@ Pennsylvania Power & Light Company Two North Ninth Street

  • Allentown, PA 18101 + 215 I 770'5151 May 20, 1986 Mr. Paul Koval Chief, Operations Section Bureau of Water Quality Management Pennsylvania Department of Environmental Resources 90 East Union Street, Second Floor Wilkes-Barre, PA 18701-3296 SUSQUEHANNA STEAM ELECTRIC STATION DISCHARGE MONITORING REPORT NPDES PERMIT NO. PA 0047325/ APRIL 1986 CCN 741326 FILE R9-8A PLE-8332

Dear Mr. Koval:

Enclosed is a copy of the April 1986 Discharge Monitoring Report for Permit No. PA 0047325. The following information details data and/or noncompliances for some of the permitted outfalls:

Outfall 071: Cooling Tower Blowdown Discharge flows were estimated.

Outfall 079:

Sewage Treatment Plant There were high total suspended solids (TSS) of 40.6 mg/1, av. monthly (limit 30 mg/1) and 141 mg/l (instantaneous maximum limit 60 mg/1). The high TSS levels were attributed to carry-over of aluminum hydroxide from the reactivator waste stream. This noncompliance has been corrected. See Note #1 of DMR 079 for additional information.

Outfall 271: Waste Filter Bypass Because of reactivator pressure problems the reactivator discharge was directed to this outfall only one day in April.

The concentration of TSS was 1,500 mg/1. This noncompliance has been corrected. See Note #1 of DMR 271.

8605270252 860520 l

DR ADOCK 0500 7

[h s

1

1 PLE-6332 May 20, 1986 2

CCN 741326 FILE R9-8A If you have any questions, please call me at (215) 7707889.

Respectfully yours, e-

/f Adh' J one S. Fields ior Environmental Scientist - Nuclear i