SHORT IN MCC BYPASSES SWITCH PROBABILITY = I.OXIO-10 +/- LIMITORQUE FAILED IN OPEN POSITION PROBABILITY - 6XI0"7 OPERATOR DOES NOT OBSERVE INDICATIONS PROBABILITY = 8XI0~3 o AND LOGIC OR LOGIC EVENT OR FAULT ASSUMED BASIC NOTES: I. OPERATOR ERRORS ASSUMED TO BE DETECTED 2. AFTER ONE 8-HOUR SHIFT. MISSION TIME ASSUMED TO BE 0.1 HOUR FIGURE 6.3-7 FAULT TREE FOR INADVERTENT CLOSURE OF ONE NORHALLY OPEN ECCS HOTOR OPERATED VALVE BEAVER VALLEY POWER STATION UNIT NO. 1 UPDATED FINAL SAFETY ANALYSIS REPORT

REV. 32 ..-----___. FILL OUTSIDE INSIDE VOLUME CUNlKOL TANK CH-TK-2 SI:::AL WAIHZ HEAT l::XCHANGER CH-E 1 CONTAINMENT CONTAINMENT REFUELING WATER STORAGE T/1.NK QS-TK-1 30 CH-11 CiC CH-115B CH-115D es5c 855B y .,---,----,----i r:1<1 I CH-147 CH-275A~ CH-7\\ CH-1r;r: iJ FJ -- I - . f)) ~'%mm P-1 B fil -4 - -( -o l ~ CH-P-lC CH-148 CH/1.RGlNG PUMPS rROM RLCIRC CH-23 CH-24 151 SPRf\\Y LLJMLS 0 .,.....;;~'----c::+------1. I-__._-------..------------. 1--i""'.::)1.;;: ~---,.-------+-:) ) 945 I

854A, 1111!

06~'A L"'" _ _,z"'" SJ-P-1A + %3C: ;[) SJ\\F~~JEi~WN 28 /I\\ 1.. I 8G4B 0

i

[>kr:_ 1-----.----+-- 9,15 867FI SI-P-lB FKOM RECIRC SF'RAY PUMPF' FROM RCP SEAL LEAKOFF CH-122 940 -;_'><] 867B CH-160 CH-289 869A 867D BORON lNJECTWN TANK SI-TK-2 -~ I 61, 46 15 7 cg - CH 170 CH 31 83 COLU LI:::G II\\JJECTION C:-+--- 13 {::::;--+--- 14 LOOP LOUP Li LOOP C CONTAINMENT SUMP 8608


~ 69 68 860A K;\\U \\USFAI<\\FlGURE b.1 HRU\\FH 6.-l-8.dgn NUTES:

1. ALL VALVE MD EQUIPMENT IDENTIFICATION NUML[:R:5 ON THIS LIGURE !\\RE PRLCEDED BY THE SYSTEM DESTGNATOR "ST" UNLESS OTHF.RWISE INDICATfD
2. VALVES SHOWN IN SAFETY INJECTION COLD LEG H*.UECi"ION Pi iASL AUGNMENT HE.A.DER EGFNFRATTVf EAT EXCHANGER H-E-3 liOT LEG INJECTION INSIDi:: OJNlAINMEN r OUTSIDE CONTAINMi::NT FIGURE 6.3-8 SAFETY INJECTION SYSTEM INJECTION MODE

REFERENCE:

STATION DRAWINGS RM-407 & 411 SEAVER VALLEY POWER STATIDN UNIT NO. 1 !JPDATE'[) FT!\\JAI SftFETY Al'JALYSIS REPORT

RffUELING WATFR STORAGE TANK QS-TK-1 26 5 862A 862B CH-11 SB 27 CH-115D SI-P-1A LOW HLAD 28 SAFETY INJECTION PUMPS SI-P 18

\\ll l.\\lfSFAR\\HGURE 1 HRll\\Hi 6" 3-!Ldgn VOLUME C:ONTROL TANK CH-TK-2 SEAL WATER HEAT EXf'.HANGFR CH-E-1 OUTSIDE Ii'JSIDE CONT41NM1:N CON AILMEfLT FROM RCP Si:AL LEAKOrf

/I§) 5 REV. 32 ,----------~ FTLL HLADLR CH-310 T~ PRESSURTZER CH-3l 1 AUX SPRAY R.foENt:RAi !Vt: CH-115C~ CH-ll5Ei---<[J) ~- 1275B CH- /J (.H-153 I 154 CH-7.6l1 C 1-122 CH-289 Ir.3 HEAT I Xct Lfl.NC!ER CH-E-3 8508 CH-18 -t><I-w-CH-20 I ~ CH-147 Ci 1'52 CH-P-1A CH-23 ~-~-----< :>t-rl><l I CH-2!:i Y><}- Cl!-159 CH-P-lB CH-24 ..---.,-------'-14¥>!- w-C><J ~!----,,--~I- ~~~w_J - _ I CH-161 --J><I--' CH-P-1C CL-143 CHARGING PUMPS -l><J-s61A 867B 890B 869A 0 836 869B 8{,AD BORON INJECTION 1ANK ST-TK-2 J:jj,) 1 84 I 99v 98 T 10 25 COLD LEG INKCTION 3 85 "*15~' ,__ __ _,,,I ""'!<1 1r HOT LEG INJLCTIOI\\J l--~-~-~-wM_/_i_uC-~4_~~--------------------@Y-2 _1_*_*1=========~~::_1 _ _Lc/~-IO_?l"~HT_Ji\\INt:t_,1E_N_T_s_u_1r,_1P_1 _________ _ . l INSIDE CONTAINMCNT IIUTIIIDL CIINT4.INMENT 8b0A w_ 68.J NOiES:

l. ALL VALVE AND EQUIPMEf"ff IDENTIFICATION NUr1 1BFRS ON "HF FIC:URF Ar? - rFB"'.DFr) FY T E SYSTEM DESIGNATOR "SI" UNLESS OTHERWISE INDICATED
2. VALVES SHOWN IN SAFETY INJECTION COLD LEG

=N-LCT=JN DH. :,E.\\LI 0LNl-:~N. FIGURE 6.3-9 SAFETY INJECTIOf\\l SYSTEM RE:CIR.CULAl lOi\\l rvlQOI:: REI-LRLNCL: S, ATlON DRAWINGS RM-40/ & 411 !1El'WER VA! LEY POWE"R. STATTON UNIT NO. 1 UPLJATl::lJ f-INAL SAfEW ANALYSIS Rl::POIH

I REV. 24 35 30 25 Fee XinQ. 20 15 10 CASE 6L LHSI / ~ '~~ 0 2000 4000 6000 TIME Sec 8000 10000 FIGURE 6.3-10 AVAILABLE NPSH FOR LHSI PUMP. PUMP SUCTION DER-Mm. ESF BEAVER VALLEY POWER STATION UNIT 1 UPDATEO FINAL SAFETY ANALYSIS REPORT 25-MAR-2008 14i41 Mj\\ul\\UFSAR\\g60300l0.dgn PREPARED ON* THE CNSU ? CAEODt STSTEM

r OS-TK-l REFUELING WATER STORAGE TANK FROM FUEL POOL COOLING AND PURIFICATION SYSTEM FROM RESIDUAL HEAT REMOVAL SYSTEM REFUELING WATER RECIRCULATING PUMPS OS-P-1B OUENCH SPRAY PUMPS REV. 27 OUTSiOF. REACTOR CONTAINMENT 2<I 0S-MR-1A REFUELING WATER REFRIGERATION UNIT EVAPORATORS TO FUEL POOL -CK5-COOL ING PURIFICATION SYSTEM OS-E-IA REFUELING WATEH 2B STORAGE TANK COOLERS INS!BE REACTOR CONTAINMENT QUENCH SPRAY HEADERS "Ln If. "In CONTAINMENT 5UMP ALL VALV; ANO EQUIPMENT iDENT IFICATIQN NUMBERS ON THIS CIAGRAM ARE PHECEDED 2Y THE SYSTEM DESIGNATOR 'OS' UNLEG5 OTHERWISE INDICATED. FIGURE 6.4-IA CONTAINMENT DEPRESSURIZATION SYSTEM QUENCH SPRAY SUBSYSTEM

REFERENCE:

5TAT!ON DRAWING RM-SS3 BEAVER VALLEY POWER STATION UNIT NO. 1 UPDATED FINrtL SAFETY ANALYSIS REPORT

RECIRCULATION SPRAY HEADERS REV. 21 -II Ih RS-E-IA r RS-E-1B INSIDE RECIRCULATION SPRAY PUMPS RS-8SK-1 RS-8SK-2 RS-BSK-3 RS-8SK-4 SUMP SUCTION BOX CONTAINMENT SUMP At.L VALVE AND EQUIPMENT fOENTIFlCATfON NUMBER5 ON THIS DIAGRAM ARE PRECEDED BY THE SYSTEM DESIGNATOR '33' UNLESS OTHERWISE INDICATED. \\\\sr RS-E-IC RECIRCULATION SPROT COOLERS -HI REACTOR CONTAINMENT RS-E-1O OUTSIDE REACTOR CONTSINMENF FIGURE 6.4-1B CONTAINMENT DEPRESSURIZATIQN SYSTEM RECIRCULATION SPRAY SUBSYSTEM

REFERENCE:

STATION ORAViNC RM-<<!3 BEAVER VALLEY POWER STATION UNIT HO. 1 UPDATED FINAL SAFETY ANALY5I5 REPORT

REV. 24 CHANNEL BOX SUCTION BOX OVER FIGURE 6.4-2 CONTAINMENT SUMP STRAINER ASSEMBLY BEAVER VALLEY POWER STATION - UNIT 1 UPDATED FINAL SAFETY ANALYSIS REPORT or.\\ul\\UFSW\\g68<<02&dgn prepared the asu

REV. 0 (1/82) FIGURE 6.4-3 TYPICAL-GENERAL STRUCTURAL ft PIPING ARRANGEMENT RECIRCULATION SPRAY ft LOW HEAD SAFETY INJECTION SYSTEMS OUTSIDE MOTE: THIS FIGURE PROVIDES A TYPICAL REPRESENTATION OF THE I??wffA5JJW5°i2lffIj?l?TlATInm unit no l GENERAL STRUCTURAL AND PIPING ARRANGEMENT AND SHALL NOT BE ,_",V IU USED FOR DESIGN OR OPERATIONAL PURPOSES. UPDATED FINAL SAFETY ANALYSIS REPORT

REV. 0 (1/82) RECIRCULATION WATER OUT RECIRCULATION WATER IN .UPPER TUBESHEET SEGMENTED BAFFLES ON SHELL SIOE LOWER TUBESHEET SERVICE WATER OUT FIGURE 6.1-4 RECIRCULATION COOLER (TYPICAL) SHELL AND TUBE DESIGN COUNTERCURRENT FLOW BEAVER VALLEY POWER STATION UNIT NO. I UPDATED FINAL SAFETY ANALYSIS REPORT

REV. 0 (1/82) OSS-1713A 22 1/2* UPWARD VERTICAL DOWNWARD QSS-I/2B40-QSS-1713A AT 221/2° UP FROM HORIZONTAL QSS-I/2B40 VERTICAL DOWNWARD HORIZONTAL RSS-l/2 B6O HORIZONTAL RSS-l/2 B60 RSS-t/2 860 RSS-1713A AT 45>>UPFR0M HORIZONTAL RSS-l/2860 HORIZONTAL RSSH/2B 60 VERTICAL RSS-l/2 B 60 HORIZONTAL RSS-1713A AT 45" UP FROM HORIZONTAL FI6URE 6.4-8 SPRAY PATTERNS IN CONTAINMENT BEAVER VALLEY POWER STATION UNIT NO. 1 UPDATED FINAL SAFETY ANALYSIS REPORT

I REV. 0 (1/82) CONTAINMENT STRUCTURE RECIRCULATION SPRAY HEAOER SPRAY DROP VELOCITY SECTION PLAN AX IS OF SYMMETRY FI6URE 6-4-9 AIR MOTION INDUCED BY RECIRCULATION SPRAYS BEAVER VALLEY POWER STATION UNIT NO. UPDATED FINAL SAFETY ANALYSIS REPORT

REV. 24 60 50 40 30 X 10 9: 20 10 t

CASE 6L-RS ORS l I 60 50 40 30 20 10 2000 4000 6000 TIME Sec 5000 10000

/ 1 CASE 6L-RS IRSJ 2000 4000 6000 TIME Sec 8000 10000 FIGURE 6.4-10 AVAILABLE NPSH FOR RECIRC. SPRAY

PUMP, PUMP SUCTION DER-Mm. ESF BEAVER VALLEY POWER STATION UNIT 1

UPDATED FINAL SAFETY ANALYSIS REPORT 25-MAR-2Q08 12i40 Mi\\ul\\UFSAR\\g6040ai0.dgn PREPARED fllfCl THE CMSU SYSTEM

TO MOUMY BUUMB OOMUT MNS tin elevates must SLGRS VCMT 4*7A W+-4A LEAK COLLECTION EXHAUST FANS REACTOR CONTAINMENT REV. 18 AU VAJ.VC MO EQUPMENT OENTtfCATON WAOERS ON TH8 0U6RMI ME PRECEDED BY TX£ SYSTEM OCSGNATCW -VS1 IM.CSS OTHERWISE NOTED FIGURE 6.6-1 SUPPLEMENTARY LEAK COLLECTION RELEASE SYSTEM REFERENCE* STATON ORAWMO RM-516 KAVtR VMJ.EY POWER STATDH UMT NO. I UPDATED n& SAFETY ANALYSIS REPORT

jria n=E s

'FpsBfiEE
  • F;'i ozo c'e c

o+ 6 o o o o, N(, t T B Ff; si il a

D I

B t 3 t o q .h, 6 u nB: { B UI IT., oE Tst* Io 3 I6 H c, q 6 t .l d' E t-ll?-$Fo-?5-6gl ? H$FF --T Ti l. ? ? isFi I l l

- a l o {

I t E a l t o n l l t o l 6 d I l i i o l I l:J r' I I l { l Dr5 I O rY dr dc, $r r i SFI $ o D I I osd ilil^ 0T3 I o o E G6l r r ^ m J+' i oD n{ N it (r' 3(t'\\, a.) a d$ e 9 E o' N F I r r N r f r EfrE Bilig@ TB$

IEiiEgiHi

,ilii*glil ag'EEiF d E e a A g gH fr

n d

n= e 5 c f As ti il'l __i ir .rt r !,o (l o II oD s! i o oroo 65 Eg oh, a7 o3 I f 6.1. T ID 0 nr ot 6+ gl I P ; { f,F d q f ; n a z { . t c o = fiE I o = e e A i { 6

E O

H O O = r ; 6 c t : "'t ii HE

  • "EF 9 rH*

isFe ea aH f, o n E { < e F ing i P T I oD o tg O tt c q.gE

>fi tioi$H ga a

B1 ifiF H3E ilEHE 1;Eq

qfr fo.

v D esf; s' I E I q = U! o ID{ zo E t a N t ' l!f ! = { E l 7 0 .b l'l ?l o l o i D ] E? 5 tx ? 3T o m D m v Dt-rm -o o-rrl 7 U' -l D{ oz z{ zct Tl

5 2 =

o P { D mct D I 3 D 3

F r C

' t . t

a
o

! P

o
o
z m\\ss)

Il3 3 I& sD I a6ea)

' I' *' I' I' I' I' t' ' I' ' I' i' I' i' I' ' I' i' I LOOP SEAL Y CTOC COUTWMMIUT7 ^ibfV^°t-,^-":tAs-i53 ? 1AS-27S r1/2r-lflS-1058 AS-I. FDR UL MSI COM RDtR TO BVM-4& 7CTCBHIWNATt<<UIPC0NHIMeiCATaMFR>a CONN. NO. ON CONDENSER OWG. 13626-6-160 OR GLANO STEAM CONO. DRAWING 4514025 5-

  • IMWCATE8 FUHNBKEO BY SQIW MFK.
  • IMWCATE8 FUHNBKEO BY SQIW MFK MCV-fKi 6.m*tUPfUE0 ft TURflmE MANUFACTURER.

