Application for Amend to License DPR-65,revising Tech Specs Diesel Fuel Oil Surveillance Requirement.Proposed Change Would Change Yr of ASTM Std Used for Acceptance of Emergency Diesel Generator Fuel Oil.Fee Paid
ML20155J795
Person / Time
Site: Millstone 
Issue date: 06/14/1988
From: Mroczka E
NORTHEAST NUCLEAR ENERGY CO., NORTHEAST UTILITIES
To:
NRC OFFICE OF ADMINISTRATION & RESOURCES MANAGEMENT (ARM)
Shared Package
ML20155J797 List:
References
B12913, TAC-68456, NUDOCS 8806210041
Download: ML20155J795 (3)


Text

%

~

E General Offices

  • [3 t

June 14, 1988 Docket No. 50-336 B12913 Re: 10CFR50.90 U.S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, D.C. 20555 Gentlemen:

Millstone Nuclear Power Station, Unit No. 2 Proposed Revision to Technical Specifications Diesel Fuel Oil Surveillance Reauirement Pursuant to 10CFR50.90, Northeast Nuclear Energy Company (NNECO) hereby proposes to amend its Operating License, DPR-65, by incorporating the changes identified in Attachment 1 into the Technical Specifications of Millstone Unit No. 2.

The proposed change would change the year of the ASTM standard that is used for acceptance of the emergency diesel generator fuel oil.

The existing Technical Specifications require that the fuel oil acceptance limits be in accordance with Table 1 of the 1974 Edition of ASTM D975, when sampled for viscosity, water and sediment.

The request proposes to make the 1978 Edition of ASTM 0975 the governing standard.

The following table summarizes the criteria presented in each of the editions for Grade No. 2-D Diesel Fuel 011:

1974 Edition 1978 Edition Water / Sediment (Volume %)

0.05 Max.

0.05 Max.

Kinematic Viscositv (CST)

Normal 2.0 - 4.3 1.9 - 4.1

- Cloud Pt >10 F 1.8 1.7 Saybolt Viscosity (SUS) 32.6 - 40.1 32.6 - 40.1 l

Test Method (Water / Sediment)

ASTM D1796 ASTM D1796 Test Method (Viscosity)

ASTM D445/02161 ASTM D445/D2161 aAsp

\\

8806210041 880614 0

I g4 PDR ADOCK 05000336

{

\\

p DCD 1

U.S. Nuclear Regulatory Commission B12913/Page 2 June 14, 1988 It can be seen from the above comparison that the only difference between the two editions is the allowable kinematic viscosity limits.

The 1974 edition presents an acceptable range of 2.0 to 4.3 and the 1978 edition requires 1.9 to 4.1.

The upper end of the range is limited by the engine and injection system design and the minimum limit is specified to minimize power loss caused o

by injector pump and injector leakage.

The reduction in Cloud Pt >10 F from 1.8 to 1.7 is in a conservative direction in that it increases the temperature at which cloudiness would be detected in diesel fuel oil.

The reduction from 4.3 to 4.1 is conservative in that it reduces the maximum allowable viscosity, thus ensuring that the engine or injection system limitations are not exceeded.

The reduction from 2.0 to 1.9 is in the direction which would tend to increase system leakage, but the change is relatively insignificant.

The diesel engine manufacturer has been contacted and concurred that no significant difference exists between the two ranges.

The Technical Specification Section affected by this proposed change is 4.8.1.1.2.b, on page 3/4 8-3.

The reference to "Table 1 of ASTM 0975-74" would be changed to "Table 1 of ASTM D975-78".

NNEC0 has reviewed the attached proposed

change, in accordance with 10CFR50.92, and has concluded that it does not involve a significant hazards consideration in that this change would not:

1.

Involve a significant increase in the probability of occurrence or consequences of an accident previously analyzed.

The proposed update in the ASTM Standard used to set acceptance criteria for emergency diesel fuel oil would have no effect on plant operation.

2.

Create the possibility of a new or different kind of accident from any previously analyzed.

The reduction from 2.0 to 1.9 in allowable kinematic viscosity of the diesel fuel oil is in the direction which would tend to increase system leakage but the change is relatively insignificant.

The manufacturer of the diesel generator was contacted and concurs that no significant difference exists between the two viscosity ranges.

3.

Involve a significant reduction in a margin of safety.

A significant reduction in safety will not be realized in the change from one edition of the Standard to a later edition as the only difference is a minor reduction in allowable viscosity.

The Conynission has provided guidance concerning the application of standards in 10CFR50.92 by providing certain examples (51FR7751, March 6,1986).

The change proposed herein most closely resembles example

',1 ),

a purely administrative change to technical specifications: for example a change to achieve consistency throughout the technical specifications, correction of an error, or a change in nomenclature. The change from a 1974 ASTM standard to a 1978 standard has no operational or safety impact on the plant.

U.S. Nuclear Regulatory Commission B12913/Page 3 June 14, 1988 The Millstone Unit No. 2 Nuclear Review Board has reviewed and approved the attached proposed revision and has concurred with the above determinations.

The proposed change is not required to support continued operation.

Therefore, NNEC0 requests the effective date for the proposed change be 60 days after issuance by the NRC Staff.

This will provide adequate time for changes to controlled documents and any applicable training of operational personnel.

In accordance with 10C R50.91(b), we are providing the State of Connecticut with a copy of this proposed amendment.

Pursuant to the requirements of 10CFR170.12(c) enclosed with this amendment request is the application fee of $150.00.

Very truly yours, NORTHEAST NUCLEAR ENERGY COMPANY

<</

E. 'J./hroczka /

Senior Vice President cc:

W. T. Russell, Region I Administrator D. H. Jaffe, NRC Project Manager, Millstone Unit No. 2 W. J. Raymond, Senior Resident Inspector, Millstone Unit Nos. 1, 2 and 3 Kevin McCarthy Director, Radiation Control Unit Department of Environmental Protection Hartford, CT 06116

.-