7. ntHH TO 8VS-480 R>R STBAM TRAP WRORMATION. a. geno. id W&4U rw v Tv>>e simmc* (Mfmmatiom. ADO NIPOL* >> TO ALL V8MTS t MAIMS 10. VALVES HVV-OPERATOR. CONTROLS AND IMT BONNET REPLACEO WITH BOLTEO COVER. OUALITT GROUP CLASSIFICAIIONS ARE

  • INCORPORATED BY REFERENCE*

INTO THE UFSAR.A CHANGE TO DUALITY CROUP CLASSIFICATIONS CONSTITUTES A CHANCE TO THE UFSAR. SAf/r/ ££Mr££> REVISION 38 INCORPORATED dun ea OlM ia-B076-e8l-B04 DUN 10-8404-683-682 DUN 10-0404-684-682 iuifiv cperatins catmr FLOW DIAGRAM AUXILIARY STEAM AIR REMOVAL-SH 1

zo Es Ia3 Iss ll bl o aE N o n ?N rot t nT6 $s

iiti, ia ii

? tt o f o9 6 o n m ,+ T x 6 Q o ; F$-S

  • e{

t+t E s N o 2o2 o I or o o o tlo I l* 6 z o aEnsl s.! q d tt o I i6ilr* HrFssfl ffiF*I 9JEd' - ! l Eeo rr o4m o o o 9 . 6 - t z ! o{ o 0o u { 4 or oc67 oo Ji I --L a o o (I G, < p N ;dH g F

ig 6

o T E T a o (D -T-I I I l(t E' 6 6 o U +

  • o rH i5 I

T ra-Dae N oo oo bEE 6 z o 6', or {to N o6 o I I I t - ^ o r3;r lf,'\\: i u!n oo$ry oo o^ ^ r!e +sBi oz o N o! !o n, r-- I I

D o 6 u { 0 ?I E t D 2

D E o o a, o atE oE I 33 CN 6i oi E9 60 ql Lrtt o g t-o o a ? C3* riifisla PIP eFIE lr , tD+ idr I o o{ m o a{B ct q s 0o ab:c o O !l o o C} { rffin

$- B ;3ll
  1. FF O=g fiH F f*

J ig -\\ a i - Z Dt3 oo! - !'8& cf;9 I F 33 T a t a?(t ait o e !o ttt n ?, 8 E5rys,s

Ei 6S E a

o!!c' o g ou

iil

{ IEt o II I g I s tE E E0 6, o o B 7o o nTI uo t ot ? TI q q B N EH Ei E! aF 68-Tit F + J ra l l l 6 m O .lr 4 j o .sE i 9 to I 6 (t -l _ t _ _ - l t t l l l l t l l l l t l t l t t l l t lt l t l l l t l l l t l I I L____L__----J a,"ffilliilH'

Hi lffi g ;F;i 3EEsiEilE$

Ef;;HiiFEA[i

iiiiiHEEii'H!ii fi o

ai! iir sEH EffI i 6{ I' I

omfr, D

I Dcx TFm o 7I a D3 t o 0 i it n 3 t I IC I rE ffifi i lild E 6 {

  • {

E daeI

E t oif; n-{

9.r m ; ql fr t I o n u 5 q to el d c' q I o N (' o o ?{ { I D N ?l ?l -l Fll !lgl- ]H m D frl t D l-t- tn T o-nt v (n{D{ oz cz{ zo I e6ea)

No. 8700-RM-0022A CHILLED WTR RETURN FROM AND AIR COMPRESSORS FIG 2S-2 (F-10) RM-22C j SUPPLY HEADER FIG 15-2 (A-7) RM-228 TO SUMP VENT AND DRAIN SYSTEM FIG <)-4 (C-I) J l) SUPPLY HEADER 4'-CC-112-l5l-3-' FIG 13-3 (A-2) OVERFLOW NON 0 03 y-r-CC-17-151 NOW O 03 2*-CC-32-151-03 TO i supply heaoer FIG IS-2 <A-6) RM-228 /**-CW-4-I5I 2--CC -322-151-03 REFUELING WATER STORAGE TANK COOLERS REF FIG 13-1 (B-81 RM-513-1 / 2--CW-15-1S1 PRIMARY PLANT COMPONENT COOLING WATER HEAT EXCHANGERS 24--CC-2-I51-03 J. I 172 /-3/4I-CC-53*>>-15l / FROM JSUPPLY HEADER FIG 15-3 (8-2) RM-220 FTP CC-I2B ^B"-CC-66-l5l FIG 15-2 (G-3) RM-2ZB LMS FS /1CC-127-2 INSIOE CRANEI OUTSIDE CRANE 6--CC-83-15K FWJM \\ DEGASIFIER p 3/4--CC-532-8"\\i2 REJ-ICC-I6B r l-l/2"-CC-!44-ISI-03 I6--CC-I91-15I-03 PRIMARY PLANT COMPONENT COOLING WATER PUMPS ^8*-CC-468-13l-03 /-24--CC-266-I51-03 FROM RETURN HEAOER FIG 15-5 (B-8) RM-22D I. ALL VENT. DRAIN. TEST CONNECTIONS. INSTRUMENT ROOTS AND RELIEF VALVES ARE 3/4'UNLESS OTHERWISE NOTED X NUMBER SHOWN AT REACTOR CONTAINMENT LINE IS PIPING PENETRATION NUMBER ON RV-1A.

5. FOR INSTRUMENT CONNECTIONS REFER TO BVM-42.

6. VALVES IN PIPE SIZESi 18" OVER CLASS 121. B-UNDER CLASS 151. 7. REFER TO BVS-462 FOR TEMPORARY STRAINER INFORMATION. 8. ADD NIPPLES TO VENTS A CHAINS. VALVE REFERING TO THIS NOTE WAS A TV (GLOBE). OPERATOR WAS REMOVEO AND A MANUAL OPERATOR PROVIVEO. REFERENCE DRAWINGS! REACTOR CONTAINMENT PENETRATIONS RV-1A FLOW DIAGRAM F1_OW DIAGRAM COMPONENT cVTNG^wXR-St^BlotE CONDENSATE SYSTEM RM-.7A BORON RECOVERY SYSTEM RM-2SA RESIDUAL HEAT REMOVAL SYSTEM* RM-41B-I FUEL TOOL /e;-CC-58-l51-O3 T EXCHANGERS r i 15-2 ID 1-22B CM]--; HEA FIG IS-2 (D-6 RM-22B 10#-CC-2B-15l-D3 , FROM EVAP OVERHEAO 4 CONDENSER S l5"2 5<>>) RM-22B TO REACTOR CONTAINMENT SUMP FIG <>>-l IE-4) RH-34A REACTOR CONTAINMENT SUMP FIG

  • )-!

(E-4) RM-34A OUALITY GROUP CLASSIFICATIONS ARE "INCORPORATED BY REFERENCE' INTO THE UFSAR. A CHANGE TO OUALITY GROUP CLASSIFICATIONS CONSTITUTES A CHANGE TO THE UFSAR. ALL MANUAL VALVE EQUIPMENT IDENTIFICATION NUMBERS ON THIS DIAGRAM ARE PRECEDED BY THE SYSTEM DESIGNATOR MCCfrUNLESS^OTHERWISE 8*-CC-8l-l5l7 EVAP OVERHEAD f '\\ CONDENSER FIG 15-2 (0-41 RM-22B LIQUID WASTE OISPOSAL SYSTEM SAMPLE SYSTEM VENT DRAIN SYSTEM REACTOR COOLANT SYSTEM RM37A CHARGING t VOLUME CONTROL SYS. RM-3-ffl RM-38A3 RM-32A RM-34AJ.C RM-37A.B LOCAL SAMPLE TO NEAREST FLOOR ORAIN NEUTRON SHIELD TANK COOLING WATER SUB-SYSTEM PLUMBING SERVICE BUILDING - R8-18A.B.CAE.F.G LOGIC DIAGRAMS LSK-I2-7.8.H.l2,IXM.I8 REVISION 31 INCORPORATED DUN 88-0530-001-802 ECP 08-0530 BEAVER VALLEY POWER STATION UNIT NO 1 NUCLEAR CPBUTINB COHPAHT

g 10 11 12 No. 87OO-RM-22B' TO LW-P-2A <>>M-30A <= § VG5-6OB(TYPI 3-CC-IS-I5I iVt?Tn4 1 I 3. r-fUEL BUUXNlG / , iifcc-445-ISi Lj ^4 AS-BUILT quality GHDuPCLAssiFCATiONS are-Incorporated BY REFERENCE'OiTO THE UFSAR.A CHANGE TO QUALITY GROUPCLASSIFC&T1QNSC0HSTITUTES A^HAMGE NUCltftR SfcftH REUTtO PORTIONS OF.THIS DRYING s&w DvyG-. nq

I I-1" I' I' < I I' I I" I' I

  • I' I lTl'I'lY1 v

A) ICC-iteVl FCy -715>I A-S Tv _ / ,4-J( 1 3/4--CC-56MSl-O2^J ICC-WPl l OUALIT>> CROUP CLASSIFICATIONS ARE INCORPORATED B>> REFERENCE INTO THE UFSAR. A CHANGE TO OUALITY CROUP CLASSIFICATIONS CONSTITUTES A CHANGE TO THE UFSAB. INCORPORATED ECB-B4-03IB 1OCN l-RH-BB22C-EB4-B3ia-ei IOCN 1-RM-8822C-EB4 831B-0Z DIAGRAM REORAWN ECR-04-83IB CHANGED SAFETV CLASS OF COMPONENTS SEE IDCNS FOR LISTING OF COMPONENTS FLOW DIAGRAM COMPONENT COOLING WATER SH 3

No. 8700-RM-22D !3d \\ W-CC-S27-I5I-O3 -'i U 24--CC-I13-I51-03 S3 IB--CC-528-I5I-03 (3B6>^WT \\ /-TV~ L)-wr \\ ^ Tv ~~\\^**\\ i ^-2"-cc-297-iai-TS-, \\^CC-IB78y CLI58I CLI5I l ^^ V-2I-CC-2<<3-l59l-03 r >-lfi

2. ALL MANUAL VALVE EOUIPMENT IDENTIFICATION NUMBERS ON THIS DIAGRAM ARE PRECEDED BY THE SYSTEM OESIGNATIOM TCR-UNLESS OTHERWISE II
3. ALL VENTS. DRAINS. TEST CONNECTIONS. INSTRUMENT LIEF VALVES ARE V UNLESS REVISION 17 OF THIS DRAWING WAS REDRAWN AND PARTIALLY SUPERSEDES DRAWING 8700-RM-22D. REVISION 16 BEAVER VALLEV POWER STATION UNIT NO.

1 FLOW DIAGRAM COMPONENT COOLING WATER 2eei 15)55 g:\\ul\\mB22B<<<.d2l

No. 8700-RM-22E 10 CONTAINMENT PENETRATION INNER COOLING UNITS CC-I2I 3/4*-CC-2<)2-15l-03 D -ti T^ P-CC-3S-I5I-I TO 87B8-RM-22C NOTES:

1. FOR GENERAL NOTES AND REFERENCE OWCS. SEE 8700-RM-22A.
2. ALL MANUAL VALVE EQUIPMENT IDENTIFICATION NUMBERS ON THIS DIAGRAM ARE PRECEOEO BT THE SYSTEM DESIGNATOR TCR* UNLESS OTHERWISE INDICATEO.

CL 151 ITVPI ITYP> CL N<>> ITTPI 1-3/4 CL ISI ITYP) -CC-3B5-I51-O3 REVISION 1 OF THIS DRAWING WAS REORAWN FROM PARTIALLY SUPERSEDES DRAWING 8700-RM-22D. REVISION 16 INCORPORA IATED ECR 84-0310 IDCN-I-RM-B022E-EB4-031B-0I FFNOC NUCUAR tffRATINE COPAHf BEAVER VftLLEV POWER STATION UNIT 1 FLOW DIAGRAM COMPONENT COOLING WATER lAAl°*"18700-RM-1 07-S£P-2)M5 13:44

No.8700-RM-002^A 1 2 /-**-VC-SB-I52-03 03lN0N 0/-r-VG-44-152 l-l/2'-LW-235-302 FIG 17-3(0-18) RM-38C (E-iei l-l/2'-LW-236-382 FIG 17-3IC-1BI co-iei -FIG 17-1 (0-41 SRM-30A (0-4 REFiFIG IS-2(B-l RM-22B 1BR-E-8A OEGASIFIER VENT CHILLER FIG iq-im-BlVJBR-'e5A RM-43A PAHL r-GU-ll-134 IBR-1B3AI 2'-BR-2l8-l52 > PRCS IBR-103 IBR-103A ^^_ ^238 3-REF: FIG 15-2(8-2) RM-22B /FIG S-2<<A-<>> 3--BR-46-I52 4<-VG-<l-152 LO 4--VG-3-I52-03 H) FIG 7-3IA-IB) RH-3SA 2-152-03 3'-BR-35-l52 2--BR-68-152 IGW-23 3/4--VG-42-I52-03 I/2--VG-41-N8-03 FIC 7-3(A-5) 3/4'-H-13-N8 l/2'-H-15-N8 I y 2*-BR-34-l32 / REFi FIG 27-2(8-1) RM-1E8 /2--BR-235-N8 3"-BR-35-l52 DEGOSIFIER CONTROLLER RM-34C FIG <i-4U)-2) /2'-DA-86-N8 FIG 17-1 \\ (E-5) \\ -l/2'-LR-23B-l52> /3"-BR-2-152 3/4-CC-446-1 Itij r-3/r4>cC-44 RM-22B FIC 7-KC-7 3'-BR-2G-152 3--BR-75-I52-' NOTE 2*T" TRB IIBR-1B0 IBR-IB0A4 -1/2* A/S -^TO LRC-IBR-18IA (B-7) IBR-P-7A DEGAS IF IER CIRC PUMP REF FIG 15-2(C-2) RM-22B IBR-I-IB

REF, FIG 18-3 (C-71 RM-33A CESIUM REMOVAL ION EXCHANGERS IBR-I-IA REFi FIG 18-3(C-6)

RM-33A DEGAS1FIER TRIM COOLER IBR-E-1BA 2--BR-9-152 03lNON 0/-T-VG-45-152 REF. RM-22B IG 15-2(8-2) CLI52 CLN8 3/8'-SS-l4-N8 REFi FIG I5-2IE-U RM-22B IBR-E-8B OEGASIFIER VENT CHILLER FIG iq-im-7>>VIBR-lB5B RM-43A 3'-GW-3l-154 2*-B<<-21l-l52 > REFi FIG 1S-2IE-2) RM-22B IBR-FL-1B COOLANT RECOVERY FILTER FROM COOL FILTER JCH-FL-2 FIG 7-KG-8) RM-3SA 1-1/2--BR-I4-152 REFi FIG 27-SB-2) RM-168 IBR-E-G8 OEGASIFIER STEAM HEATER 2--DG-41-152 FIG S-210-10) r-BR-213-152 FIG 8-2(F-8)A I. REFER TO BVM-42 FOR ALL INSTRUMENT CONNECTIONS. OEGASIFIER CONTROLLER MEJ-1W-I8 OEGASIFIER RECOVERY EXCHANGER 2. REFER TO BVS-462 FOR TEMPORARY STRAINER INFORMATION. 3. OISSIMILAR METAL FLANGE JOINT TO HAVE INSULATEO GASKET, WASHER AND BOLT SLEEVES.. A/S TO LRC-IBR-IB1B(F-7)V

RM-22B REF S->>F-2) RM-226 OEGASIFIER TRIM COOLER 0UAL1TY CROUP CLASSIFICATIONS ARE 'INCORPORATED BY REFERENCE' INTO THE UFSAR. A CHANGE TO OUALITY GROUP CLASSIFICATIONS CONSTITUTES A CHAM* TO THE UFSAR. ALL MANUAL VALVE. EOUIPMENT IDENTIFICATION NUMBERS ON THIS OIAGRAM ARE PRECEDED BV THE SYSTEM DESIGNATOR '1BR* UNLESS OTHERWISE INDICATED. INCORPORATED OUN I1-B049-001-047 ECP 11-B84S BEAVER VALLEY POWER STATION UNIT NO 1 HXllAR BOUTINS COHPNf/ FLOW OIAGRAM BORON RECOVERY SYSTEM-SH 1

NO.B700-RM-29B itrrrtefr' rr-i t TNUtMOSIATIC'nuP BR-E-7A (_ L£l_ I&M 1 liSVMl

DUI.SIEM) t MR ROW* COMPOCNT CflGLMC WTER BtKH RECWERT SttltH IIOIUD WdSIE OISPOSM. flOK 0VCHAM - VH\\C SrSICN fUM BVam <<ENI 1 ORMK STSIEM5 RH-IE8 SH. I RM-22A SKI. li 4 RH-2SOX SKI RH-3M 0M-32A3 SK 2 3 RM-34B t C UAOUM - chmsh. i va.wnRa sts. sk 14 2 FUM OMCHM - GCSECUS mSTE OlSfOS* BRP-6& IVAPORATOR CUtCUUMION PUMP ISK-JJ-ie LSK-U-II LSK-33-12 LSK-33-13 2. RR REMtESENTS REACH 3. Pf>> R£PRESKTS PDRTABLE REACH ROD. 4. <\\/\\j REPRESENTS LINES THAI ARE HEAT TflOCEO. DO* t<<sRBornM& cine. satciMisvnKM DUALITY CROUP CLASSIFICATIONS ARE NCORPORATEO BY REFERENCE' INTO THE UFSAfl. A CHANCE TO DUALITY CROUP CLASSIFICATIONS CONSTITUTES A CHANGE TO THE UFSAR FLOW DIAGRAM BORON RECOVERY SYSTEM SH2 AUlfiW omATINS (OfAST 6CAVCR VALLEY POWER STATION UNIT NO I" DWO. WO. 117O0-RM-21B 21 04-OCT-JBO4 07:32

No. 8700-RM-32A r'TiTiT'TiriTiTiTiT'T 0 2 3 4 5 I

  • i' I
  • t
  • I' ITITITIT-T-Ti1

? a_ CMQINIIKf 0 ***

  • MMttUAKP >>Y*iTtM 10 D

FROM ISI-TK-lgJ 3/8*"SS"! I. LOCAL SAMPLE POINIS ARE SHOWN ON 1HE AFPLlCASLE DRAWING AND NOT ON THIS ORAUINC. 3. APPROX 19 FEET l/ffOO X 8.033* WALL SS TUSINO WOUND IN r DIAMETER COIL. 5. PROVIOE FOR CAPPED LINE SIZE TEST CONNECTION ON ALL CONTAINMENT PENETRATIONS. 6. APPROX 5e'-a-0F 1/4*00 CL N<t TUBING. B. SUPPLIED 8V EQUIP HFC. 1. ADD NIPPLE TO VENTS AND ORAINS. anal 4 owramc MKCJM M £o<<nlMMHf*n)l COHTAINHXMT I f*r~ST "^-STEAM GENERATCR SAMPLE PANEL PKL >>-1 II. SEE CR 11-1888 SINCE UPSTREAM RELIEF VALVES ARE CAPPED. RAD MONITOR RM-ISS-IB0 IS PROTECTED WITM^ THROTTLEO INLET AND SEALED OPEN OUTLET. I?. 0UAL1TY GROUP CLASSIFICATIONS ARE 'INCORPORATED BY REFERENCE* INTO THE UFSAR. A CHANGE TO QUALITY GROUP CLASSIFICATIONS CONSTITUTES RM-I7A RM-?2B RH-2<1A C RM-3BA B RM-348 t> C RH-37A B RESIDUAL HEAT REMOVAL SYSTEM RM-4I0-I CHARGING AND VOLUME CONTROL SYSTEM RM-31A B SAFETY INJECTION SYSTEM RM-4II-? SLOWDOWN SYSTEM RM-58A COMPONENT COOLING WATER BORON RECOVERY SYSTEM LIOUIO WASTE DISPOSAL SYSTEM

VENT AND DRAIN SYSIEM REACTOR COOLANT SYSTEM D! I 4 INCORPORATED ECP-85-027<) lDCN-l-RH-ee32A-EB5-027S-81 FENOC IU1CAR OPERATING CUPAHT 4-II-B6 BEAVER VALLEY POWER STATION UNIT 1 FLOW DIAGRAM SAMPLE SYSTEM SH 1 SL AA 8700-RM-32A 33 29-aPR-2886 I6i51

NO.8700-RM-0032B I

i

j

  • i

I

I I j

1 10 3/4--WO-21-I32 FROM COMPONENT COOLING WATER FIG 15-218-8) RH-22B FROM VOLUME CONTROL

TANK, 1CH-TK-2 b

FIC 7-3 (B-IB) RH-3<M 3/8'-SS-ll-N8-O2 FROM ISS-TK-IC FIC MA-1 (C-6> RM-32A l/4'-SS-R4-l>> 3/B--SS-I23-N8-02 VOLUME CONTROL TANX LIQUID kl/4'-SS-l4B-N8 REACTOR COOLANT DEHINERALIZER OUTLET HEADER -3/8*-SS-l<>>6-N8 REACTOR COOLANT DEMINERALIZER INLET HEADER y-3/8*-SS->>30-NB I N-3/4--SS-15-I STRIPPED LIQUID FROM OECASIFIER OUTLET FIG 8-21C-2I RM-Z9A -S/B'-SS-W-NB STRIPPED LIQUID FROM OECASIFIER OUTLET FIC B-2(a-2> RM-2SA ^-3/B'-SS-l45-N8 irC>>D 15? REACTOR COOLANT FROM OEBORATING OEHWERALIZER ICH-l-38 FIC 7-2CC-5) RH-34B REACTOR COOLANT from OEeofwrtNO 0EMINERAL1ZER ICH-I-3O FIG 7-2(0-61 RM3<<>> rVe*-SS-IS3-N8 AEACTOR COOLANT FROM CATION BED OEMINERALIZER FIC 7-2IF-2I RM-1% REACTOR COOLANT FROM M1XE0 BED OEMINERALIZER 1CH-I-IB FIG 7 2IC2I RM-3S8 r 3/8'-SS-130-N8 j-3/8*-SS-IS2-N8 CL NB CL 152 1 KED KID C3D? I/2--SS-I7B-N8 REACIOR COOLANI FROM MIXEO BEO DEMINERALIZER ICH-I-IA FIC 7-2IC-3) RM-3<>> CUNIA1NMENT SUMP REF RM-SI3-2 1(r3/81-SS-13l-N8 KilD STRIPPED REACTOR COOLANT FROM COOLANT RECOVERtr TANXS FIG 8-2(0-18) RM-2SA r3/8--SS-3J-Na y-W-SS-I'M-NB IrCUD V4--SS-117-IS2-O2 \\. VOLUME CONTROL TA FIG 7-3(D-8) RM-34A \\ PRIMARY DRAIN , TRANS TANK NO 2 FIG <)-2<O-4l -3/8>-SS-l37-N8 FROM REACTOR COOLANT SVSTEH HOT AND COLO LEG SAMPLE FIC I4A-IIA-B) RM-32A NOTE; _/<< FIC l4A-l(G-<nf sump pit FIC 1-4IC-S) RM-34C PORTIONS OF THIS DIAGRAM ARE NUCLEAR SftFElr RELATED FOR NOTES AND REFERENCE ORAWINCS SEE RM-32A. DUALITY CROUP CLASSIFICATIONS ARE INCORPORATED BY REFERENCE' INTO THE UFSAR. A CHANGE TO DUALITY CROUP CLASSIFICATIONS CONSTITUTES A CHANGE TO THE UFSAR. ALL MANUAL VALVE EQUIPMENT IDENTIFICATION NUMBERS ON THIS DIAGRAM ARE PRECEDED BY THE SYSTEM OESIGNATOfl "ISS" UNLESS OTHERWISE INOICATEO. REVISION 17 INCORPORATED DUN 10-0422-801-082 ECP 0S-BW FFNOC HUCllAK OPBUTINB COCA/fT BEAVER VALLEY POWER STATION UNIT NO 1 FLOW DIAGRAM SAMPLE SYSTEM SH2 RM-0032B

NO.8700-RM-0034A NClESi 9 10 I. NUMBER SHOW* <<r CONlflMKENT LINE IS PIPING PENETRATION ON IRV-IA. CL 682 CL N9 l/2--0G-2?i-682 CL 682 CL N9 I/2--0G-278-6B2 VSLO IRH-2 b I/2--OC-2S5-I502 VSLO M0Y-IRC-53Gb FIG 6-2 <fl-9> RM-37B I/2--DG-287-I5B2 VSLO M0V-IRC-592b FIG 6-1 10-31 RM-37A I/2--DG-295-15B2 VSLO MOV-IRC-598 b riO 6-1 IB-3>> RM-37A

2. REFER TO BVH-42 FOR ALL INSTRUTEN*

CONNECTIONS.

3. LOCATE A

HINIMUM OF 2 FEET BELOW NUMBER 3 REACTOR COOLeNf FUMP SEAL AND A MINIMUM OF 8 FEET ABOVE IOG-TK-1. 15021 CL N9 I/2MJ0-2B6-I582-V 1/2--0G-8I-N9 MOV-IRC-537 b CL 15B2la N9 I/2--00-84-NS CL 602 CL N9 I/2--0C-276-682-V lw,..oc.,03.N, l/2'-GG-297-l502 VSLO M0V-IRC-5SI h FIG 6-1 Ifl-BI RH-17A

4. REFER 7Q 8VS-462 FOR lEMPORAIir STRAINER INFORMATION.
5. TEST CONNECTION FLPNJE WITH 1/2 INCH SMAGELOCK COKN£CTiQN.
6. VSLO LINES ARE NON-0.

VSLO IRH-8 b FIG 10-1 (G-Sl M0V-lRC-5<<fc FIG 6-1 (0-81 RM-37A CL 1582 ICL NS 1/2--OG-293-1582 -i VSLO V Cl I 1/2--DG-288-I5B2-. VSLO \\ CL 1582) a H"> -v i/r-oc-iu-N<>> l/2<-CG-296-l582 VSLO MOV-IRC-565i FIG 6-1 <B-9> RM-37A REFERENCE DROUINCSi COMPONENT COOLING WATER SH SAMPLE SYSTEM VENT I DRAIN SYS1EM REACTOR COOLANT SYSTEM BORCN RECOVERY SYSTEM IIOUIO WASTE DISPOSAL SrSTEH RESiDUAL HEAT REVOoAL SYSTEM SAFE1Y INJECTION SYSTEM CHARGING AND VOLUME CONTROL SYS SH STEAM GENERATOR BLOWDOWN MOV-IRC-986 fa FIG 6-1 ID-SI RM-37A RM-22A.8. & C RH-32A RM-3<<A.e. & C RM-.1/A K B RM-2SA, B. C.& 0 B RH-41B-I RM-4II-I 2 RM-j'W B RM-5BA CL 602 ICL US l/?-0G-278-682 VSLO 1RH-IB b !G IB-I lE-51 I/2--OG-274-682 1/2*-00-283-1502 VSLO PCV-IRC-45W b l"-DG-U6-i52 l/2*-0G-H5-S<>> .^2^00-268-1582-MOV-IRH-708 b FIG IB-1 (G-l) I/2--OG-282-I582 VSLO PCV-IRC-455A b SCHEDULE OF PENETRATIONS RV-I CL 15821 CL HS l/2--0G-2<<8-l582-v I VSLO \\ I cl 1502 la l/2*-0G-288-l5e?-. VSLO V CL I5B2 CL NO I/2--0G-26S-15B2-. VSLO V I M0V-IRH-7BI b FIG IB-I (G-2) GASEOUS WASTE DISPOSAL SYSTEM PLUMBING. ROOF DRAINS FIRE PROTECTION SPENT FUEL POOL SYSTEM SYMBOLSi VSLO VALVE STEM LEAKOFF AC AOMINISIRATIVELT CONTROLLED IS TEMPORARY SIRAiNcR DESIGNATES SUPPLIEO WITH EQUIPMENT LO - LOCKED OPEN FROM LOOP I CL I5BZ NON 0 "°"'" CL N9 M0V-lRH-72<<Ab FIG 18-1 (C-I8J MCV-ICH-J37 b FIG 7-4 (A-S> RM-3SA TO PRESSURI2ER RELIEF TANK l FIG 6-2 IB-6) RM-378 OIL COLLECTION FROM IRC-P-IA OIL C0LLEC1I0N FROM IRC-P-IB OIL COLLECTION FROM IRC-P-IC AF-1RC-5A T^- 31 1 f (MFH-1RC-5A AF-IRC-58 f^_ y I^ /* TJ fMFM-1RC-SB JT 1 V-AF-IRC-5C f^- 31 1 I IMFH-IRC-5C FROM LOOP 2 DRAIN FIC 6-1 IC-4I RM-37A FROM LOOP 3 DRAIN FIG 6-1 lF-4> RM-37A LEAKOFF FROM REACTOR COOLANI PUMPS FIG 6-3 IA-SI RH-37B FROM ICH-E-4 FIG 7-4 (B-<M FROH REACTOR COOLANT PUMP SEAL VENT POT IRC-K-3A FIG 6-3 16-11 RM-37B FROM ISI-TK-I8 M0V-ISI-8S2 FIG 11-2 (0-11 FROM REACTOR VESSEL FLANGE LEAK BE TEC I ION LINE FIG G-l (G-ll RM-37A FROM 3/41-DG-55-l5B2-Oi^ MOV-IRC -557A b FROM REACtO COOLANT PUMP SEAL VENT POT IRC-TK-3C FIG 6-3 (G-ll RM-37B 3/4--0G-46-I582-OI FROM MOV-IRC-557C lf + 1 FIG 6-1 (F-Sl J FROM REACTOR COOLANT PUMP SEAL VENT POT FROM IRC-TK-38 lRC-Tr-2 FIG 6-3 (G-l) FIG 6-2 (0-51 RM-37R HM-37B r-DG-68-lb2 ^D2'-Oi;-240-liJ FROM M0V-IRC-557B t, FIG 6-1 10-6 RH-37A FROM M0V-ISI-652C ISI-TK-IC FIG !l-2

F-1I CL I502ICL 152 01 KCN 0

FRCM PRESS RELIEF IK NITROGEN SUPPLY LINE Fir. fi-2 ir-4i HM-37II FROM M0V-IRC-54S ON IPC-1K-2 PHESS RELiEF TK<< FIG G2

3-3l hm-j;b

'.OS-TK-2 <f-2 18-91 RM-348 FROM RV-!SI-8£B% FIG l<-2 IA-1I FR3M RV-ISI-0E83 FIG 11-2 (C-H FROM 2--OA-I57-IS4 RV-1S1-858C FIG 11-2 -.F-ll INSIDE I OUtSitJC CONTftlKHENI I CONTAINMENT FROM NCUTRON - SHIELD TANK CLNG WATER SUB SYSTEM FROM 2--0A-I58-I94 TELL TALE DRAINS FIG 28-1 IC-18) d FIG IS-I (E-l) RM-22A IDA-IIOB\\ LSHH TDCMB7ST 1DG-I07A3 PRIMARY DRAINS TRANSFER TANK 10C-TK-I I I I*- 3--OG-237-I52 IN CORE INSTRUMENTATION ROOM SUMP PUMP REACTOR CONTAINMENT SUMP PUMPS i _{lJ- -f CIA / -g)-* IDG-1888 /"**DO-I23-I52 TO COHTAINMEtIT I CONTAINMENT PORTIONS OF THIS DIAGRAM ARE NUCLEAR SAFETY RELATED DUALITY CROUP CLASSIFICATIONS ARE 'INCORPORATED BY REFERENCE" INTO THE UFSAR A CHANGE TO OIJAt.ll" G30UP CLASSIFICATIONS CONSTITUTES CHAM3E TO THE UrSAR.' ALL M9NUAL VALVE EQUIPMENT IDENTIFICATION NUMBERS ON THIS DIAGRAM ARE PRECEOEO BY THF. SYSTEM DESIGNATOR MDV UNLESS OTHERWISE INOICAIEO. PRIMARY OHAINS TRANSFER IANK PUMPS 10 SUMP I0A-P-4A 4e VIA ORASN TRENCH REVISION 38 INCORPORATED ECP 85-8423 ECP 89-8197 IGCN-I -RM-0a34A-E8S-8423-8l FFNOC 1 m 6'73?/ll ~l <<~^. BEftVEH VflLLEV POWER STATION UNIT NO I Mttf/W OPERATING COPUTt FLOW DIAGRAM VENT DRAIN SYSTEM SH I

No. 8700-RM-0034B i

  • I' I l' I' I' I' I' I' I' ' I' ' I' '

I I' I' i I' I I' I '0- I I > I I I I I' ' I' *' I' ' I' I'T 1 3 5 \\L 7 B 9 10 11 12 i r c i

10 FROM RV-1CH-2S7 VOL CONTROL TANK FIG 7-3IB-S) RM-3<<(A -3/8"-VC-35-N8-03 TO OEGASIFIEH I8R-EV-2A FID 8-1IA-SI RM-2SA TO DECASIFIER IBR-EV-2B FIG 8-KE-S) RM-2SA FROM PRIMARY SAMPLES VENT HEADER FIG I4A-2 IE-IB> RM-32B THIS PIPING. TANK. VALVES. TRAPS ECT ARE WHOLELV LOCATED AT THE EMERGENCY

RESPONSE

FACILITY STRUCTURE AND GROUNDS. BEAVER VALLEY POWER STATION. LEVEL INDICATOR SET POINTS ARE HIGH 75 PERCENT LOW 25 PERCENT. ALARM LOCATIONS ARE SECURITY IRM 126) AND SERVICE OOCK IRM 1121. IRAP PRIMERS CONTAMINATED WASTE STORAGE TANK 2580 GAL. CAPACITY 10G-TK-3 UNDERGROUND CONCRETE PIT OUTSIDE ERF PUMP PIT TIG <)-<<IA-1) RM-34C -I/2--DG-2-IS2 FROM VOLUME CONIROL TANK ICH-TK-2 FIO 7-IIG-Sl R3<M PRIMARY SAMPLES DRAIN HEADER FIG l4A-2(F-1l RM-32B VSLO PCV-ICH-M5 FIG 7-110-Id) RM-3SA I1 DG-8-152 I-I/2--OG-2-I52-03 F 1/2--DC-18-N8-03 03 \\ l/2I-0C-5-M8-03 VSLO FCV-1CH-162 FIG 7-IIG-3) RM-3SA 3/4--DC-I5-I52 -1/2--GW-I53-N8 FROM OEGASIFIER H 1BR-E-8AL>> 8 FIG 8-IIE-I8) RM-2SA FROM KNOCK-OUT H POT DRAINS FIG I1-2IF-II RM-43B FROM PRIMARY DRAINS h) TRANSFER TANK IOG-TK-1 FIG t-IIF-101 RM-34A I/2--DG-I7-N8-03 VSLO FCV-ICH-122 FIG 7-I1E-I1 VSLO HCV-ICH-186 FIG 7-41BI1 RM-3<IA FROM 0i NITROGEN SUPPLY FIG IS-2IC-2I RM-4IA M GASEOUS WASTE DISPOSAL SYStEM FIG 19-KF-l) P" RM-43A FROM PRIMARY GRADE DEARATOR FIG B-710-21 RM-2SE FROM ISW-TK-I ( FIG ie-l(G-ll RM-33A .4--PG-l72-l52<<-l32lCLlS4 w4\\\\ 2--VA-6I-I54-T-VA 154 -v VA-73-1 VA-E6-I LI52 lCL1S4 -VA-34-IS4 /-2--VA-48-I54 3/4--VA-6B-I54 FROM IBR-TK-7 FIG 8-4(A-SI RM-2<>>C I/2--VA-7I-I54 FROM EAST WASTE AREA SUMP PUMPS ISW-P-2A 28 FIG <)-4lF-6> RM-34C FROM COOLANT RECOVERY TANK I8R-TK-4A ft 48 FIG B-2IA-8) RM-2SA r>>& jcc-tk-i FIG IS-1IA-I0I RM-22A SOUTH AUX. BUILDING SUMP PUMPS IDA-P-3C 30 FIG S-4IE-4) RM-34C Nl/2--VA-27-N8 .-VA-64-.54 J 1'2-VA-32N 1-I/2--VA-22-I34 FROM FROM EVAPORATOR EVAPORATOR DISTILLATE ACCUM DISTILLATE ACCUM 1BR-TK-IA EVAP. OVERHEAD CONDENSER IBR-E-7A FIG 8-3IA-9I RM-2<W IBR-TK-IB EVAP OVERHEAD CONDENSER IBR-E-7B FIG 8-3IE-8) HM-2S8 FROM SOUTH VEST AUX BUILDING SUMP PUMPS 1DA-P-8A i BB FIG <)-4fA-<)> RM-34C EVAPORATOR TEST TANK ILW-TK-5A I SB FIG I7-2IA-BI RM-388 FROM CHARGING PUMPS SUMPS FIG S-41B-5I RM-3CC CLI54 CLIS3W 2--CH-22B-I53W r3/4'-VA-l<)-l 1/2' FROM BORIC ACIO TANKS ICH-TK-1A t IB FIG 7-3ID-4I RH-3S8 -VA-C3-IS4 FROM NORTH >><<-t>J 134 e BlL0I FROM EVAPORATOR BOTTOMS HOLD TANKS VENT CONDENSER IBR-E-14 FIG 8-4ID-4I RM-2SC k EVAPORATOR DISTILLATE ACCUMULATOR ILW-TK-4 EVAPORATOR OVERHEAD CONDENSER ILW-E-2 FIG 17-2(0-51 RM-3BB T Jb LOW HIGH LEVEL WASTE ORAIN TANK U.W-TK-2A 1 2S FIG 17-KB-61 RM-38A

  • 4 SUMP PUMPS IDA-P-3A 38 FIG S-4(C-3t RM-34C LEVEL WASTE DRAIN tANK ILW-TK-3A 3B FIG I7-KA-II RM-38A GENERAL NOTES AND REFERENCE DRAWING RM-34A REFER TO BVS-462.F0R TEMPORARY STRAINER INFORMATION.

DUALITY CROUP CLASSIFICATIONS ARE1 INCORPORATED BY REFERENCE1 ALL MANUAL VALVE EQUIPMENT IDENTIFICATION INTO THE UFSA* A CHANCE TO OUALITY GROUP_CLASSIFICATI0NS NiSbERSONTHIS DIAGRAMIARE PRECEDEO^BYThe SYSTEM DESIGNATOR MOV UNLESS OTHERWISE GE O OULI GROUP CLAS CONSTITUTES A CHANGE TO THE UFSAR. PORTIONS OF THIS DIAGRAM ARE NUCLEAR SAFETY RELATED INCORPORATED ECP-BS-0315 1DCN l-RM-ee34B-E05-03IS-ei FFNOC HJCLEAR (POUTING CO/PANT B-2B-B7 BEAVER VALLEY POWER STATION UNIT NO I FLOW DIAGRAM VENT DRAIN SYSTEMS SH 2 P r lAAl'B^B8-RM-003'1B 11*5

No.8700-RM-0037A \\\\-\\- 1 10 nOTRQ L 29* INSIDE DIAMETER t It* MSBlE DIAMETER 4. SLOPE (TONS DOWNWARD TOWARD SPRAV VALVES TO PROVIDE WATER SEAL BETWEEN PBESSURHER AND SPRAV VALVES. 5. CLOBE VALVES NORMALLY INSTALLED WITH FLOW UNDER SEAT. EXCEPTION IS SS4A. 8.4 C 6. VENT HOLE PROVIDED. 7. SPRAV LINE SCOOP. 6. 1/2* SWACEUX TEST CONNECTION FOR DISC PRESSURIZAnON SYSTEM. 9. VSWASEUX TEST CCtMCTION FOR TEMPORARY LEVEL MDICATMH 10. ACCESS OR REACH ROD REQUIRED FOR MANUAL ADJUSTMENT DURING

NORMAL PLANT OPEflAn 1L ACCESS FOR INSPECTION OF REACTOB COOLANT PIPE TO REACTOR VESSEL NOZZLE WELDS TO I ISOLATION FLANH MAV/MAVNOTHAVi 11. PLACE CETECTDB5 AT BOTTOM Of TOE. 14. V HALF COUUNE WITH SCOOP. UTILIZIN6 A iKLt ORIFICE. 19. ajOKUNESTORtOVIDEWATERSEALFORRELIEFVALVES. It. 17. <Ltr HOLE THROUGH VALVE OUS. 18. LOCATE BELOW ELEVATION OF REACTOR VESSEL FLAN6E, 19. LOCAL COUCCTIONPOINT FOR DETERMINING LEAKACE RATE. M. LCCATECONNECnONtf'BELOWHORIZONTALCENTERLINE 21. THE BOTTOM TWO HOT LE6RTDTHERMOWELLS OtO*S 240*) ARE LOCATED IN THE SAMf CROSSECTIONAL PLANE. THE TOP HOT LE6 RTO WERMOWEU (OlTlS LOCATED 64'TOWARb THE REACTOR FROM THAT CROSSEcftONAL PLANE It LT0&4BIC 4 LT-RC-4UC PROVIDE RCS LEVEL INDICATION DUWN6 REFUEUN>> AND MID-LOOP OtCAATION VIA TEMPORARY CONNECTIONS TOL-FW494AL-FW-476. A TEMPORARV SPOOL IS INSTALLED AT MOV-RC-99S TO PROVIDE AN ALTERNATE FLOW PATH TO LT-OC>M1C A LT-RC-tB2C. LE-RC-4S0 4 LT-RC-480 ARE INSTAUEO ONLV WHEN NEEDED FOR AUK-LOOP LEVEL THEV PROVIDE RCS LEVEL INDICATION VIA TEMP. CONNECTION TO L-FW-489. 24. 28. RTS INSTALLED IN WELL 29. PARALLEL PIPE PATHS SHOULD BE OF APPROX. EQUIVALENT LEN9THS. FLOW PATH LEN6TH OF EACH I" PIPIN6 SECTION SHOULD BE AKttOXIMATELV

  • FEET (12MT1 MAXIMUM).

10. 11. TEST CONN FOR LOOP STOP VALVE ANALVSIS. 12. ALL INSTRUMENTS ARE SUPPLIED BVW.- 11. LOCATE AS CLOSE TO CONTAINMENT AS POSSIBLE. DEAD W6T. TESTER PENETRATION DET. REFER TO SECT. 4.0 PACE 5.16 C STDS.

  • ITEMS MARKED 8V ASTERISK ARE SUPPLIED BV W.

THE ]V EQUIPMENT NUMBER IS SHOWN IN PARENTHESIS 15. TV6ON HOSE TO BE CONNECTED BETWEEN 1MESE POINTS FOR FILUN6 A DRADON6 OF PRESSURIZER 14. ft-MT HOSE CONNECTIONS 17. ir << 29* RED. ELL. CONNECTS HOT LE6 STOP VALVE WITH STEAM CENERATOR IS. 19. TEMPERATURE ELEMENTS LOCATED ON 5ENSD06 LINES. D runv i<<<<ait>><<i mini rrcr<<M>> HOW OUCtkM -UUFBKUn COOUNS Mr* O1MSIM-MINT (MUM 9V>>TCM>>>SM-I >>.oiv ckham -cn>>wiwa<vw. gwrtot it*. <<m PUWOlMUN-ltltltMinTHNfTB. <<M-lfl Block Oiacrmk-aVtwc control block d1amuu-6vtavg protcction BIOCK MMIUM PacesuRaCR LVL.COHTi 4 RH-tlA. IM-tCC<<D W-H4 ItSCOIOSHfCTI USWKsmtrA

BLOCHDMMAM FR[S*WIIKeR PRSS.C0NT.4mn B4BWJO SHUTS turn tmstm-naam. >oat umool (raw M-sw-t SYMBOCS: 0-BLkNKtO DawM COMNUTIOM V-BIAHKCO VU4T COMWCTMM to-pml eatN FC-PAU. ekMID LMC-LeAX IMUITORINS CON. sis - actuatio wf ttrmrt uwcctiom MB-IHVOB, MIBMSBMRIIR 0MS-<<UT*iBt MMMLC BAP<<IW VUS-VM.VB *TlMUAKOfFraB COMTMUMMM *M9BVTWL II OtUMflMi KM--V4A tfo-NUOU W*W tC-ACMMBTIIATlVtlV COMTRSurO ClA.-ACTUA.TtD <<r COMTAWMtNT ISOLATION MWMAH0NM. FAT-FAIL AS IS. KC-HOSe CONUCCTION GROUP CLMSIFKATiaNS CONSTITUTES A CHANGE REVISION 31 SATISFIED ECP B't-Bm INCORPORAIEO ECP 08-B304 OUN 08-0004-081-684 DUN 88-0084-882-084 FFNOC HUCttlK BfMTING COPANt

5/8/09 BEAVER VALLEY POWER STATION UNIT NO I FLOW DIAGRAM REACTOR COOLANT SYSTEM-SH 1 -f lAAl?7S-RM-0037A

10 No. 8700-RM-0037B QT>3o 1--RC-I56-1582-0I -J -RC-IG6-1502-O2 .CIA I2*-RC-III-E82 oy4t-RH-l5-l53W RM-4I0-I r-OC-162-152 RM-34A 3--CH-l38-IS3W RM-31A 3-CH-I46-I53W RM-3<U T-CH-233-153W RH-39A RH-32A S-ISI 3/<<'-RC-I15-I53W-s i J ^-3'-CC-226-l51-03

  • *""'*'*>J^2-^C23Bl5l03 HEATERS OFF (LOW LVD I.F.TOOWN ISO ILOW L>>L>

HEATERS ON IHI LVD /-2--CC-234-l5l-03 l-tc-222-151-03 RH-OTAf£4 >J/<<--HC-l4B-l5JW 2--CC-238-I50I-O3 SRM 22O.P RM-220 PRESSURIZER HI LVL REACTOR IRIP LO PRESSUR1ZER LVL SIS ACT LOGIC 2"-CC-242-l50l-O FROM STEAM CEN IRC-E-IB (RM-37AI V 31#-RC-5-258IR IRC-P-IA '1v.Jv (pcpch reactor coolant pump OUALITT CROUP CLASSIFICATIONS ARE INCORPORATED BY REFERENCE* INTO THE UFSAR. A CHANCE TO 0UAL1TY CROUP CLASSIFICATIONS CONSTITUTES A CHANCE TO THE UFSAR. FOR GENERAL NOTES REFERENCE DRAWINGS SEE RM-37A ALL MANUAL VALVE EQUIPMENT IDENTIFICATION REVISION 3<>> INCORPORATED DUN 08-0375-631-084 SAFISFIEO ECP flq-BI<>>7 FFNOC NUCLEAR OPOUTim COPANT BEAVER VflLLEY POWER STATION UNIT NO I FLOW DIAGRAM r-./.. l REACTOR COOLANT SYSTEM SH 2 <F*UI) UF I 87bb-RM-0037B

I le, z,o !sa I f,] 3 Isst(/) .o D cl tFt S ! i r T i 6 i g E Y adq f,t-dTD r m' i n e F J T J P - G l r f i ! t r{ l t= n' T i 9 D\\ fl F EE H +lfil q i A - - ja* I TEH 8T$ Iln \\ U

  • t v E TIH l n A l o YJ.ft

? E8r iF i ? o 9 6 t, oI ri ?r Ei: I sti rrof ++Si FF Bg ?? o0ri.a4 W"il T+F EI Tfri1 {*n H;, ll'*\\ d l l - L E l r l d O .#-E EP l3-t E{ht ilaii + t:+x _ $

  • grT sAf a*E-lEi

+ n - T I Ei,r+ i D j - i ! tifl ucE z tr ( j n t. i A i T 6it t 8 l 3 -tE^11 t l - l ,*'l oo uo off E o !

6ut ?

B F o o D 3 TO N f o I E o t B E, o I D !o-o N t r o J Z a - I Ia* o O e - N O 6f -6 I lf*lr i+iii ,fl:1ifi Jfr ffi: id, t? ltl ^

DFTEI l*

t!r 4 Fi 2. 6 ! (b{' dt g -a iz f o c6 i l\\; N -a A* s&5 N! \\ t t L o I 6I a =l q d I= t, t o e?F --il L+r liliil i'L L ___ t/2.-cl-zt9-ts3,t-ozJ sJ I 4. 7 o i o 5 {i kc T ? $? F 4 0 5 T : N E l,/ or 6 o o N ' T, riiq o N. i or ? o I 6u -'1 5 ! T I \\lu t {9r I I - J FI D mn Drrm T o{rn T an D-{ oz z{ zo IDftc) z 6) nc <Tl o r r-o c,{ 3mct n D

cf6, 1 f F =

ot-q ut an I (f Jo t e6ea)

zo O !ss I ll 3 Isa L).o w N ot o I oq it{ Ax, J q a t o Jg It qJ n-NoI (t a o o E N o (I o{ oI o G q oI o rjl t N o I g u a Nt oI o q a q

'?-!--:1 rt I

or o T

  • o-o 6{

i 9 a A 3 I o u( \\ n 6 ot o:r N.o.' N n N u{ .lo r l Lelg o t0{,l ^l 6 a T E rh.f a l t j N a a 6 o rt o I{ (t ^t 0{ o,{'l o{ o rt 1--t 1 itE st Ir-i+ ru .r d:e A H T = H$EE H6 fii:*i i:*g giins Ftfrs s5 5n m in

sls r P r
6 H Inil 6 0 d N i n ry nI Iuu I

q I c,o t f'E{ u N I -*6 T+?- Hii" g! 1I a 0 d o oB o-atl a rtT{ o u t N* o (rl a 3 o rt a N oT o u a u n e o t rt (1T nr !e (tl N .lp -16 6ls olH 6l? .lp r16 6l? nZ rtN (t U f fv !o o q oo, BEi^; {Pts*n q=s n, !e plp alF U o o zo ot c u0ra n 6 63 o 6 qo t zo o 6 q o z o o o a I 2o U o ag q} z D n _ 5 9 IsET; BH-5 s igsixi 6 J @ G I u or \\ at3 It E iis3' dxeE b 2'-CH-2?7-f{lTE r \\ o Is u N A t u o a ol 16! -:i :fm . @ O l N E @ N @o alo ! { oD o u o+ n rt o B t &. B N r F S s F 5 ' p P F : - r r r r r r { ';ilEiEl'tiIE

  • EE t au I;g

^l a D g 3H IE $*He t +8* ETFd 3$l J oT qo u nT o6 n-oo 0u{ it o I olo 6g o n u o t T B i e i x

( { o K i \\ " / <

r{H \\.< oI O o a o .l ri I I'l(' a , 6 _EiE!; oQ ' - u I o o I .lu o o E ocom I !B Ic Im I 2 o \\ Hlp sl6 o oI 6 o

t t,

plr el$ ola O t D{ ua,r( Ioo nI+t-o - r i e { rt I ato u C c, isHE iiEEfiAIlig 'g$frF* P 3 od g A I o I o d f 0 o I Jj ulo( clo , x a a ! t ! ! ! + I T + T T T T T isH$tg$3$ b zo-o { gs im m r{ o+ q $ t 6i+ g o d 6 nI d@ oo o o (,l o D n (t J u t o r! nI B o GI Io rH g N N 8 P +E+ En oD o u N l rF 39 aot fol iBs -drF r I lt oI (t tE o tCl I. ri o o g n-De CPB.= T9 la E e ? !BE s B c F l. EiH J D o. I D ifrE iAaH l P s B n t o i l iffs rt qE

  • frr 9 ! -r;E nlF 9!9.

Q(,PFiIH udE e83H:3 oo:o n DoE;6 rili

  • s$

It m a aE tts t;r I I I I I g n nr 6 JH {D m D m

o Dt-rm 1'

o{trt a a J D o z E= -l 6 - T

- cl

= f m o r)D oc, z t {x) 33 f r l,C' < I {.r,D 1 7 m o = 7 U)Cl t\\) t a6ea) (r Jo tI I rF) ii

^

, a i E:. i + @ l e l o l E I 9 l -

No. 8700-RM-0043A I I I /X--CV-t-H9-iOy H CONTROL 3/4'-GN-IB-6B NITROGEN SUPPLY FIG 11-2 <A-M/2--GW-II7-NB L0 RO-IGW-I83CI RD-1GW-IB3C2 RO-ICW-I03C v I/2--CW-II2-N8 l/2"-CU-2l-Na l/2>-CC-4fi2->>l8 REF COMP COOL WATER FIG 15-2 IE-K I RM-226 'I/2--CC-463-N8 11 FROM COMP I I COOL WATER I1 FIG 15-2 10-21 I RM-22S \\ RM-22B 1CW-I04B \\ W-I83C2/ VIGW-IBX r I/2--GU-I88-N8 /l/2>-GW-2l2-NB-I-GW-I86-153B, CI/2--GW-22I-NB CL N8lCL ,538 lCL 153a/ ^ ^1 I r-CV-37-1538 FROM CONTAINMENT PARTICIPATE GAS MONITOR PURGE RM-IRM-2ISA B FIG 41-5 <D-S) FROM HSHH-IGW-IBBAi___i FIG ^ FROM CVS SWEEP GAS BLOWEfO 648-17 02 ANALYZER RH-43B FIG 11-2 10-11 l*-CHS-7-151 FROM RSHH-1GW-I088 u-t FIG 43-WA-4I T i -*lJ-l3^-V FIG l">>-2 <E-6lP>> 1 RM-43B 4'-PG-l72-l52-< T-GW-I2S-I54 S UNIT I 1 PURGE TO [ RM-1GW-I0I AND O2AS-IGW-II0-M2 10 NOTESi A. REFER TO BVM-42 FOR ALL INSTRUMENT CONNECTIONS. B. I* SUCTION TO RM-GW-IB8A. MINIMIZE AMOUNT OF ELBOWS AND HORIZONTAL RUNS. BENOS TO BE 5'OIA MIK. CALL VENTS. DRAIN. INSIR AND RELIEF VALVES. ARE 3/4' UNLESS OTHERWISE NOTED. FROM GASEOUS WASTE. CONTAINMENT & y SWEEP GAS FIG IS-2 (C-IBl RM-<1SB PORTIONS OF THIS OIAGRAM ARE NUCLEAR SAFETY RELATED TO PROCESS tfENT ON UNIT COOLING TOWER TO/FROM RM-IGW-IB8A I AND P RM1GW-IB88 FIG 43-SB-2KB-31 , N-3/4--GW-224-I54 TO/FROM Y RM-IGW-II0 QJVt/b-3/4' DUALITY GROUP CLASSIFICATIONS ARE -INCORPORATED BY REFERENCE* INTO THE UFSAR. A CHANGE TO OUALITY GROUP CLASSIFICATIONS CONSTITUTES A CHANGE >>0 THE UFSAR. REVISION 42 INCORPORATED DUN B8-B6I2-80I-BB2 FFNOC MOOR CPCRATIHB Ctt§WfT 11/18/08 BEAVER VALLEr POWER STATION UNIT NO 1 FLOW OIAGRAM CASEOUS WASTE DISPOSAL SYSTEM TOlg 42 2I-N0V-288B BBiB7 K:\\ul\\RM-B843A.DGN 'PflEPMISD OK

No! 87OX6-RM-*3B os mmuo Of I* ntm rtaun I GROUP CLASSIFICATIONS CONSTITUTES A CH(<<*>t . ^S \\ J.

  • Mini moo.

V TO THE UfSAR. HUCLEM OKRATINB COPANT BEAVER VALLEY PQWEfrSTAJDN UNIT. S&W DWG. Np ppppp

rTTH'i'ri'rn i rri'i'riTi 2 i 4 5 Q. i i r<<i << i i r i i No. 8700-RM-50A FROM i FEEOWATER INJECTION TO SAMPLE COOLER I4A-I IC-lf RM-32A EEOWATER TANK 3 25-2 10-11 BM-39C IRC-E-IA STEAM GENERATORS REF. FIO 6-1 (B4) r-KFPD-27-601-' RETIREO TC llN PLACE FEEOVAUR mri tank 3 F1C 25-2 IE-II RM-S8C AUXILIARY fVFEEDVATER AMBIENT TEMPERATURE MONITORING TRAIN A AMBIENT TEMPERATURE MONITORING TRAIN B -WFPD-2B-60I I RETIREO UN AUX STEAM FIC 27-2 IA2) RM-168 2"-WGCB-l-60l-02 r-WGC8-2-60l-O2 -. TO SAMPLE COOLER FIC I4A-I IF-ll RM-32A IRC-E-IB STEAM GENERATORS REF. FIC 6-1 104) 1FW-E-8 BLOW00WN TANK REBOILER FROM MAIN STEAM LINES FlC 26-4 IG2I RM-28A 2--SHP0-I6-6O1 LAH SIEAM GENERATOR BLOMDOWN TANK IFW-TK-I FROM SIEAM GENERATOR NITROCCN BLANKETING SYSTEM FIC 21-4 <F-I RM-S4A TO SAMPLE COOLER FIC I4A-1 IF-ll IRC-E-IC SIEAM GENERATORS REF. FIG 6-1 (F4) STEAM GENERATOR DRAIN PUMPS FIG 17-1 IE-8I 30B -I/2--GN-38-15 3*-LW-135-l5l FROM COMPONENT I COOLING 1 SYSTEM FIG 15-2 10-4) RM-22B ALL VENTS. DRAINS. TEST CONNECTIONS. INSTRUMENT ROOTS. AND RELIEF VALVES ARE 3/4 INCH UNLESS OTHERWISE NOTED. 2. REFER TO BVM 42 FOR ALL INSTRUMENT CONNECTIONS. 3. SAMPLE CONNECTIONS TO BE LOCATED AS CLOSE TO STEAM GENERATOR AS POSSIBLE. FSlISCH 160 SCH 1601 02 NON 0 4. REFER TO BVS 46? FOR TEMPORARY STRAINER INFORMATION. 9. ADD NIPPLE TO VENTS AND DRAINS. 6. 1FW-E-8 HAS A 3 INCH NOZZLE CONNECTION AND A 4 INCH X 3 INCH 150* RF. SO REDUCING FLANGE ON NOZZLE. RV-180-IBI HAS A 4 INCH 150* RF INLET FLANGE AND A 6 INCH 150* RF OUTLET FLANGE. TO COMPONENT COOLING SYSTEM FIC 15 S (0-41 RM-22B 7. HEAT TRACE CIRCUITS ON LINES 4--WGCB-40-6BI. 4--WGCB-41-60I. ANO 4--W0CB-42-68I ARE RETIREO IN PLACE (SEE 8708-RE-63BM). FROM RM-iBO-tea G 43-2 (B-10) RM-S43-2 DUALITY GROUP CLASSIFICATIONS ARE 'INCORPORATED BY REFERENCE* INTO THE UFSAR. A CHANGE TO DUALITY CROUP CLASSIFICATIONS CONSTITUTES A CHANGE TO THE UFSAR. ILW-P-13 STEAM GENERATOR BLOWOOWN TRANSFER PUMP 8UIL0ING SUMP FIG 9-4 (C2I RM-34C PORTIONS OF THIS DOCUMENT ARE NUCLEAR SAFETY RELATED 2*-OA-l'M-IS4 I-I/21 3--LA-1B-I54 ALL MANUAL VALVE EQUIPMENT IDENTIFICATION NUMBERS ON THIS DIAGRAM ARE PRECEDED BY THE SYSTEM DESIGNATOR MBO* UNLESS OTHERWISE INDICATED. REVISION 2 INCORPORATED ECP-83-0028 IDCN-I-RM-B850A-EB5-B828-0I BEAVER VALLEY POWER STATION UNIT NO J NUCLEAR OPERATING COfMff FLOW DIAGRAM STEAM GENERATOR BLOWOOWN 17-JAN-2086 14i34 K:\\ol\\rma85Bo.dgn

I-1

I II

I

I

I

I If"II

I

I 1 *II* I -1 No. 8700-RM-0053A MOTOR DRIVEN AIR COMPRESSOR 1EE-C-2A 1 J -ASC-I60-ISIB COMPRESSOR L IEEjC-JA j I/2--ASC-157-I5IB L__IEE_-C-JB I-1/2--ASC-70-I5I-O3 3/4"-ASC-208-l5l-O3 -1/2--ASC-8I-I51-O3 3/4#-ASC-2l5-ISI-03 IEE-SP-4A1 MOISTURE SEPARATOR (TYP) IEE-SP-5AI MOISTURE SEPARATOR (TYPI IEE-SP-581 a MOISTURE ~ SEPARATOR 2 (TYP) A MEE-4IT /2"-ASC-l67-15IB I/2--ASC-IG8-151B I-1/2--ASC-7I-I5I-03 3/4--ASC-207-I51-O3 -I/2--ASC-78-15I-3/4'-ASC-2ll-15l-O3 l/2*-ASC-82-!5l-O3 SC-2I6-I5I-03 ISI-D3 3/4--ASC-206-151-03 STARTING AIR l2a 1-1/2- 'NKS 1-V l-l/2'-ASC-79-t51-D3 3/4--ASC-212-I51-03 STARTING AIR TANKS 83-151-03 3/4'-ASC-217-l5l-03^*1l STARTING AIR -1/2* ENGINE 1EE-EG-1 GENERATOR 3/4f-ASC-202-l51-O3 STARTING AIR TANKS 1--ASC-203-I51-O3 rH-lEE-3' Y I" vH-l/2*-ASC-218-MFR-03 l-l/2*-ASC-223-MFR-03 1-I/2--ASC-220-MFR-O3 I--ASC-21S-MFR-03 -ASC-225-MFR-03^ / I l'-ASC-22'<<-MFR-O3-' I rgiTKy m l-l/2'-ASC-23B-MFR-03 r-ASC-22S-MFR-03 SC-235-MFR-03 l'-ASC-234-MFR-O3 ^-3/8>-ASC-22l-N8-03 3/8--ASC-222-N8-03 3/8g-ASC-227-N8-O3

  • 3/8t-ASC-226-N8-O3 v 3/8'-ASC-232-N8-O3 3/8*-ASC-231-N8-O3 3/8>-ASC-237-N8-03 -^

3/8--ASC-236-N8-03 AIR STARTING UNIT FOR OIESEL GENERATOR SET IEE-EG-1 AIR STARTING UNIT FOR OIESEL GENERATOR SET 1EE-EG-2 2<-0L-81-15l '-0L-1BI-I5I CL136G 3--0L-S2-I36G-' 4*X 31 AF-EE-1BS IEE-FL-1B y-(lF0-23)/ 2--OI-4B-151-03 3/4--0L-63-I5I-03 4*-OL-34-15l-03 AF-1EE-1I1 2" l-l/2*-0L-4S-l5l-O3 2*-0L-8B-ISI 2*-0L-87-13SG 1EE-TK-2B DAY TANK 55B GAL. 1EE-TK-6 DIESEL GENERATOR FUEL OIL HOLDING TANK 8B08 GAL 2*-0L-SI-151 2*-0L-<<)8-151. IF0-32V1 2'-0L-52-151-03-^ IEE-TK-10B OIESEL GENERATOR ENGINE MOUNTEO FUEL OIL TANK 95B GAL 1EE-EG-2 DIESEL GENERATOR SETl l/4--OL-76-N7-O3^ 3/4 N2 C2 Nl Cl C3 IEE-TK-IB DIESEL GENERATOR FUEL OIL STORAGE TANK 20000 GAL DIESEL GENERATOR FUEL OIL TRANSFER PUMPS 10 GPM AF-IEE-106aO 2"-0L-51-l51-03-/1 ALL MANUAL VALVE EQUIPMENT IDENTIFICATION NUMBERS ON THIS DIAGRAM ARE PRECEDED BY THE SYSTEM DESIGNATOR '10A1 UNLESS OTHERWISE INDICATED. AF-IEE-I IF0*22J 2--0L-44-151-O3 REFER TO BVM-42 FOR ALL INSTRUMENT CONNECTIONS. ADO NIPPLES TO ALL VENT AND DRAINS. 1EE-TK-2A DAY TANK 550 GAL REFER TO UNIT 1 RM-0536-B3. 04 AND 05 FOR THE OIESEL GENERATOR LUBE OIL. COOLING WATER AND AIR INTAKE AND EXHAUST SYSTEMS. IEE-IBIB 3/4--0L 151-03 3/4--0L-2S-151-03 IEE-TK-10A DIESEL GENERATOR ENGINE MOUNTEO FUEL OIL TANK 550 GAL 3/4'-0L-37-15l-03-' 3/4--OL-30-15I-O3 QUALITY GROUP CLASSIFICATIONS ARE 'INCORPORATED BY REFERENCE* INTO THE UFSAR. A CHANGE TO DUALITY GROUP CLASSIFICATIONS CONSTITUTES A CHANGE TO THE UFSAR. IEE-EG-1 DIESEL GENERATOR SETl ^- 3/4--0L-II9-151-03 IEE-SP-5B2 LOCATED INSIDE DRYER HOUSING. N2 C2 Nl Cl C3 IEE-TK-IA OIESEL GENERATOR FUEL OIL STORAGE TANK 20800 GAL NOTES ARE LOCATED AT GRID LOCATION F-l PORTIONS OF THIS DIAGRAM ARE NUCLEAR SAFETY RELATED EVISION INCORPORATED DUN 11-0691-001-002 DUN 11-0691-002-002 ECP 11-0691 BEAVER VALLEY POWER STATION UNIT NO I tUXejUf CPEMTINS COMPAfff FLOW DIAGRAM EMERGENCY OIESEL GENERATOR FUEL AND AIR SYSTEMS dtcjo. B700- RM-0053A

No. 8700-RM-0410-001 1 1

I' > I

  • i
  • I *i' I

i* I

  • i' I i'

I ' I I -1 I' I' I 10 TO REFUELING WATER STORAGE TK 1OS-TK-I UPPER SECTION I3-1IA-6I 152 I/2--OG-260-1502 VSLO/ RM-34A FIG 9-1(8-61 TO LOOP 2 COLO LEG IG I1-21E-2I I0--RH-23-I502-OI l/2*-OG-28!-1502 TO LOOP 3 COLO LEG FIG 1I-2CG-2L I0--RH-24-1502-O1 CL 602 ^6'-RH-44-602-O2 /"CUD ~ NOTE C I ° L3/41-RH-27-602-O2 NON-REGENERATIVE HEAT EXCHANGER J 1CH-E-2 0 FIG 7-l(B-8) RM-3<)A \\ TCN <-I4<-RH-2-602-O2 ^W-RH-43-602-02 CL 682 CL 1502 /I4--RH-4M502-O2 U-3/4--RH-32-G02-O2 224 TO ISS-E-5 SflHPLING SYSTEM FIG 14A-KC-II RM-32A NUCLEAR SAFETY RELATED DUALITY GROUP CLASSIFICATIONS ARE 'INCORPORATED BY REFERENCE' INTO THE UFSAR. A CHANGE TO QUALITY GROUP CLASSIFICATIONS CONSTITUTES A CHANGE TO THE OFSAR. ALL MANUAL VALVE EQUIPMENT IDENTIFICATION NUMBERS ON THIS OIAGRAM ARE PRECEDED BY THE SYSTEM DESIGNATOR MRH* UNLESS OTHERWISE INDICATED. OP MANUAL FIG NO 10-1 FFNOC 1 L.JVW\\S NUCLEAR OftMTINS COP/NT vm 5/7/12 NONE PIPING INSTRUMENTATION DIAGRAM RESIDUAL HEAT REMOVAL SYSTEM AA -0410-001 ' PREPARED CN

17-MAY-2012 10:10 Ki\\ul\\RM-e4l0-e01.OGN

z,o m\\ F I I3 Ie 5 I Fs p n D o 2q)aia

c3 d -

(r,l Iif e r r 2 j;t -r ti-3! q q) a _6 T} $F= a -5 9g

hi Vang 2 0'e

? ea 3H = t G M 5 D22 -9 o ue o U) rT D ?m

  • ti 6 l o l o rl-FIE I{JN t- --- ---1 I

r-o A'-rs$F x il 6il;q }{ irsf H i 8 D 6 6 o 6 u o I l. i {0 tIc o o n olo o r.! o ou I uo o t Y 6 h z T o c o zo o o o o rto o E1 F*e,- li;:' I o uo N I o o l d r < 6 Ts 6B o z,o z o $rHi' 'li rc a t z j 6 e N !,i U T E T c* r E o e 0 j !('l t 0 q o tle N o .'l q e o (' 6 t us 0 o No 5 o }g 3+ i; ", 3;"& o 0 u I N 0 ia i r z ? c 3 e 2 j 6 ffiq ! 0 0 ENF EfrA EHN i{ o I 3 D P ^ t a i e lt.[ r 1 j rtB O r O'+a 6I o-rf 6 t Ito o tJ

  • 3F lv3F f I l,f;iEt; e 5 q

0 I u t o o 0 t us o $a Bri +l-fi Eli o l g nz -Fh f6h B ? c H o l dt -Hd w I t <;rI .l 4 ar t o d H-2o In t{ R q ';9 t"?1 )[ jril $$t;=' tqi r { s ol ('l o ulo o o lt o rll s o ol at I?s o

r hj"H dl d"H 3l-Eii;*

q q (' q t 6 o! o E I N o 2o z(D I oo

t <

./ ri! tt"L 4z'B 4p N .1-l.> o t l ; ll'+'i* D d.t d"5 to o i. 6 E zI E 6' zo-C' C' n D o o r ? Isde IFIEC !eE' (' oH D.t a3 aF$E -s EEidFI IHgiii - = { 9 I ldf;e n FHE-6 tt 63 I 6 F, rl c !

Hdfrd Ic u

3 l nr ' F o - ? r, P5-

P ]

? a B SGli .jg PIP EIF i l E tg ri o! .looil z9 g Fg cl ig I \\- uo (t{ o 4 o are 3r Itz I I !0 t Pr F:F Fti Ftfi v6 il L o u a D B o1 I BHE !ri B } "Fd i -n H 6) z Cf I o I I 6 B \\.; ds N$+F Fn f I I t is le; q o G? og o n o q g o E' 26{ n o g ? ug \\ N v} d o u a o o q (l Ito-I (,l o o g Ite? o H;C ! @ nFfrH $fia BfrB o D o tt f o gt olo 9N 0 I c E & 2 i o $s a i,' l,l o al, FT?g Ii" + lo F noE ! c ! D -3*fl U3 { 0 3 o Ite ao ,h fi It( o { url 4 n T <gr r I l 9 =3rEsii o Io +c o t o 6l N6 q Es us 0 q 6 .t 6 tT .-i; o D tE ! l c ! f;I: ^l z o $;EE-sEE o o u., oz o \\ g, Iu tlg oo { 6 ul u0D oN 0 3!*i' I =rtrfr FJ, in{ g ' l EI 1E? pp ET+

${

EI q il; m o I z \\ffi ilFg- $,J$-#' E ffilr+liffi $H o *gE;* e i i ? t - t i t 6 = I [;EI*H rt o l,l o ooo 6 q so g o cr tt UO z* e ? o src- ^li[6r t m E oi q 2 o H EE o o a E 2 o r-o-T'tY 6 I d D i0 olF? +E ? t o l (,r nE I 6 q B +s F P x 6 = o ' i N e r? h n& d"H a i O r o 6 9ui -69 g?tr ", i;o l$ la F$

  • t

'g z (Jrc, ] F t t t - t H< zv) 7 n m = qfi zD. v : o i;z ilg 3 D6,tt D 3 TD m D m 7 D?r rrl 1t c'{ rrr T u, -t D 1 o c z I zo o{ 19 e f, 3 I 65 Ies (t Jo T p6ea)

No. 8700-RM-0411-002 I 9 ro caseous j WASTE

DISPOSAL, 0

FIG 1S-IIA-I1 HM-43A 10 PRESSURIZER RELIEF TANK FIO E-2IC-II RM-37B -CN-6-68I ro volume CONTROL TANK ^^ FIO 7-3IA-5) RM-11A r 1/2--BN-3I-NS ro VALVE 2-CNS-B8I -883-4 -y UNIT II UNIT 2 \\ 1/21 ^r-CN-21-1582 A 1/2" J SAMPLE SYSTEM FIG I4A-KE-II RH-32A 2*-SI-l22-6e2 j -SI-188-682-02-' 3/4--RC-248-N8 TO LOOP 1 REACTOR COOLANT SYSTEM FIG 6-II0-I8I (IRC-S RH-37A CL6MI l CLI58I lCL1502 H'WO-382) HlW-388) (lNG-]8l)-' 681 ^ N CL 6821a NS 3/8--SS-I34-N1-02 -CN-1-6BI-D? " NOTE T-GN-78-681 -1 LOOP I COLO LEG I FIG 6-ICB-2I RM-37A FLOOR DRAIN (1_- SYSTEM ^" FIG 1-1 (E-71 RH-34A STATION INSTRUMENT AIR CLIS2ICL682 r-OC-68-152 'EMT AND DRAIN SYSTEM FIG <)-l(C-4ip RM-34A iSAMPLE SYSTEM FID I4A-IIF-I) RH-32A 3/4--RC-237 TO LOOP 2 REACTOR COOL SYSTEM FIG 6-KE-1B) RM-37A /IIA-I88-I HKlNG-317) I--GN-44-682-O3 -if 3/4'H>>-56-N8-03-x K UT HID 3£4"-SI-<<<-IS82-0l 63 >>- r-GN-42-602-03 ir-CN-S4-6Bl-03-' CLE82 CLG8I l"-GN-S8-N8-03-' CLN8 I CL6021 CLNS LOOP 2 COLD LEG( FIG 6-KC-2J RM-37A 12--SI-26 3-1582-01 NITROGEN / AIR SUPPLY i TO PCV-1RC-4SSC IG 6-2<ft-l0l 37C -NS-03 -GN-43-6B2-O3i

^-r-CN-45-682-O3

CL602lCL6ei CL68llCL682 CL682lCLN8 l/2"-ACC-ie4-N<>>-03-< _CLN8_v3/4'-CN-S7-N8-03 CLNS NON 0 03 CLN8ICLN<1 1/2--GN-37-68I CL6B2 NOTE S CLOT /-l/2"-GN-87-NS f-SI-317-682-02 4--SJ-328-682-02 -^ 3/8' TCN NITROGEN / AIR SUPPLY JTO PCV-IRC-45S 0 FIG G-2CB-IB) RM-37C GN-86-N9-03 r7-SI-ll3-602-a2 V / 2*-SI-M2-6B2-O2:C r3/4--SI-ie9-82-02TO SAMPLE SYSTEM <p v) FIO I4A-KE-U RM-32A r-GM-82-682-03 NOTE GN-TK-IC r-GN-11-682-03 NOTE S I 1/2* CL682lCLN<I NOTE S 3/4'-GN-8e-602-03 l/2--GN-81-N<>>-03 NON 0lO3 V4--RC-238-N8 TO LOOP 3 REACTOR COOLANT SYSTEM FIG 6-1IF-I8) RH-37A FROM INSTRUMENT >>'>> f ALL MANUAL VALVE EQUIPMENT IDENTIFICATION NUMBERS ON THIS OIAGRAH ARE PRECEDED BY THE SYSTEM DESIGNATOR 'ISP UNLESS OTHERWISE INDICATED. OP FIG NO 11-2 PORriOHS OF THIS DRAWING ARE NUCLEAR SAFETY RELATED LOOP 3 COLO LEOf FIC S-1E-21 RH-37A l2*-Sl-264-1502-O DUALITY CROUP CLASSIFICATIONS ARE

  • INCORPORATED BY REFERENCE* INTO THE UFSAR.

A CHANGE TO DUALITY CROUP CLASSIFICATIONS CONSTITUTES A CHANGE TO THE UFSAR. BEAVER VALLEY POWER STATION UNIT NO 1 PIPING INSTRUMENTATION DIAGRAM SAFETY INJECTION SYSTEM 87BB-RM-0411-002 23-MOV-20H 8<h38 Ki\\ul\\RM-0411-O02.OCN

ii'iiiii*>>i-ii No. 8700-RM-0412-001 ENGINEERED SAFETY FEATURES (SAFETY INJECTION. CONTAINMENT DEPRESSURIZATION. CONTAINMENT ISOLATION, MAIN STEAMLINE ISOLATION) CONTAINMENT VACUUM PUMPS WHWPHWHWI 5Jj ^l--CV26-.53B ^JCvEJgLT^'"182 ^^^f^E^^^jj-iT) l ~^£ NON 0l02/^47VT ^ 02lN0N 0 \\- r-cv-12-1538 102 L 2--CV-2-I54-02 I/2TTCN Y^T) CI^ KT FROM RlS-lPfiS-58^ I CANNEQ BLOWER FR0M RIS-IPAS-5A << J TO 1HY-C-1A FI° <<-l(A-3) f-H2A-1HY-IB1B FIG 46-KA-2) FIC ^6-2(0-11 52(frV-2--CV-I5-154-02 ^\\ MA j 1LM-ITO-2 W Ml DUALITY CROUP CLASSIFICATIONS ARE

  • INCORPORATED BY REFERENCE' INTO THE UFSAR.

A C?SHS!.Ifi 0UW"ITY GR0UP CLASSIFICATIWK CONSTITUTES A CHANCE TO THE UFSAR. ALL MANUAL VALVE EOUIPMENT IDENTIFICATION NUMBERS ON THIS DIAGRAM ARE PRECEOEO BY THE SYSTEM DESIGNATOR 'ICV UNLESS OTHERWISE INDICATED. OP MANUAL FIG NO 12-1 BEAVER VALLEY POWER STATION UNIT NO 1 PIPING INSTRUMENTATION DIAGRAM CONT VACUUM LEAKAGE MONITORING

No. 8700-RM-0420-001 <HrCD inn ks 4'-FC-10-152:' ^6'-FC-18-152 3B~ __VU DRAIN LINE FOR DIKE 141 FAILED FUEL STORAGE CANS FAILED FUEL STORAGE CAN PIPING SYSTEM

  • M/2'-FC-107-NS FROM WATER SUPPLY <<__

FIG 8-6 (B-2) ?"*" RM-21O ^2'-FC-127-152 O

'At AUXILIARY FUEL BLDG IjUNNEL I BUILDING 3--FC-27-l52^ 4*-RH-34-152 FROM i RESIDUAL HEAT PUMPS FIG 10-1 (C-1) L\\ _S iu 0 1QS-TK-1 FIG 13-1 (A-4) FROM

  • m 0

1CH-BL-1 FIG 7-3 (D-6) RM-31A AUXILIARY BLOG FIG 13-1 (B-7) COOLING SYSTEM PURIFICATION SYSTEM QUALITY GROUP CLASSIFICATIONS ARE INCORPORATED BY REFERENCE1 INTO THE UFSAR. A CHANGE TO DUALITY GROUP CLASSIFICATIONS CONSTITUTES A CHANGE TO THE UFSAR. ALL MANUAL VALVE EQUIPMENT IDENTIFICATION NUM8ERS ON THIS DIAGRAM ARE PRECEDED BY THE SYSTEM DESIGNATOR "1PC-" UNLESS OTHERWISE INDICATED. OP MANUAL FIG NO 20-1 REVISION 12 INCORPORATED DUN 13-0561-003-012 DUN 13-05B1-0B6-B08 FFNOC FikiEhirgy i <_f¥<<^v^ mamopothimecompany NONE m 6/V15 amir MVF BaueJ MKjtr BMCIJir. mturr BEAVER VALLEY POWER STATION UNIT NO 1 PIPING INSTRUMENTATION DIAGRAM FUEL POOL COOLING PURIFICATION SYS t&% p lAA[T£aB.RM-0420-001 12 k.\\ul\\RM-0420-0Bl.OGN

NO.8700-RM-0430-001 rri'i'l'i'n i"irir>r* iii<i

ri11 r i i CL3ailCLl5jJCL3Bt 3/4--WR-635-3BJ-03 241-WR-5e2-l5l-' 2B--WR-58I-I5I-" dUK GEK TREJ-IRW-27B CL3Bl(CLI5llCL3BI 2*-WR-475-l53A-Q3-v T ^-2*-WW-476-153A-Q3 TO BACK UP SEAL WATER SERVICE WATER PUMPS FIC 3B-1 (C-21 RM-47C 3/4'-WR-6<>>-IS7W-03 SCM4BlSCH8fl ,6--WR-676-157W-03 3/4'-WR-46B-IS3A-v y-3/4'-WR-456-N8\\ K-3/4--WR-6SI-I57W-03 10 DUALITY CROUP CLASSIFICATIONS ARE

  • INCORPORATED BY REFERENCE' INTO THE UFSAR.

A CHANCE TO OUALITY GROUP CLASSIFICATIONS CONSTITUTES A CHANCE TO THE UFSAR. ALL MANUAL VALVE EQUIPMENT IDENTIFICATION NUMBERS ON THIS OIAGRAM ARE PRECEOED BY THE SYSTEM DESIGNATOR '1RW UNLESS OTHERWISE INDICATED. PORTIONS OF THIS DRAWING ARE nn MAMI IAI Cm MH NUCLEAR SAFETY RELATED UK MHNUflL h Ib NU )-l REVISION 32 INCORPORATED DUN ll-B2%-BB2-ee4 FENOC NUCLEAR OPERATING COfAHT Lfc£_ JfL BEflVEft VftLLEY POWER STATION UNIT NO 1 PIPING INSTRUMENTATION DIAGRAM RIVER WATER SYSTEM 32 ' PKPAREO O>> 2l-AUG-2ei2 66:40 K:\\ul\\RM-0430-0BI.OCN

No. 8700-RM-0430-002 iTn'n'n^TiTiTiTiTiTrriTiTiTiTiTiTi'PTiTiTi'l 2 3 4 S VL. 7 8 9 10 ll 12 l ~ f= = l j~ 1 FIG 30-1 IB-IB)> I 24' UR-I9I-38I-O3-V HEJ-IRW-4A2 6 A' HEADER 8 r r-24--UR-2B-ISI-O3 10 burieoIaux BU)o^2<<--wR-ze-isi-O3 A CL3BI I CLI5I X CMLORIMOfOR VIA C/-IWT-S62 a. r.im "CONTROL ROOM Tair coNoniOKER:: _.L.. CONDENSER IVS-E-4A I I REF FIG 44A-2IB-2I PN RW-IBlAy OTE 13 3g-WR-56-l57W-O3-Cmy,\\ 137 1 ^ 3'-NR-56-IS7W-O3 'CLI5llCLI53lCL157 IVS-P-3A <f y-VR-B50-l5l-O3 FROM FIG 44A-2<~"": IF-* T-CONTROL ROOM AIR CONDI IIONEH-' --.CONDENSER N 3--WB-68-157W-03 'N 3"-wR-45-l57w rT4^ ~\\c'y'r 3--WR-42-15l-03v I fi rO^) P-3'-WR-4S-l57W-O3-^ CL15ll CLIS3 l CL157W IVS-P-3B ^3--WR-652-l5l-03 CUS7WlCLN8/<'*-1>'<<-l2-l*-03 -t FIG 30-3 IB-I> jCH 7-UR-402-157W-O3 j^D 3'-WR-l0G-l57W-O3- ^3"-wR-5<>>-IS7W-03 ^3--wR-ie<t-l57W-O3 Mj<<3 I\\W. iMIII- "L"' 44^-4 "LYPl'l I V CLI57W IB-21 CLI57W A \\l-l/4'-WR-724-157W-O3 y \\ .1 (567>y rO^I-l/4'-wR-72£-IS7w-03 O-TK 566) TV I i 3--WR-I0B I57W-O3-4 "" MHW-I21B m \\ 1 I I-I/4--WR-72S-I57W-U3 -l'-uR-72<<-lS7w-O3 /2-1/2-- / CTYPI tHSTfT-7 J2D CLI57WlCLIS3 lCLI57W L 11--WR-722-I37M-D3 'V-3"-WR-45-!57U-03 3--WR-54-I57W s COOLING COILS 3'-WR-44-IS7W-O3 2--WR-46-1S7W-03 [423J <SK: 2'-WR-7B-l57<<-O3>1l rl-L/2'-MR-6Z5-19JA-O3 / \\ fig 7-ae-ai / \\ r^ !* i/ 1 o>>-tj lich--7a; f*-o 1 \\ o>>-tj lich--7a; f*-oQt 422 03_JJ,0 NCN 0 2I-WR-7l-l57M-O3-/< -?- V,., 3'-WR-57-l57w-O3 CmP 2'-WR-72-l57w-O3^ ^-2--WR-48-l5?w-03 J IV

  • l/2--WR-62^-IS3A-03 cl 1/2" UR-62£j!

^O"03 / Fg__J~ \\ FIG 7-5(D-8> / /IHU-Jirf ^*2--WR-47-l57w-03 9 XV T + !"l/ JL J \\ ('73 Kf 1 JICH-E-7BJ r*-O °ts l-l/2*-wfl-6D8-l53">-03 l-l/?--wR-6?7-l'S3A-m REF I FIG 7-SIG-8. iVr + + -,/ X ~-\\ j JICH-E-7C1 \\ Tx IRW-I07C CHARGING POMP LUBE OIL COOLERS /\\ QzEK? Qt>> r*b \\ T f-WR-4S-l57U-03>> 2--WR-4S-I57W-O3 -^ Y-M>> 2*-UR--3e-IS7W-03 3"-WR-S2-l57W-03-/< 2--WR-SI-1S7W-031 PQlJ-3 IRW-18^--, FROM CKLORINATOft VIA CV-IWT-5S3 r NON 0l03 VIA CV-IWT-563 I \\

FIB 32-6 IE-IB) Vy-CHL-23132 (lWT-S (IWT-3B8K I 3--WS-233-l5l-03-//l 573J I'-WR-72I-157M-O3 y-UR-54-IS7U-O3 LI57WICLN8 03 NON 0 Ojfl ^-f-WB-751-l FIG 30-1 (0-101 (> BURIEOI AUX BLOC 24--WR-IB2-381-03 >^ ct3ei lclISl -c* FROM REACTOR PLANT SAMPLE PANEL fc-CLI52ICLI57U NON 0 03 ^-I-l72 X Cili>\\T,° -l-l/2"-WR-543-!57W-03 f I'-WB-S48-N8 3/4'-WR-747-l57W-O3-' NON 0 -WR-4e3-l57W-O3 n /-C 646 ) -I^M-JFIG 30-3 IC-31 ^-6'-WR-S3-l<37W-O3 REJ-IRU-4B2 \\\\ ^-24'-WR-W-15l-03 -*-i FIG 30-3 IG-1) ALL MANUAL VALVE EQUIPMENT IDENTIFICATION NUMBERS ON THIS DIAGRAM ARE PRECEOEO BY THE SYSTEM DESIGNATOR 'lRV UNLESS OTHERWISE INDICATED. >-24'-WR-l1-l51-O3 DUALITY GROUP CLASSIFICATIONS ARE 'INCORPORATED BY REFERENCE* INTO THE UFSAR. nr> K/)AMI l/\\l rir MO A CHANGE TO DUALITY GROUP CLASSIFICATIONS CONSTITUTES A CHANGE TO THE UFSAR. UK MANUhL rib INU D REVISION 20 INCORPORATED IOCN l-RM-0<<30-002-E03-026e-ei FENOC HOCAR CffRATING COfAHT -n 11/04/10 \\ML BEAVER VALLEY POWER STATION UNIT NO I PIPING INSTRUMENTATION DIAGRAM RIVER WATER SYSTEM -p lAAl*S75a-RM-0430-002 l2*0 ^PRfPAl 64-Nov-2eia 08:m k-iwivRM-zi 3a-aa2.0CN

zo \\lss In3 Is ells {9{, r ( t r ]B3EE sln;aaa +$lEa r aJ* llts lElg EPggE q: x o s 3o t o 0 q{ v ,.tu c' D r ilT oa t3 j 3 0 D oo iEl' J o l 85 z ooz 3FH;C T

t - t - "

F1 't t - a a 1 r o { I d o { g 6 (t t E r^l EIl:l ,C FI 0lq N o o D < i ?;*.r' 7 A raO crIils 3 6 s j E I d ! o t s F n - ct= $sr il*E fii i !(tT al ! l p ? 1 6 3 r l

T O u l rEl' I{t ao ug a,

I I o u pF Fts pli FH 9l T-i1tgl PIP $l$ 17 i l? l Y 03 o tt{ J u o JY{ t{ 5 ( !s N zl o I o zlo ol q iisi f Ee{[

  • grV
  • 4ft i *4Ft Idlr o l*+

+E ft J (! o{ I o .,t o o - n

F F D v 4 z

o T lB . a l } T?T 61 dt: a C v 6 o o u o P*= 6a Ts$ fi Eifi t\\, 6 0 ? N o ?( T olo 6 siffii 83ffi- = a e u zo I IE Tsq l # p l i t d l.l4 l o l t + t t \\ J t iq tro aad iiE$ .j'Ui a E g o o t! !(,l o6 e aT N HF +!3 !gE {, Jo q o o i9-3 o o ooD o 'p ;E c ( ! 6 ,fr tt uI ,m ,{ q{ I Ju B3 J3I{ g RI/ F'1 EE 3*9il*

IHf,T;

-nfr ?{3 E8@ 40 qp* F = < I6o F:? 2 D ! 6 i o fril: ntrfi o z - q { a !o q o oo m D ? lEIfr?, e i l 5 1, r3l=E ?r ift;- -.i..3"_.i_..- I 'lz t5 o q c' N -tc -.be 3 i I I I c i'o aN{ r o Dlo a D n q t 6 { o 2 q o f,ci o l r E t.l.1 nl YE=s t m E D t? O us

q u0 tt D o N Do T OFs c' C, r$l ft dtq 4. t ! l ilcI t us n o gl a f*

0 m

4 8lP $lE q ao ? D I FB F o I 7 a ToH s!6i* as1 I t?T Ni T: qo o n^ ! t r . I a F C ,!t \\ I I!li u E ,:o f o rt c, r63 (J.:n? 3*

  1. j tD o

u D o o i d g o Ts To 9o-6N o o B o C t ,i-a,3 m5 n C, at U d Io sl a du o 0o q q 1 i q o o l u q 6 d o o 6 r Z q'{ !u((, @( !{I(' a( I o{ u B-{ 3m': lf I {? (t i th t J t S l tEt I ry b6+ t - 2 Foll. n U IB. ?o-Qo u.i s o o u t .X al ir a{$E i v u{ 3 Its

t$=t Fit 3,irI

?*; e8 f, ol 6 V 1 +{ N !B g; o N

n I t, o J g R tfi o

Ei-aI o{
  • e t3 lT EE rd o l

. 3Hi dg t! o Iug o t I qs us o 2l dl h E7 Fo cl { t D l' o S( !{ q oo l F l \\l 3. 1 l ! fg5*; FHIfrfr ? 6 r33 g;l 3ii 1 {-I*i iT*? OE t (r o q N + tt o t, I ]H E FI D m I D-r m 'tt o t m I ah DJ oz z{ zo T T z,6) T F ( s fnz u a{ {:o D C { 3 m m t z{ (/)D (4= $tz 3cf D T D 3 (f Jo T e6ea)

No. 8700-RM-430-4 TPTTTTT T"T irn'"TIT 1 6 TRAVELING WATER SCREENS 10 24--WR-I67-IS1 eg^i pump pump i-PIT PIT )T IHrt ...m IT'*T L 24--wr-i6s-isi\\ ETTBfl^B1 L24..WR.l6a-i3i D 3I3~) 5/<!D ^"^ 4--WR-5I4-I5I-1-1/2"^J J 2--WR-51G-ISI TRASH PIT DRAIN LINE

10 RI>>ER lIcL IS^-22^ FROM FILTEREO WA1ER FIG 32-1 (C-6) 3--WF-l-l9l

  • A1 HEADER f

>>T 1 FIG 38-1 (A-SI / 2--WR-6G-151-O3-' 2--WR-67-151-03 ALL MANUAL VALVE EQUIPMENT IDENTIFICATION NUMBERS ON THIS DIAGRAM ARE PRECEOEO BY THE SYSTEM DESIGNATOR 'IRW UNLESS OTHERWISE INDICATED. FROM B* HEADER FIG 38-1 10-51 A CHANGE TO OUALITr GROUP CLASSIFICATIONS f)P MAM IAl FTfi Mfl CONSTITUTES A CHANGE TO THE UFSftH. Ur I IHINUHL f 1U INU REVISION I' INCORPORATED ECR-05-0367 IOCN-l-RM-0430-B04-Ee5-e3G7-0t FFNOC NUCLEAR OKRATIK CO/PANT t 11-15-05 BEAVER VALLEY POWER STATION UNIT NO I PIPING 8. INSTRUMENTATION OIACRAM RIVER WATER SYSTEM AA 8700-RM-430-4 17 "tl I5-M0V-26IJ5 16:21 K!\\.il\\M43iJl)04B.OGN

No. 8700-RM-0434-001 /"CUE) pcv-isw-ibj O-i* >>-7-4FIC I8-3CC-5I 1SA-C-1A (SHOWN IN LOADED CONDITION) MSA-IB8A JrGID <<KiID /-CUD i CUD i<]ED t-C^) -ASC-36-2IB -sj CL2IBICLI2I 3/4-n CL MFGICLI2I ISft-1058 h 1SA-C-1B (SHOWN RUNNING UNLOADEOI NOTE 2 REF FIG 28-210-6) l--ASC-34-2IB-\\l I-ASC-35-2IB-VI I I I ^ N ISA-DR-4 I CL2IB C*jy$ CL2IB C*^)^ O.2IB 3/4--ASC-5S-12I ^\\ DUALITY GROUP CLASSIFICATIONS ARE INCORPORATEO BT REFERENCE' INTO THE UFSAR. A CHANGE TO DUALITY GROUP CLASSIFICATIONS CONSTITUTES A CHANCE TO THE UFSAR. ALL MANUAL VALVE EOUIPMENT IDENTIFICATION NUMBERS ON THIS OIAGRAH ARE PRECEOEO BY THE SYSTEM DESIGNATOR 'ISA-UNLESS OTHERWISE INDICATED. OP MANUAL FIG NO 34-1 PORTIONS OF THIS DIAGRAM ARE NUCLEAR SAFETY RELATED REVISION I BEAVER VALLEY POWER STATION UNIT NO 1 NUCIEAR CPBUTIHB COPAMT PIPING INSTRUMENTATION DIAGRAM STATION COMPRESSED AIR MM 87B8-RM-04 34-001 19

I*I

  • I

1 I' **I*t I"' I I*1 I >>1I I I ii* t*"i*r'i*11*

  • ii 8700-RM-0434-002 POMP HOUSE TEMP.

CONTROL ER-IVS-54-AB-I IVS-F-94A IVS-F-54B 87Be-RB-2E 8708-R8-2E CL2IBICLI53 / 2--ACC-4-2IB / 2--ACC-I34-I53-' 2--ACC-I36-I53 IIA-TK-I STATICM INSTRUMENT AIR RECEIVER COOLING TOWER PUMP HOUSE KjD I--ACC-22-2IB >>L10S-ICW-IBIB2 UNIT I IU.MI1 2 SAFECUAROS INSIDE REACTOR CONT INTAKE STRUCTURE S<<8-46> FILTERF.O AIR FIG 34-7 (0-4>> NOW olo2 y-ACC-113-151-02^ SOV ><i PIC-IRU-II7 FIC M<<C-V .LIOS-ICW-I0IC2 °LIOS-ICW-lf)!D2 CONTAINMENT INSTRUMENT AIR FIG 34-6 (01) PORTIONS OF THIS DIAGRAM ARE NUCLEAR SAFETY RELATED ACC-18-2IB 3/4--ACC-32-2IB OUALITY CROUP CLASSIFICATIONS ARE INCORPORATED BY REFERENCE' INTO THE UFSAR. A CHANCE TO OUALITY GROUP CLASSIFICATIONS CONSTITUTES A CHANGE TO THE UFSAR. ALL MANUAL VALVE EQUIPMENT IDENTIFICATION NUMBERS ON THIS DIAGRAM ARE PRECEOEO BY ^ SYSTEM DESIGNATOR 'I IA-UNLESS OTHERWISE INDICATED. FROM STATION AIR FIG 34-1. IB-8 REVISION 26 INCORPORATED dun 0s-B42i-eei-ee2 SATISFIEO ECP 818117 BEAVER VALLEY POWER STATION UNIT NO 1 PIPING INSTRUMENTATION DIAGRAM INSTRUMENT AIR CONT 1NST AIR II 1 A A I>>C"<> T" lAAl a7e8-RM-0434-002 \\26

--"--l I t) zo c0 !ss 17 3 f Sul (t I SI PB-i trL',Oc, \\

t+oo T HlfiE

+ E o r a = Tilts

$g l r J

D ? o I o ? o m= s0

  • a

< o F D nl n o < F (D E} 4 I C ? E o I o q Ut B 0 .rD I t{ E A d o N 6 6 o Ifi" I -'-T 3lm BOF 6 s q q d F u EH '0r-EFA o1-

3 E

a J(' a I o o 6 6 = nc' b-r ooo P T u c E-' nc) e 06 . o cm rF ? 43q !D E e o 5l oI (t Et a P u0o

  • qr b-r u

a {p e A @,r E ol o o o 6 O oo B I o{- JA or o D El r o B r* i ? I ott B Egs' r{ oo I z f E

ld og FE z 1 o <

n-B oF pn 5 o 7r I D28 ESE H:E qhl I T f i n 33f; i EAE f;

  • g q 1

I:E H F d Fsil il firEi

i

i ! f ; n E s Esfr r (ts at o{ 6 E c l il{ -ilen *1 a:E* - <- 1 16-l JH (D m D tn n D J-r 'II !o((n f, ltt{- oz. c2 --l z.o iD z.3man 'r H?

ro mi:

i.iC) trt

D F

ND i oz, UI a o{ o ? 7={ st ol (t s TD (r Jo 1 e6es)

i"'iIaaI"'I'"i'i*i'*'i'i'I'i'I'*'i'i'i No. 8700-RM-0513-02 5 6 (4) 180° RECIRCULATION SPRAY HEADERS SEE OETAIL B FOB glglSEAL PIPING IRS-S-1 SUMP STRAINER SUCTION BOX-v CONTAINMENT SUMP REF FIG 1-IIF-3) FIC 13-110-10) FIG I4C-KG-2) RH-320 RH-34A 2*-RS-7-IS3A-O2-> J_ _L IRS-P-2B DETAIL

  • B-OUTSIDE RECIRCULATION SPRAV PUMP SEAL PIPING IRS-P-2A OETAIL

'A1 OUTSIDE RECIRCULATION SPRAY PUMP SEAL PIPING OUALITr GROUP CLASSIFICATIONS ARE 'INCORPORATED BY REFERENCE' INTO THE UFSAR A CHANCE TO DUALITY GROUP CLASSIFICATIONS CONSTITUTES A CHANGE TO THE UFSAR. ALL MANUAL VALVE EOUIPHENT IDENTIFICATION NUMBERS ON THIS DIAGRAM ARE PRECEOEO BY THE SYSTEM DESIGNATOR 'IRS'UNLESS OTHERWISE INOICATEO. FIG NO 13-2 REVISION 6 INCORPORATED DUN 06-B227-8B1-DUN 06-0227-801-DUN 05-0361-001-084 BEAVER VALLEY POWER STATION UNIT NO I NUaeAK aPBUTINS COVUtt FLOW DIAGRAM CONTAINMENT DEPRESSURIZftTION

No. 8700-RM-0546-01 1

i

i iir < i i I>> i

  • i^t i i i

ii r i

i

TTT i 10 2"-CV-l5-15<<-O2 FROM CONTAINMENT o DOME f FIO I2-KF-7I INSIOE REACTOR CONTAINMENT OUTSIDE REACTOR 2--HY-37-IS38-

2--HY-35-15I-02 U. ls I RM KJ/4--MY-3/8--HY-7-N8 2>-Hr-3B153B-FROM CONTAINMENT p. FIG I2-IIE-7I 02 INOKI 0 / SEE ECP BS-B535 ,a. \\"' \\""N " J FOR ITATUS OF PIPEL J5V\\o / >>M0 COMPONtNTS 2VHY-D2-I53B Is ^-2I-HY-ll-l538-a2 Is V2 RM RM CLI53B I SEE ECP 08-0535 FOB STAIUS OF PIPELINES AND COHPONENIS 3/e-T CLIb. ^*MY-S'-IBI-^J A MASS Jji,ci T FLOUMErER OUALITV GROUP CLASSIFICATIONS ARE INCORPORATED BY REFERENCE' INTO THE UFSAR. A CHANGE TO DUALITY CROUP CLASSIFICATIONS CONSTITUTES A CHANCE TO THE UFSAR. ALL MANUAL VALVE EOUIPMEHT IDENTIFICATION NUMBERS ON THIS DIAGRAM ARE PRECEDED BY THE SYSTEM DESIGNATOR 'IHY'UNLESS OTHERWISE INDICATED. FIG NO 46-1 REVISION 7 INCORPORATED OUN 88-0535-001-092 FFNOC NUCLEAR CPCRATIM COPMtt w< 11/10/0 BEAVER VALLEY POWER STATION UNIT NO I FLOW DIAGRAM POST DBA HYDROGEN CONTROL SYSTEM I 8708-RM-0546-01 ul\\rtM-05aS-ei.OGN

I i i

i i i i

  • i i

i r i r r)

  • i
  • i' i' I ri- > I

i r i i

I I

I I -1 r i i' i' I

i

  • r' 1

No. 8700-RM-546-2 3/8#-HT-<<>>3-N'>>-03-\\ 3/8--HY-54-NS-O3-V 1/2' -^T I V SOV "* ^ NON Dlo2\\HY.l03n, tCN H>>-IB2B27 U671i 1/2-PORTIONS OF THIS DRAWING ARE NUCLEAR SAFETY RELATEO REVISION I OF THIS DRAWING SUPERSEDES ALL MANUAL VALVE EOUIPHENT IDENTIFICATION NUHOERS ON THIS OIACftAM ARE PRECEDED BY THE SYSTEM DESIGNATOR 'HI1 UNLESS OTHERWISE OUALITY CROUP CLASSIFICATIONS ARE -INCORPORATED 8V REFERENCE" INTO THE UFSAR A CHANCE TO QUALITY CROUP CLASSIFICATIONS CONSTITUTES A CHANGE TO THE UFSAR. FIG NO 46-2 BEAVER VALLEY POWER STATION UNIT NO 1 NUOSAR OPEKATIHB COflllt FLOW DIAGRAM POST DBA HYDROGEN ANALYZER SYSTEM}}